background image

General
Description

The Model EC-25 Extended Coverage
Upright Sprinklers (Ref. Figure 1) are
“Control-Mode Extended Coverage
Sprinklers” having a nominal K-factor
of 25.2. Their use is especially advan-
tageous as a means of decreasing the
number of required sprinklers to pro-
tect

occupancies

requiring

an

area/density application of water.

These sprinklers offer maximum cov-
erage areas of 14 feet by 14 feet (196
sq. ft.) which is almost double that of
standard coverage sprinklers used for
similar applications.

Where the FM Approval is utilized, the
EC-25 has successfully undergone
full-scale fire testing at FM for use un-
der  obstructed  ceiling conditions for
area/density design applications.

This

testing has demonstrated that the
Model EC-25 at its extended cover-
age spacings can be installed using
all other standard coverage sprin-
kler criteria. As such, they are ac-
ceptable for all currently recognized
area/density applications

.

Applications for the Model EC-25
Sprinklers are expanding beyond the
current testing. For information regard-
ing additional research fire tests that
may be acceptable to an Authority
Having Jurisdiction please contact the
Technical Services Department.

WARNINGS

The Model EC-25 Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction (e.g., FM Global). Fail-
ure to do so may impair the integrity of
these devices.

The owner is responsible for maintain-
ing their fire protection system and de-

vices in  proper operating  condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.

Sprinkler
Identification
Number

SIN TY9128 - (Upright K=25.2)

Technical
Data

Approvals

FM Approved. UL  and  C-UL  Listed.
(Approvals only apply to the service
conditions indicated in the Design Cri-
teria section.)
NYC under MEA 355-01-E.

Maximum Working Pressure

175 psi (12,1 bar)

Pipe Thread Connection

1 inch NPT or ISO 7-R1

Discharge Coefficient

K = 25.2 GPM/psi

1/2

(362,9 LPM/bar

1/2

)

Temperature Ratings

165°F/74°C or 214°F/101°C

Finish

Natural Brass

Physical Characteristics

Frame . . . . . . . . . . . . .

Brass

Deflector . . . . . . . . . . .

Copper

Compression Screw

. . . . . . . . .

. . . . . . . . . . . . Stainless Steel

Hook . . . . . . . . . . . . . . Monel
Strut . . . . . . . . . . . . . . Monel

Link Assembly . . . .

Solder, Nickel

Button

. . . . . . . . . . . . . Brass

Sealing Assembly . . . . . . . . . .

. . . . . Beryllium Nickel w/Teflon

†

Ejection Spring

. . . . . . . Inconel

Deflector Nut . . . . . . . . . . Brass

Patents

U.S.A. Patent Number 4,580,729 may
be applicable

to

the Model EC-25.

Other patents are pending.

Operation

The fusible link assembly is comprised
of two link halves that are joined to-
gether by a thin layer of solder. When
the rated temperature is reached, the
solder melts and the two link halves
separate allowing the sprinkler to acti-
vate and flow water.

Model EC-25
Extended Coverage Area Density Sprinklers
25.2 K-factor

Technical Services:

Tel: (800) 381-9312 / Fax: (800) 791-5500

Page 1 of 4

TFP213

FEBRUARY, 2002

Customer Service/Sales:

Tel: (215) 362-0700 / (800) 523-6512

Fax: (215) 362-5385

TFP213 (2-13.0)

OBSOLETE

Отзывы: