D301087 1211 - BL20 CANopen
4-11
Connections for data cables to BL20-GW-CANOPEN
The passive bus termination must be applied externally if the BL20 gateway is the last station in the bus
structure.
Table 4-7:
List of connecting
leads for direct
wiring
Designation
Meaning
CAN_L
Inverted data signal (dominant low)
GND
Ground (optional)
SHLD
Shielding (see below)
CAN_H
Non-inverted data signal (dominant high)
Attention
If the gateway is wired up directly, then the bus connection must be shielded (e.g. with the
help of a BL20-SCH-1 clamp).
Figure 4-5:
Shielding connec-
tion for an BL20-
GW-CANOPEN
Attention
No compensating current should flow through the shielding.
To achieve this, a reliable system of equipotential bonding must be installed.
Note
Equipotential bonding impedance
≤
1/10 shielding impedance
Содержание BL20-GW-CANOPEN
Страница 1: ...BL20 USER MANUAL FOR CANopen...
Страница 4: ......
Страница 8: ...D301087 1211 BL20 CANopen iv...
Страница 14: ...About this Manual D301087 1211 BL20 CANopen 1 6...
Страница 24: ...BL20 Philosophy D301087 1211 BL20 CANopen 2 10...
Страница 54: ...BL20 Communication in CANopen D301087 1211 BL20 CANopen 5 2...
Страница 68: ...Guidelines for Station Planning D301087 1211 BL20 CANopen 6 14...
Страница 82: ...BL20 Approvals for Zone 2 Division 2 D301087 1211 BL20 CANopen 8 2...
Страница 83: ...D301087 1211 BL20 CANopen 8 3...
Страница 84: ...BL20 Approvals for Zone 2 Division 2 D301087 1211 BL20 CANopen 8 4...
Страница 85: ...D301087 1211 BL20 CANopen 8 5...
Страница 86: ...BL20 Approvals for Zone 2 Division 2 D301087 1211 BL20 CANopen 8 6...
Страница 92: ...Glossary D301087 1211 BL20 CANopen 9 6...
Страница 94: ...Index D301087 1211 BL20 CANopen 10 2...