background image

Residential
Extended Coverage
Quick Response Extended Coverage

Product
Description

1

2

(15 mm)

Orifice
Adjustable
Pendent
Automatic
Sprinkler

The Omega Model EC-20A

Sprinkler is a low profile, aesthetically
pleasing, ceiling mounted sprinkler
that offers a high degree of protection
for human life.  It operates five to six
times faster as a quick response
sprinkler than a standard sprinkler
and features a spray pattern that has
been shown to be more effective in
the control of fires.

The Model EC-20A incorporates

two significant cost-saving features: a
unique deflector that provides a much
greater area of coverage than most
other sprinklers and a special
escutcheon assembly that provides
for 

7

8

" (22.2 mm) of field adjustment

resulting in an easily accomplished,
tight fit against the ceiling.
    The Model EC-20A carries a triple
Listing by Underwriters Laboratories
for use as a Residential Sprinkler, an
Extended Coverage Sprinkler and a
Quick Response Extended Coverage
Sprinkler.  It qualifies for installation in
residential and light hazard
occupancies in accordance with
current NFPA 13, NFPA 13D, or
NFPA 13R Standards.

The Model EC-20A has a

maximum working pressure of
175 psi.

The Model EC-20A is available in

three standard finishes, chrome
plated, brass plated or white painted.
Its mating escutcheon plate is
available in three standard finishes,
chrome plated, brass plated or white
painted.  The Model EC-20A is
shipped with a protective plastic cap.

Technical
Data

Factory Hydro Test:  100% at 500 psi

(34.5 bar)

Standard Finishes:

Sprinkler: brass, chrome plated, white

and off-white painted

Escutcheon Plate:  brass, chrome

plated, white and
off-white painted

Adjustable Range Below Ceiling:

  3

/

8

" to 1

1

/

4

(9.5 mm to 31.8mm)

Highest Allowable Ambient Storage

Temperature:  100

°

F/38

°

C

Length:  2 

7

/

16

(61.9 mm)

Width:    1

1

/

4

(31.8 mm)

Weight:  4.7 oz. 

(133.7 grams)

This cap should be left on during
installation to help protect the EC-20A.
The plastic cap must be removed
before placing the sprinkler system in
service.

Operation:  A fusible alloy pellet is
compressed with a bearing disc into a
copper housing by a ball plunger.
Heat is absorbed by the heat
collecting fins and conducted to the
alloy pellet.  At the rated temperature
the alloy melts, causing the ball
plunger to drop, freeing balls from the
retaining groove.  This movement
allows system water pressure to force
the orifice sealing mechanism and
deflector assembly open. Water is
then discharged in a designed flow
pattern.

Model:  EC-20A

Style:  Pendent (adjustable)

Orifice Size:  

1

/

2

(15  mm)

K Factor:  5.6 

(80.8)

 Nominal

Thread Size:  

 1

/

2

"

(15mm)

 N.P.T.

Temperature Rating:

Residential:  160

°

F/71

°

C

Extended Coverage: 145

°

F/63

°

C

160

°

F/71

°

C

Quick Response Extended
Coverage:

145

°

F/63

°

C

Approvals:   U.L., U.L.C., M.E.A.
                    (Cal. No. 375-75-SA)
Maximum Working Pressure:  175 psi

(12.1 bar)

Manufactured by: Central Sprinkler Company
451 North Cannon Avenue, Lansdale, Pennsylvania 19446

EC-20A       1-98

Omega EC-20A

No. 4-7.0

OBSOLETE

Содержание CENTRAL Omega EC-20A

Страница 1: ...ed brass plated or white painted The Model EC 20A is shipped with a protective plastic cap Technical Data Factory Hydro Test 100 at 500 psi 34 5 bar Standard Finishes Sprinkler brass chrome plated white and off white painted Escutcheon Plate brass chrome plated white and off white painted Adjustable Range Below Ceiling 3 8 to 11 4 9 5 mm to 31 8mm Highest Allowable Ambient Storage Temperature 100 ...

Страница 2: ...0 mm Dia Max escutcheon 2 50 8 mm Dia Max 1 3 4 44 5 mm Dia Min 1 1 16 Max 27 0 mm 7 16 Min 11 1 mm 1 8 3 2 mm Push on Ceiling Escutcheon Note Use this flange for field installation DO NOT HOLD by deflector Pipe Drop Reducing Coupling Dust Cover Finished Ceiling Line O B S O L E T E ...

Страница 3: ...A 13R standards Deviations from these requirements and standards or any alteration to the sprinkler itself will void any warranty made by Central Sprinkler Company In addition installation must also meet local government provisions codes and standards as applicable The system piping must be properly sized to ensure the minimum flow rate at the sprinkler Check for the proper model style orifice siz...

Страница 4: ...to reassemble or otherwise reuse a sprinkler that has operated Replace any sprinkler exhibiting corrosion or damage always use new sprinklers of the same style orifice and temperature rating as replacements Because the discharge pattern is critical to protection of life and property nothing should be hung or attached to the sprinkler unit that would disrupt the pattern Such obstructions must be re...

Отзывы: