turck TBPN-L1-FDIO1-2IOL Скачать руководство пользователя страница 1

Your Global Automation Partner

TBPN-L1-FDIO1-2IOL

Safety Block I/O Module

Safety manual - Translation 

Содержание TBPN-L1-FDIO1-2IOL

Страница 1: ...Your Global Automation Partner TBPN L1 FDIO1 2IOL Safety Block I O Module Safety manual Translation...

Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...

Страница 3: ...Prerequisites 8 6 2 Reaction time 8 6 3 Safety characteristic data 9 7 Operating instructions 9 7 1 General 9 7 2 Before operation 10 7 2 1 Mounting 10 7 2 2 Connection 11 7 2 3 Address assignment 12...

Страница 4: ...4952 0 F 49 208 4952 264 more turck com www turck com 10 Appendix Designations and abbreviations 17 11 Appendix Function tests 17 12 Appendix Document history 17 13 Appendix Technical data 18 14 Appen...

Страница 5: ...ke sure that this is the latest version of the safety manual at www turck com The German version is considered the definitive document Every care was taken in the produc tion of the translations of th...

Страница 6: ...Link slots each provide one digital in output at pin 2 The non safety ports C4 C5 and C7 can be switched off safe via the internal outputs FSO0 and FSO1 see 4 5 Block diagram on p 7 This allows a safe...

Страница 7: ...fety in output C4 DXP8 9 standard in outputs safe shutdown via FSO0 C5 DXP10 11 standard in outputs safe shutdown via FSO0 possible C6 IOL IO Link port1 C7 IOL IO Link port2 safe shutdown via FSO1 pos...

Страница 8: ...rt a LOW state 0 to the logic 5 2 Fatal Error The following errors lead to Fatal Error and thus to the safe state Incorrect wiring at the output e g capacitive load energetic recovery Incorrect power...

Страница 9: ...ww turck de SIL The device must only be mounted installed operated and maintained by trained and quali fied personnel The device is not specified for a certain application Make sure that application s...

Страница 10: ...ingle safety component Carry out a validation of the safety category for the complete system depending on the selec tion of the used safety components 7 2 1 Mounting ATTENTION Mounting on uneven surfa...

Страница 11: ...s with PELV voltage according to EN50178 PELV Assure that the maximum output voltage of 60 V is not exceeded even in case of an error Connect the device to the power supply according to the pin assign...

Страница 12: ...ing The safety function of the safe channels can only be configured via the software Turck Safety Configurator After the configuration the device generates a CRC and a configuration protocol This prot...

Страница 13: ...et Traffic 100 Mbps yellow Link established 10 Mbps yellow blinking Ethernet Traffic 10 Mbps PWR green Voltage OK red Power supply faulty ERR green No diagnostics red Diagnostics pending BUS green Act...

Страница 14: ...hannel active and overload of supply input only 12 15 green IO Link communication or DI active red Error 0 7 red all blinking alternating Fatal Error WINK white flashing Helps to localize the module i...

Страница 15: ...he respective output pin 2 8 5 DXP 8 6 IO Link 1 BK GND V2 2 BU GND V1 3 GNYE FE 4 BN 24 VDC V1 5 WH 24 VDC V2 3 4 5 2 1 w v 3 4 5 2 1 X1 X2 4 1 3 2 5 v 1 Vaux1 T1 2 FDI T2 3 GND V1 4 FDI T1 5 T2 4 1...

Страница 16: ...BPN L1 Safe electronic input OSSD 2 FDI T2 1 VAUX1 3 GND 4 FDI T1 5 n c OSSD TBPN L1 9 2 Outputs Safe output PP switching 2 n c 1 n c 3 GND V1 4 FDO 5 n c TBPN L1 For PP switching outputs connect the...

Страница 17: ...qualified personnel A suggested function test consists of the following steps Step Action 1 Switch every safety related input at least once a year 2 Control the switching behavior by monitoring the o...

Страница 18: ...Max cable length max 1 F at 150 limited by line capacity Test pulse typ 0 6 ms Test pulse max 0 8 ms Interval between 2 test pulses 900 ms for static inputs Safety inputs for OSSD Signal voltage low l...

Страница 19: ...perating storage temperature 40 C to 70 C 40 to 158 F Protection class IP65 IP67 IP69K Housing material Fiber glass reinforced Polyamide PA6 GF30 Window material Lexan Tests Vibration test according t...

Страница 20: ...t puj cymi normami EMV Richtlinie EMC Directive Directive EMC Directiva CEM Direttiva EMC compatibilit elettromagnetica Dyrektywa EMC 2014 30 EU 26 2 2014 EN 61000 6 2 2005 EN 61000 6 4 2007 A1 2011 E...

Страница 21: ...28 subsidiaries and over 60 representations worldwide www turck com D301391 2018 01 D301391 1801...