MODEL PCA090480WH
CHAPTER 3
TROUBLESHOOTING
Section 6: Troubleshooting Direct Digital Controller (DDC)
3-6
March 2013
Page 94
Proprietary/Confidential
© 2013 Twist, Inc.
2 flashes / second
4 flashes then pause
Two or more devices on this
Network have the same
ARC156 network address.
2 flashes / second
On
Exec halted after frequent
system errors or GFBs
halted.
5 flashes / second
On
Exec start-up aborted, Boot
is
running.
5 flashes / second
Off
Firmware transfer in
progress, Boot is running.
7 flashes / second
7 flashes / second
Ten second recovery
alternating
period after brownout.
14 flashes / second 14 flashes / second,
Brownout
Alternating
There are other LEDs that provide information of the condition of the unit.
Digital Output Status
Lights when the digital output is activated.
Analog Output Status
Lights when the analog output is activated.
Rx
Lights when the module receives data from the network segment, there
is
an Rx LED for ports 1 and 2a.
Tx
Lights when the module transmits data over the network segment, there
is
a Tx LED for Ports 1 and 2a.
There are two push buttons available for this unit. One is for Regional Jet
mode, and the other is for Narrow Body mode. Depending on which
pushbutton is depressed the ALC will bring the unit up in the proper mode,
determining by ambient temperature the correct running mode for the present
conditions.
Property of American Airlines