MODEL 800243 or 800326

 

THROUGH-THE-WALL ROOM PRESSURE SENSOR 

 

INSTALLATION INSTRUCTIONS 

 
 

WARNING 

THE MODEL 800243/800326 ROOM PRESSURE SENSORS MUST BE WIRED TO 24 VAC ONLY.  
WIRING THE UNIT TO 110 VAC 

WILL CAUSE

 SERIOUS DAMAGE TO THE UNIT AND VOID THE WARRANTY.  

The pressure sensor must be mounted through-the-wall between the controlled space and referenced space. 
 
These installation instructions guide the installer through the installation of the TSI Model 800243/800326 
Through-the-Wall Room Pressure Sensor. Unless specified otherwise, figures and instructions apply to all 

versions. Please read these instructions thoroughly before beginning installation. 

 

 

 

 

This product is classified by UL as to fire resistive properties only. See UL File R15545. 

 

 

Figure 1

Typical Installation

  

Component List 

Part Number 

Qty  Description 

800243 

or 

800326

 

1

 

Pressure sensor 
with cable

 

 

 

 

Содержание 800243

Страница 1: ...ounted through the wall between the controlled space and referenced space These installation instructions guide the installer through the installation of the TSI Model 800243 800326 Through the Wall Room Pressure Sensor Unless specified otherwise figures and instructions apply to all versions Please read these instructions thoroughly before beginning installation This product is classified by UL a...

Страница 2: ... screw that holds the sensor base to the pressure sensor Figure 2 Mod Remove pressure sensor and store in a safe place From the side of the wall the sensor will be mounted slide the sensor tube through the wall Mark the tube where it is flush with wall Remove sensor tube and cut tube 1 8 inch shorter than flush marking NOTE If 12 sensor tube needs to be extended use same size or larger diameter tu...

Страница 3: ...e 4 Pressure Sensor Mounting WARNING DO NOT connect more than 24 VAC to any terminal CEILING DUMMY COVER CONTROLLED SPACE REFERENCE SPACE TYPICALLY A HALLWAY BLACK FIRE SEALANT RING MUST INSERT INTO 2 HOLE PRESSURE SENSOR THE DISTANCE BETWEEN CEILING DOOR JAMB WALL ...

Страница 4: ...o Control cables should cross power cables at a 90 degree angle o Use a consistent color code to maintain polarity o Control signals require home run wiring star configuration DO NOT daisy chain control wires or use a series configuration Refer to the wiring diagram Figure 5 for proper wiring installation Power Requirements Through the Wall Sensor Each 24 VAC 50 60 Hz 3VA WARNING Sensor must be wi...

Отзывы: