D301271 1013 - FGEN - multi protocol
3-11
Address assignment
3.5.7
Addressing via mode PGM-DHCP
switch position:
600
The device sends DHCP-requests until a IP-address is assigned (DHCP-server, PROFINET-controller).
The assigned IP-address is stored to the device and the DCHP-client is stopped.
Even after a restart of the device, the device sends no further DHCP-requests.
PROFINET
This mode assures a PROFINET-compliant operation of the modules.
3.5.8
F_Reset (Factory Reset)
switch position:
900
Setting 900 sets all device-settings back to the default values and deletes all data in the device's internal
flash.
Note
If a DHCP-server is used within the network, problems may occur during IP-assignment.
In this case, both, the DHCP-server as well as the PROFINET-controller (vie DCP), try an IP-
address-assignment.
Note
Setting 900 is no operation mode! Please set the device to another mode after having reset
the IP address to the default values.
Содержание FGEN-AIM Series
Страница 1: ...USER MANUAL FGEN AIM stations with multi FUNTIONALITY Sense it Connect it Bus it Solve it...
Страница 8: ...D301271 1013 FGEN multi protocol vi...
Страница 14: ...About this manual D301271 1013 FGEN multi protocol 1 6...
Страница 42: ...Digital inputs FGEN IM16 x001 D301271 1013 FGEN multi protocol 4 4...
Страница 46: ...Digital outputs FGEN OM16 x001 D301271 1013 FGEN multi protocol 5 4...
Страница 104: ...Application example FGEN for EtherNet IP with Allen Bradley PLC and RS Logix 5000 D301271 1013 FGEN multi protocol 8 14...
Страница 126: ...Implementation of Modbus TCP D301271 1013 FGEN multi protocol 9 22...
Страница 186: ...Guidelines for Electrical Installation D301271 1013 FGEN multi protocol 13 8...