Guidelines for Electrical Installation
D301239 1013 - BL67 AIDA PROFINET
7-2
7.1
General notes
7.1.1
General
Cables should be grouped together, for example: signal cables, data cables, heavy current cables,
power supply cables.
Heavy current cables and signal or data cables should always be routed in separate cable ducts or
bundles. Signal and data cables must always be routed as close as possible to ground potential surfaces
(for example support bars, cabinet sides etc.).
7.1.2
Cable routing
Correct cable routing prevents or suppresses the reciprocal influencing of parallel routed cables.
Cable routing inside and outside of cabinets
To ensure EMC-compatible cable routing, the cables should be grouped as follows:
Various types of cables within the groups can be routed together in bundles or in cable ducts.
Group 1:
shielded bus and data cables
shielded analog cables
unshielded cables for DC voltage
≤
60 V
unshielded cables for AC voltage
≤
25 V
Group 2:
unshielded cables for DC voltage > 60 V
and
≤
400 V,
unshielded cables for DC voltage > 25 V
and
≤
400 V,
Group 3:
unshielded cables for DC and AC voltages
> 400
The following group combination can be routed only in separate bundles or separate cable ducts (no
minimum distance apart):
Group 1/Group 2
The group combinations:
Group 1/Group 3 and Group 2/Group 3
must be routed in separate cable ducts with a minimum distance of 10 cm apart. This is equally valid for
inside buildings as well as for inside and outside of switchgear cabinets.
Содержание BL67-GW-PN-AC
Страница 1: ...USER MANUAL PROFINET AIDA gateway BL67 GW PN AC...
Страница 6: ...D301239 1013 BL67 AIDA PROFINET iv...
Страница 20: ...PROFINET D301239 1013 BL67 AIDA PROFINET 3 4...
Страница 66: ...Technical features D301239 1013 BL67 AIDA PROFINET 4 46...
Страница 94: ...Guidelines for station planning D301239 1013 BL67 AIDA PROFINET 6 6...
Страница 112: ...Mounting and mounting instructions D301239 1013 BL67 AIDA PROFINET 8 10...
Страница 113: ...D301239 1013 BL67 AIDA PROFINET 9 1 9 Appendix 9 1 Nominal current consumption of modules on Ethernet 9 2...
Страница 116: ...Appendix D301239 1013 BL67 AIDA PROFINET 9 4...