APM 

CT Meter 

CAUTION: Risk of Danger 

Read complete instructions prior to installation and 
operation of the unit 

CAUTION: 

Risk of electric shock 

Before installation, read the Safety Warnings overleaf. 

Intended Use: The APM has been specifically designed for engineers requiring an effective way to monitor and display 
data. The APM accepts a range of electrical inputs (depending on the model) and displays the data on its integrated 
multi-format display. The APM has been designed for installation into electrical cabinets or display panels. Output 
models include two independent outputs that can be configured by the user to be either digital set-point outputs or 
4-20mA monitor outputs.

 

DIP Switches

The DIP switches are on the back of the unit.

 

=Using external 5A secondary 

current transformer 

Sw Pos Measured  Bar Graph 

Display Value 

Item  1234 

Value 

Min  Max 

Format 

Max 

0000  Custom (Defined in Software Application) 

1000 

Auto Ranging 

0100 

5 A 

#.### 

5.000 

1100 

5 A 

#.### 

5.000 

0010 

10 A 

10 

##.## 

10.00 

1010 

20 A 

20 

##.## 

20.00 

0110 

40 A 

40 

##.## 

40.00 

1110 

50 A 

50 

##.## 

50.00 

0001 

60 A 

60 

###.# 

60.0 

10  1001 

80 A 

80 

###.# 

80.0 

11  0101 

100 A 

100 

###.# 

100.0 

12  1101 

200 A 

200 

###.# 

200.0 

13  0011 

400 A 

400 

#### 

400 

14  1011 

600 A 

600 

#### 

600 

15  0111 

800 A 

800 

#### 

800 

16  1111 

1000 A 

1000 

#### 

1000 

Use the DIP switch to set the CT Meter bar graph range, 

and the current transformer (CT) ratio if used.  The CT 

ratio is shown as the target value. Use the software to set 

other value CTs. 

Operating specification 

VALUE 

UNIT 

INPUT 

Input Range (CT Output 
Current) 

0-5 A 

I AC 

Min CT Power (Burden) 

VA 

Input range (via external 
current transformer) 

0-10,000 A 

I

 AC 

Input Current Frequency 

45-65 

Hz 

Input Impedance 

10 

mΩ 

Accuracy 

0.5 

Resolution 

mA 

Sample rate 

KHz 

Display modes 

RMS 

Size  

Wiring Diagram

 

68 x 68mm (2.68in) +0.7 -0mm 

Size of 

the cutout in the panel: 

CT METER 

Using Current Transformer 

The APM CT meter has been designed to be used with an external current 

transformer. Never connect the meter directly to a live circuit.

 

Operating Specification

www.

.com

[email protected]

1.800.561.8187