APM
CT Meter
CAUTION: Risk of Danger
Read complete instructions prior to installation and
operation of the unit
CAUTION:
Risk of electric shock
Before installation, read the Safety Warnings overleaf.
Intended Use: The APM has been specifically designed for engineers requiring an effective way to monitor and display
data. The APM accepts a range of electrical inputs (depending on the model) and displays the data on its integrated
multi-format display. The APM has been designed for installation into electrical cabinets or display panels. Output
models include two independent outputs that can be configured by the user to be either digital set-point outputs or
4-20mA monitor outputs.
DIP Switches
The DIP switches are on the back of the unit.
=Using external 5A secondary
current transformer
Sw Pos Measured Bar Graph
Display Value
Item 1234
Value
Min Max
Format
Max
1
0000 Custom (Defined in Software Application)
2
1000
Auto Ranging
3
0100
5 A
0
4
#.###
5.000
4
1100
5 A
0
5
#.###
5.000
5
0010
10 A
0
10
##.##
10.00
6
1010
20 A
0
20
##.##
20.00
7
0110
40 A
0
40
##.##
40.00
8
1110
50 A
0
50
##.##
50.00
9
0001
60 A
0
60
###.#
60.0
10 1001
80 A
0
80
###.#
80.0
11 0101
100 A
0
100
###.#
100.0
12 1101
200 A
0
200
###.#
200.0
13 0011
400 A
0
400
####
400
14 1011
600 A
0
600
####
600
15 0111
800 A
0
800
####
800
16 1111
1000 A
0
1000
####
1000
Use the DIP switch to set the CT Meter bar graph range,
and the current transformer (CT) ratio if used. The CT
ratio is shown as the target value. Use the software to set
other value CTs.
Operating specification
VALUE
UNIT
INPUT
Input Range (CT Output
Current)
0-5 A
I AC
Min CT Power (Burden)
1
VA
Input range (via external
current transformer)
0-10,000 A
I
AC
Input Current Frequency
45-65
Hz
Input Impedance
10
mΩ
Accuracy
0.5
%
Resolution
1
mA
Sample rate
8
KHz
Display modes
RMS
Size
Wiring Diagram
68 x 68mm (2.68in) +0.7 -0mm
Size of
the cutout in the panel:
CT METER
Using Current Transformer
The APM CT meter has been designed to be used with an external current
transformer. Never connect the meter directly to a live circuit.
Operating Specification