•  Cut the pipes so that they project outside the hole for the 

cowl during installation. The exhaust duct (1) must be 10 % 
longer than the combustion air intake duct (5). This prevents 
expansion and tensile loading of the exhaust duct.

•  Compress the exhaust duct (1) at the start – to approx. 2 cm 

– so that coil sits on coil. 

•  Slide the exhaust duct (1) over the O-ring (2a) on to the con-

nection (2) as far as the collar (3) (the wall cowl is angled 
upward).

•  Position the clamp (4) so that the flange edge of the clamp 

catches around the collar.

•  Tighten the clamp (4) (tightening torque 1 Nm).

1 4

2

3

2a

Fig. 12

•  Fix the cowl inner part (11) with 3 screws (12) (pay attention 

to the installation position. The Truma logo must be at the 
bottom). 

•  Slide the combustion air intake duct (5) on to the serrated 

connection (9) and fix with the clamp (7) (3 Nm).

•  Place cowl insert part (16) into cowl outer part (13).

•  Place the cowl outer part (13) on top and fix with 2 screws (14).

A new O-ring (2a) must be installed every time the sys-
tem is dismantled.

Connecting the exhaust double duct to the 
appliance

•  Slide the clamp (7) over the pipes. 

•  Compress the exhaust duct (1) at the start so that coil sits 

on coil. 

•  Slide the clamp (4) over the exhaust duct (1). 

•  Slide the exhaust duct (1) over the O-ring (2a) on to the con-

nection (2) as far as the collar (3).

•  Hook in the clamp (4) and tighten it (tightening torque 1 Nm). 

•  Fix the combustion air infeed pipe (5) on the connection (6) 

with the clamp (7) (tightening torque 3 Nm).

Fig. 13

 Warm air distribution

The warm air is fed from the heater mainly to the floor area of 
the living room either directly or through flexible pipes (warm 
air distribution).

Use only Truma accessories to distribute warm air in the RV.

A selection of Truma accessories for warm air distribution

Accessory

Symbol

Description

VR 80

Air duct VR 80, (Ø 80 mm)

ÜR

Air duct ÜR, (Ø 65 mm) 

SCW 2

Swivelling air outlet SCW 2

EN

End outlet EN with air throttle

EN-0

End outlet EN-O without air throt-
tle, for lamella inset LA

EM

End outlet nut EM

LA

Lamella inset LA for attaching to 
end outlet EN-O, direction of air 
flow can be adjusted by turning

Y 80

Y-piece 80,
Inlet Ø 80 mm,
Outlet 2 x Ø 65 / 72 mm

ZRS

Clamp ZRS, Ø 80 mm 

Clamp 
ÜS

Clamp ÜS, Ø 65 mm

1. If warm air distribution is used, the grid on the warm air 

outlet of the heater must be removed.

2. Only the VR 80 pipe may be connected to the heater.

1

2

VR 80

Fig. 14

Содержание VarioHeat eco AU

Страница 1: ...Installation instructions Page 2 Truma VarioHeat eco AU...

Страница 2: ...c window switch optional 4 Exhaust duct 5 Warm air 6 Circulating air 7 Gas inlet connection with gas pressure test point 8 Type plate 9 VarioHeat pre pressure regulator Installation variants 30 max 10...

Страница 3: ...ing regulations AS NZS 5601 2 LP Gas installations in caravans and boats for non propulsive purposes LP Gas installations and any other statutory regulations Use with liquefied petroleum gas LP Gas in...

Страница 4: ...Install the heater in the directions shown Fig 2 Fig 7 on page 2 The functions of parts of the vehicle that are important for operation must not be adversely affected Clearance from combustible materi...

Страница 5: ...he mounting brackets to the housing of the heater in the respective hole pattern Fix the heater with the mounting brackets and the supplied bolts B 5 5 x 25 mm The heater must be screwed to the floor...

Страница 6: ...liance Slide the clamp 7 over the pipes Compress the exhaust duct 1 at the start so that coil sits on coil Slide the clamp 4 over the exhaust duct 1 Slide the exhaust duct 1 over the O ring 2a on to t...

Страница 7: ...cate an error Choosing a location When choosing a location remember that the room tempera ture sensor must not be exposed to direct heat radiation For optimum room temperature control we recommend tha...

Страница 8: ...control panel Truma CP plus VarioHeat must be connected to the same circuit The positive cable must be protected with a 1 A fuse TIN Bus CI BUS1 12 V red red black Fig 20 View from the rear 1 Only wi...

Страница 9: ...the supply line may have to be considered Connect the negative cable to the central earthing system If parts are connected directly to the battery the positive and negative cables must be fused No oth...

Страница 10: ...UNF 3 Fig 25 After installation you must check gas supply line for leaks in accordance with the pressure drop method Do not use matches candles or other sources of ignition when checking for gas leak...

Страница 11: ......

Страница 12: ...e relevant service partners should be contacted www truma com Having the equipment model and the serial number ready see type plate will speed up processing Service Australia Telephone 61 1800 21 21 2...

Отзывы: