background image

7

Examples of warm air distribution with Truma accessories

It must be ensured that if a closable end outlet is being 
used (e.g. bathroom), at least one non-closable nozzle is 

installed in the warm air branch.

If the warm air distribution or circulated air intake is par-
tially or completely blocked, the VarioHeat switches off 

prematurely and full power is not available.

 10 - 100 cm

VR 80

SCW 2

Fig. 15-1 

– Truma 

“Warm air basic kit”

10 - 100 cm

VR 80

Y 80

ÜR 

ÜR 

EN

EM

EN-0

LA

Fig. 15-2 

– Truma 

“Warm air basic kit”+ “Warm air ad-

ditional kit”

3. Secure all pipe connections with clips / tapping screws. Fix 

pipes with ZRS / ÜS clamps.

 Circulated air intake

The circulated air (U) is sucked in again by the heater. This 
must take place from the living room (not the rear storage 
locker) to the installation space via one large or several small-
er openings with an overall area of at least 150 cm² . 

Circulated air intake with grid

If a grid (not supplied) is installed, the same requirements 
regarding the cross section through which the air is sucked in 
(150 cm²) must be observed.

W

U

U

Fig. 16

 – Example of circulated air intake through a grid

Installing the room temperature sensor

The supplied room temperature sensor must always be 
connected, otherwise the heater will indicate an error. 

Choosing a location

When choosing a location, remember that the room tempera-
ture sensor must not be exposed to direct heat radiation. For 
optimum room temperature control, we recommend that you 
install the room temperature sensor above the entrance doors.

Make sure that the sensor is always installed on a 

verti-

cal

 wall. The room air must be allowed to flow around it 

freely. 

Installation

•  Drill a Ø 10 mm hole. 

•  Feed the connector cable through the hole from behind and 

connect the end of the cable to the sensor with an insulated 
connection plug (polarity is unimportant). 

•  Insert the room temperature sensor and lay the cable end 

with bushing X7 to the heater (if necessary, extend to a 
maximum length of 10 m with 2 x 0.5 mm² cables).

•  Plug the room temperature sensor on to the cable harness 

of the heater (refer to „Electrical connections – heater“ page 
8). 

10 mm

X7

Fig. 17

Installing a digital control panel

Description 

Digital Truma CP plus VarioHeat control panel to operate a 
VarioHeat heater. A Truma  Aventa comfort (from serial num-
ber 24084022 – 04/2013) or Saphir comfort RC air condition-
ing system may also be connected. 

The control panel (with polarity protection) is supplied with 
power via a 12 V connector cable. The control panel is con-
nected with a VarioHeat heater and / or air conditioning sys-
tem with a connector cable (TIN Bus).

Dimensions

 92 

 103 

 7

 22 

 18 

 9 

 69 

 19.8 

 11.5 

 11.5 

 21.1 

Fig. 18

 – Dimensions in mm. Picture not to scale

Содержание VarioHeat eco AU

Страница 1: ...Installation instructions Page 2 Truma VarioHeat eco AU...

Страница 2: ...c window switch optional 4 Exhaust duct 5 Warm air 6 Circulating air 7 Gas inlet connection with gas pressure test point 8 Type plate 9 VarioHeat pre pressure regulator Installation variants 30 max 10...

Страница 3: ...ing regulations AS NZS 5601 2 LP Gas installations in caravans and boats for non propulsive purposes LP Gas installations and any other statutory regulations Use with liquefied petroleum gas LP Gas in...

Страница 4: ...Install the heater in the directions shown Fig 2 Fig 7 on page 2 The functions of parts of the vehicle that are important for operation must not be adversely affected Clearance from combustible materi...

Страница 5: ...he mounting brackets to the housing of the heater in the respective hole pattern Fix the heater with the mounting brackets and the supplied bolts B 5 5 x 25 mm The heater must be screwed to the floor...

Страница 6: ...liance Slide the clamp 7 over the pipes Compress the exhaust duct 1 at the start so that coil sits on coil Slide the clamp 4 over the exhaust duct 1 Slide the exhaust duct 1 over the O ring 2a on to t...

Страница 7: ...cate an error Choosing a location When choosing a location remember that the room tempera ture sensor must not be exposed to direct heat radiation For optimum room temperature control we recommend tha...

Страница 8: ...control panel Truma CP plus VarioHeat must be connected to the same circuit The positive cable must be protected with a 1 A fuse TIN Bus CI BUS1 12 V red red black Fig 20 View from the rear 1 Only wi...

Страница 9: ...the supply line may have to be considered Connect the negative cable to the central earthing system If parts are connected directly to the battery the positive and negative cables must be fused No oth...

Страница 10: ...UNF 3 Fig 25 After installation you must check gas supply line for leaks in accordance with the pressure drop method Do not use matches candles or other sources of ignition when checking for gas leak...

Страница 11: ......

Страница 12: ...e relevant service partners should be contacted www truma com Having the equipment model and the serial number ready see type plate will speed up processing Service Australia Telephone 61 1800 21 21 2...

Отзывы: