7 Commands for parameter set up
53
<ch>: 0 ~ F(Hexadecimal) for channel.
7-7 Setting of the local mode data
Command SHPF<ch><off>
Set the home position offset.
When you detect home position by command "GTHPx", home
position searching starts from the distance of offset value from
current home position.
Argument <off>
offset
0 ~ 99,999
Initial value 100
Reply Nothing
Example SHPF51000 Set 1,000 to the offset of CH5.
Remarks Only remote mode.
Command SHPF?<ch>
Confirm the home position offset.
Reply dddd (4-digit)
Example SHPF?5 replty: 0100
Remarks
Command S<mode><ch><pos>
Set the various values to be used in local mode.
Argument
<mode>
Mode
REL/ Value of the relative movement by START button in
REL mode.
ABS/ Value of the absolute movement by START button in
ABS mode.
PRS/ Value to be set by PRESET button in SCAN mode.
<pos>
Set posotion
-2,147,483,647 ~ +2,147,483,647
Initial value REL: +10000 ABS: 0 PRS: 0
Reply Nothing
Example
SPRSB+10000 Set +10000 to the preset value of CH11 for when PRESET button will
be pressed.
Remarks Only remote mode.
Command S<mode>?<ch>
Confirm the various values to be used in local mode.
Argument <mode>
Mode
REL/ Value of the relative movement by START button in REL
mode.
ABS/ Value of the absolute movement by START button in
ABS mode.
PRS/ Value to be set by PRESET button in SCAN mode.
Reply
±
ddddddd (Signed integer 7 digits or more)
Example
SPRS?1 reply: +0002500
Preset value is +2500, when PRESET button on the CH1 is pressed.
Remarks