MODEL 8681 SUREFLOW
™
ADAPTIVE OFFSET CONTROLLER
INSTALLATION INSTRUCTIONS
WARNING:
The Model 8681 Adaptive Offset Controller must be wired to 24 VAC only. Wiring the unit to
110 VAC will cause serious unit damage and void the warranty.
These installation instructions guide the installer through the installation of the TSI Model 8681 SureFlow
™
Adaptive Offset Controller and all TSI options. Some options may not have been provided by TSI, so please
review those product installation instructions. Please read these instructions thoroughly before beginning
installation.
Overview
Figure 1 provides an overview of the various components installed. The order the components are installed is
not important. The building prints will define the location of the dampers, flow stations, and pressure sensor. If
no location is defined, these instructions show “typical” installation locations.
Figure 1: Typical Laboratory Installation