![TSUJI ELECTRONICS PM16C-16 Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/tsuji-electronics/pm16c-16/pm16c-16_user-manual_1178501041.webp)
7 Commands for parameter set up
40
7-2 Moving speed setting
<ch>: 0 ~ F(Hexadecimal) for channel.
Command HOLD?<ch>
Confirm the output of hold off signal.
Reply
OFF/ Enable the output of hold off signal.
ON/ Disable the output of hold off signal.
Example HOLD?3 reply: ON CH3’s hold off signal has disabled.
Remarks
Command STOPMD<ch><pb><ls>
Set the way to stop motor.
Argument
<pb> Stop by STOP botton
0/ deceleration stop
1/ emergency stop
<ls>
Stop by limit switch
Initial value <pb>:0 <ls>:0
Reply Nothing
Example
STOPMD001 In CH0, the STOP botton is set to the deceleration stop, and LS switch is
set to the emergency stop.
Remarks Only remote mode.
Command STOPMD?<ch>
Confirm the way to stop motor.
Reply <pb><ls> Please refer to ”STOPMDx” for meaning.
Example STOPMD?3 reply: 01
Remarks
Command SPD<sp><ch><pps>
Set the speed for LSPD, MSPD, HSPD.
Argument
<sp>
Speed
L/ LSPD
M/ MSPD
H/ HSPD
Select the speed at which you want to set.
<pps>
Speed (pps)
I set the speed at 1 ~ 5,000,000 pps units.
(pps: pulses per second)
Initial value LSPD/10pps MSPD/650pps HSPD/3,700pps
Reply Nothing
Example
SPDH02000 Set the speed to 2000pps for when ch0's HSPD is selected.
SPDLF50 Set the speed to 50pps for when chF's LSPD is selected.
Remarks Only remote mode. And the motor is stopped.