Safety Manual - Translation

TB…-L…-FDIO1-2IOL

Safety Block I/O Modules

Содержание TBPN-L FDIO1-2IOL Series

Страница 1: ...Your Global Automation Partner Safety Manual Translation TB L FDIO1 2IOL Safety Block I O Modules...

Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...

Страница 3: ...overview 11 4 2 1 Type label 13 4 3 Switches and connectors 14 4 4 Block diagram 16 5 Safety function 17 6 Safety planning 18 6 1 Prerequisites 18 6 2 Reaction time 18 6 3 Safety characteristic data 1...

Страница 4: ...37 10 Appendix designations and abbreviations 38 11 Appendix function tests 38 12 Appendix document history 38 13 Appendix technical data 39 13 1 Derating 41 14 Appendix directives and standards 42 14...

Страница 5: ...ies to the following Turck safety modules PROFIsafe module n TBPN L1 FDIO1 2IOL n TBPN LL FDIO1 2IOL CIP Safety devices n TBIP L4 FDIO1 2IOL n TBIP L5 FDIO1 2IOL n TBIP LL FDIO1 2IOL 1 2 Explanation o...

Страница 6: ...8 4952 0 F 49 208 4952 264 more turck com www turck com 1 3 Additional documents The following additional documents are available online at www turck com n Data sheet n Declarations of conformity curr...

Страница 7: ...evice The installation instructions must be observed n For trouble free operation the device must be properly transported stored installed and mounted n For the release of safety circuits in accordanc...

Страница 8: ...disconnect and connect circuits when no voltage is applied n Only operate the switches if no voltage is present n Connect the metal protective cover to the equipotential bonding in the Ex area n Ensu...

Страница 9: ...2 00 2022 07 9 3 Safety Integrity Level Performance Level Category The devices are rated for applications rated to n SIL3 according to EN 61508 and EN 62061 n Category 4 PLe according to EN ISO 13849...

Страница 10: ...tended use The TB L FDIO1 2IOL are decentralized safety modules for PROFIsafe or CIP Safety The devices collect field signals and forward them safely to a PROFIsafe or CIP Safety master Due to an exte...

Страница 11: ...8 230 4 9 07 6 0 24 60 4 2 38 6 3 0 25 30 2 1 19 24 0 95 yellow C7 P2 C6 C5 C4 C3 P1 C2 C1 C0 X2 X1 Fig 1 TBPN L1 FDIO1 2IOL mm Inch 34 8 1 37 6 3 0 25 217 9 8 58 230 4 9 07 6 0 24 60 4 2 38 6 4 0 25...

Страница 12: ...3 0 25 30 2 1 19 24 0 95 red C7 P2 C6 C5 C4 C3 P1 C2 C1 C0 X2 X1 Fig 3 TBIP L4 FDIO1 2IOL mm Inch 38 8 1 53 6 3 0 25 218 8 58 230 4 9 07 6 0 24 60 4 2 38 6 3 0 25 30 2 1 19 24 0 95 red C7 P2 C6 C5 C4...

Страница 13: ...7 Type label TBPN LL FDIO1 2IOL TBIP L4 FDIO1 2IOL Ident No 100000360 HW Charge code YoC Hans Turck GmbH Co KG D 45466 M lheim a d Ruhr www turck com Made in Germany TBIP L5 FDIO1 2IOL Ident No 681405...

Страница 14: ...Link port 2 safe shutdown via FSO 1 possible F Address Rotary coding switch for address setting for PROFIsafe F address setting P1 Ethernet 1 P2 Ethernet 2 FE Functional earth TBPN LL FDIO1 2IOL Desig...

Страница 15: ...ssible IP Address Rotary coding switch for address setting last byte of the IP address for the safe function unit P1 Ethernet 1 P2 Ethernet 2 FE Functional earth TBIP LL FDIO1 2IOL Designation Meaning...

Страница 16: ...tern DXP9 DXP8 DXP11 DXP10 DXP13 DI12 C Q DXP15 DI14 C Q IO Link Port1 IO Link Port2 PM PP FDI0 FDI1 FDI2 FDI3 FDX4 FDX5 FDX6 FDX7 Fig 11 Block diagram TBPN L FDIO1 2IOL 2 4 C0 X0 V1 2 4 C1 X1 4 2 1 5...

Страница 17: ...ergency switches protective door switches n Sensors with OSSD switching outputs n Antivalently switching OSSD sensors The two safe SIL3 outputs can be used PP or PM switching Safe Status In the safe s...

Страница 18: ...dered eventually Please find the respective information in the tech nical data of the respective devices Further information about the reaction time can be found in the online help for the Turck Safet...

Страница 19: ...h regard to functional safety Turck must be notified immediately and the devices must be returned immediately to Hans Turck GmbH Co KG Witzlebenstra e 7 45472 M lheim an der Ruhr Germany In case of de...

Страница 20: ...ark ignition For use in Zone 2 and Zone 22 Only install the device if there is no potentially explosive atmosphere present Observe requirements for Ex approval Unscrew the housing Use Torx T8 screwdri...

Страница 21: ...evice on a flat mounting surface Use two M6 screws to mount the device The device can be screwed onto a flat mounting plate Attach the module to the mounting surface with two M6 screws The maximum tig...

Страница 22: ...disconnected from the mains supply WARNING Incorrect or defective power supply unit Danger to life due to dangerous voltages on touchable parts Only use for SELV or PELV power supplies in accordance...

Страница 23: ...9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 x 100 x 10 x 1 Memory Fig 15 Rotary coding switches at the device In the delivery state the rotary switches are set to 000 0 0 0 Address 000 a...

Страница 24: ...ord is transmitted in plain text NOTICE Inadequately secured devices Unauthorized access to sensitive data Change password after first login Turck recommends using a secure password Adapt the password...

Страница 25: ...Service Tool etc n Secondary IP Address depending on application possibly without function must then be 0 0 0 0 NOTE The Secondary IP address can only be set by using the web server of the device Set...

Страница 26: ...word is transmitted in plain text NOTICE Inadequately secured devices Unauthorized access to sensitive data Change password after first login Turck recommends using a secure password Adapt the passwor...

Страница 27: ...00 2022 07 27 Setting the Secondary IP Address via the web server The Secondary IP Address is not used in the device and should always be set to 0 0 0 0 Fig 19 Web server setting the Secondary IP Addr...

Страница 28: ...hich the devices are installed 7 1 6 Configuring The safety function of the safe channels can only be configured via the Turck Safety Configur ator software After configuration the device generates a...

Страница 29: ...Input active Green flashing Self test input Red flashing Cross Connection Red Discrepancy LED 4 7 C2 C3 or X2 X3 Meaning Channel is input Channel is output Off Input active Output inactive Green Inpu...

Страница 30: ...ng channel in SIO mode DI Off No input signal Green Digital input signal active LED DXP LED 13 C6 X6 LED 15 C7 X7 Meaning input Meaning output Off Input inactive Output inactive Green Input active Out...

Страница 31: ...Net IP server Device is in the Idle or Standby State n Use without safety controller Device is protected mode an EtherNet IP client is currently connec ted to the standard I Os Red Critical fault devi...

Страница 32: ...49 208 4952 264 more turck com www turck com 7 2 2 Output error behavior In case of an error a switched off output can be switched on for 1 ms 7 2 3 Decommissioning The decommissioning is described i...

Страница 33: ...X 2 RX 3 TX 4 RX ange FE v 4 1 3 2 XF2 1 RX 2 TX 3 RX 4 TX ange FE Fig 22 Pin assignment Ethernet connector XF1 Fig 23 Pin assignment Ethernet connector XF2 8 2 Power supply TBPN L1 1 BK GND V2 2 BU G...

Страница 34: ...1 3 2 4 FE XD1 XD2 1 24VDC V1 2 GND V2 3 GND V1 4 24VDC V2 FE Fig 27 Pin assignment voltage supply connectors M12 5 pin 8 3 Safety inputs FDI 4 1 3 2 5 v 1 Vaux1 T1 2 FDI T2 3 GND V1 4 FDI T1 5 T2 Fi...

Страница 35: ...4 DI DO 5 FE Fig 30 Pin assignment C4 C5 or X4 X5 8 6 IO Link channels 4 1 3 2 5 v 1 Vaux1 2 DI DO 3 GND V1 4 C Q 5 GND V1 Fig 31 Pin assignment IO Link port IOL1 C6 or X6 4 1 3 2 5 v 1 FSO1 2 DI DO 3...

Страница 36: ...up when actu ated Use e g for door monitoring with magnetic reed contacts n Example 2 The LEDs of the inputs are off when actuated and light up when not actu ated Use as programming for two hand swit...

Страница 37: ...val of the outputs will change the performance level The software and the online help of the software contain further information Safe output PP switching 2 n c 1 n c 3 GND V1 4 FDO 5 n c TB L For PP...

Страница 38: ...witching behavior by monitoring the output circuits 3 Observe the maximum duty cycle and the total operation time depending on the selected PFD value 4 If the maximum duty cycle is reached Request the...

Страница 39: ...L FDIO1 2IOL n ID 100027260 n YoC According to device labeling Power supply V1 incl electronics supply 24 VDC V2 24 VDC only through connected Current feedthrough n X1 to X1 7 8 9 A n XD1 tot XD2 M12...

Страница 40: ...rating 41 Max tolerated test pulse width 1 ms Min interval between two test pulses 12 ms at 1 ms test pulse width 8 5 ms at 0 5 ms test pulse width 7 5 ms at 0 2 ms test pulse width Safety outputs Sui...

Страница 41: ...lass reinforced Polyamide PA6 GF30 Housing color black Material connectors brass nickel plated Window material Lexan Material screw 303 stainless steel Material label Polycarbonate Halogen free Yes Mo...

Страница 42: ...ion regulation n Safety rules and safety regulations according to the actual state of the art 14 2 Cited standards Standard Title DIN EN ISO 13849 1 2016 06 Safety related parts of control systems EN...

Страница 43: ...20 ATEX 264795 X UKEX approval no TURCK Ex 20002HX II 3 G II 3 D Ex ec IIC T4 Gc Ex tc IIIC T115 C Dc IECEx approval no IECEx TUN 20 0010X Ex ec IIC T4 Gc Ex tc IIIC T115 C Dc Ambient temperature Tamb...

Страница 44: ...S A S 11 rue de Courtalin Bat C Magny Le Hongre F 77703 MARNE LA VALLEE Cedex 4 www turckbanner fr Great Britain TURCK BANNER LIMITED Blenheim House Hurricane Way GB SS11 8YT Wickford Essex www turckb...

Страница 45: ...w turck ru Sweden Turck Sweden Office Fabriksstr ket 9 433 76 Jonsered www turck se Singapore TURCK BANNER Singapore Pte Ltd 25 International Business Park 04 75 77 West Wing German Centre 609916 Sing...

Страница 46: ...Over 30 subsidiaries and over 60 representations worldwide www turck com 100000664 2022 07 100000664...