Guidelines for Electrical Installation
D301239 1013 - BL67 AIDA PROFINET
7-8
7.5
Potential compensation
Potential differences can occur between installation components that are in separate areas if these
are fed by different supplies,
have double-sided conductor shields which are grounded on different installation components.
A potential-compensation cable must be routed to the potential compensation.
A potential compensation cable must have the following characteristics:
Low impedance. In the case of compensation cables that are routed on both sides, the
compensation line impedance must be considerably smaller than that of the shield connection
(max. 10% of shield connection impedance).
Should the length of the compensation cable be less than 200 m, then its cross-section must be at
least 16 mm
2
/0.025 inch
2
. If the cable length is higher than 200 m, then a cross-section of at least 25
mm
2
/ 0.039 inch
2
is required.
The compensation cable must be made of copper or zinc coated steel.
The compensation cable must be connected to the protective conductor over a large surface area
and must be protected against corrosion.
Compensation cables and data cables should be routed as close together as possible, meaning the
enclosed area should be kept as small as possible.
7.5.1
Switching inductive loads
In the case of inductive loads, a protective circuit on the load is recommended.
7.5.2
Protection against Electrostatic Discharge (ESD)
Danger
Never use the shield as a potential compensation.
Figure 7-3:
potential
compensation
Attention
Electronic modules and base modules are at risk from electrostatic discharge when
disassembled. Avoid touching the bus connections with bare fingers as this can lead to ESD
damage.
Reference potential
Potential compensation cable
Shield
Reference potential
Содержание BL67-GW-PN-AC
Страница 1: ...USER MANUAL PROFINET AIDA gateway BL67 GW PN AC...
Страница 6: ...D301239 1013 BL67 AIDA PROFINET iv...
Страница 20: ...PROFINET D301239 1013 BL67 AIDA PROFINET 3 4...
Страница 66: ...Technical features D301239 1013 BL67 AIDA PROFINET 4 46...
Страница 94: ...Guidelines for station planning D301239 1013 BL67 AIDA PROFINET 6 6...
Страница 112: ...Mounting and mounting instructions D301239 1013 BL67 AIDA PROFINET 8 10...
Страница 113: ...D301239 1013 BL67 AIDA PROFINET 9 1 9 Appendix 9 1 Nominal current consumption of modules on Ethernet 9 2...
Страница 116: ...Appendix D301239 1013 BL67 AIDA PROFINET 9 4...