7 Commands for parameter set up
49
<ch>: 0 ~ F(Hexadecimal) for channel.
<
7-3 Acceleration and deceleration Rate Setting
Command SPDAL?
Display the speed that has been set to the motor that displays in LCD.
Reply
<0123>/<sp>dddddd/<sp>dddddd/<sp>dddddd/<sp>dddddd
<0123>
Expressed in hexadecimal notation of four-digit channel which is
displayed on the display. Display the following parameters in this order.
<sp>
H/HSPD M/MSPD L/LSPD
Display the speed that has been set to the motor.
dddddd
Display the speed as pps.
Example SPDAL? Reoky: 0123/M000650/H010000/L000100/M000650
Remarks
If the motor is in operation, display of dddddd part appears in 000000.
Command RTE<ch><cd>
Set the code in the acceleration and deceleration rate.
Argument <cd>
acceleration and
deceleration code
Enter the code a number between 0 - 115.
Refer to page 48 about the relationship of acceleration
and deceleration of the actual code.
Initial value 013
Reply Nothing
Example RTE040 Set to 40 for the acceleration and deceleration rate of CH0.
Remarks Only remote mode. And the motor is stopped.
Command RTE?<ch>
Confirm the code in the acceleration and deceleration rate.
Reply DDD (
3-digit integer
)
Example RTE?0 reply: 050 The acceleration and deceleration rate of CH0 is 50.
Remarks
Command RRATE<ch><rrt>
Set the acceleration / deceleration rate as a real number.
Argument <rrt>
Rate value
1000~0.00125
Initial value 300.000
Reply none
Example RTE02.5 Set the acceleration / deceleration rate of channel 0 to 2.5ms / 1000pps.
Remarks Valid only when the motor is stopped and when remote, see the next page for details.
Command RRATE?<ch>
Check the acceleration / deceleration rate with a real number.
Reply DDD .ddd (real number with 3 decimal places)
Example
RRATE? 0 reply: 2.500
The acceleration / deceleration rate for channel 0 is 2.5ms / 1000 pps .
Remarks