6. SPECIFICATION OF INPUTS AND OUTPUTS
6.11 CAN interface
6.11.1 Pinout
Connector
Pin no.
Note
Function
C1
13
1
CAN Interface 0 – High Line
C1
5
1
CAN Interface 0 – Low Line
C1
12
1
CAN Interface 1 – High Line
C1
4
1
CAN Interface 1 – Low Line
C1
11
1, 3
CAN Interface 2 – High Line
C1
3
1, 3
CAN Interface 2 – Low Line
C1
24
1, 2, 3
CAN Interface 3 – High Line – ISOBUS
C1
32
1, 2, 3
CAN Interface 3 – Low Line – ISOBUS
Note 1
According to ISO 11898
Note 2
According to ISO 11783
Note 3
Only for Vision 312Plus products
6.11.2 Functional description
CAN implements a bidirectional twisted pair bus for high speed serial data transfer up to 1 Mbit/s. The
bus must be terminated with 120 Ω at each end to prevent wave reflection. If the Vision 312 device is
connected at the end of a CAN bus, it is necessary to use external termination resistors as the device is
not equipped with internal termination. See figure
below for details.
Note that a common ground (chassis) or a proper ground connection is necessary for CAN operation.
When connecting with an external device (for example, a PC with CAN interface for downloading soft-
ware), make sure that the maximum voltage ratings are not violated when connecting to or disconnecting
from the CAN bus.
The CAN interface is fully ISO 11898-2/-5 compliant.
6.11.3 CAN 3
Due to the requirements of the ISOBUS standard [3], the internal protection circuit of CAN 3 differs from
the other CAN interfaces of the device. To achieve good RF immunity, it is recommended to use CAN 3
with external termination. It is recommended to implement the termination based on the equivalent circuit
shown in figure
below.