OPERATOR’S MANUAL
ISO
6
Version 4 UL 2_3 Manual
CALIBRATIONS / 95
6011258 Rev C
5. Start the tractor and engage the hydraulic system.
6. Run the engine at normal operating speed until the hydraulic
fluid is at normal operating temperature.
7. Press the
START
button.
8. The valve calibration immediately starts.
9. Keep the hydraulics engaged until the calibration is
complete. The calibration may take a minute up to several
minutes. Each calibration step is monitored at the bottom of
the display.
10. When the calibration is complete, the control shuts down
automatically. All calibration data is automatically stored.
Figure 64
Valve Calibration
LIMIT OUTPUT (GRANULAR)
It is necessary to limit the output of the control channel before
running a valve calibration in the event that system capacities
are greater than the actual desired capacities. These features
allow setting the maximum output of the channel to prevent
machine damage.
TO PERFORM A LIMIT OUTPUT:
1. At the Valve Calibration screen, press the
LIMIT OUTPUT
button to access the Limit Output screen.
2.
Move the implement to the “raised” position.
3. Apply the tractor brakes and lock in the applied position.
Содержание DICKEY-john INTELLIAG ISO6
Страница 111: ...OPERATOR S MANUAL 106 SECTION CONTROL ISO6 Version 4 UL 2_3 Manual 6011258 Rev C Figure 71 Assigning Clutch Sections ...
Страница 115: ...OPERATOR S MANUAL 110 SECTION LINKING ISO6 Version 4 UL 2_3 Manual 6011258 Rev C Figure 74 Linking Sections ...
Страница 197: ...OPERATOR S MANUAL 192 VERSION INFORMATION ISO6 Version 4 UL 2_3 Manual 6012487 Rev A ...
Страница 205: ...OPERATOR S MANUAL 200 DIAGNOSTICS ISO6 Version 4 UL 2_3 Manual 6011258 Rev C Figure 154 Manual Open of a Channel ...