background image

 

SELF CONTAINED LED EMERGENCY  
Model: SPOT DL LED 

 
Self-contained  LED emergency with LED lamp 3*1W and constant current control. Designed to work in Maintained 
and non-maintained mode.  Equipped with high luminosity white LED 3*1W for stable illumination and a small green 
Led to indicate the power presence and battery charging. 
 

Characteristics: 

Supply 230 V 50/60Hz 

Input current: 56mA 

Maintained/Non Maintained. 

Green Led indicating the battery charge 

Output voltage:9.5VDC with 3*1W LED lamp 

Output current: limited to 270ma. 

Output power in emergency mode 3.5 W  

Battery Ni-mh 6V1.2 Ah 

Autonomy 1 hour 

Protection against Overloading and end of Battery Discharge 

Open circuit protection 38 V.( LED lamp) 

Colour Temperature 5000-5500K 

Grade IP20 

Class II device 

Ambient temperature:0-50ºC 

Verification test via Telemando TM 

Battery charging 24 hours 

Max cross section of cable to be connected 1,5mm 

Max distance to led lamp 2m 

Recessed mounting. 

CE marked as per directives 2006/95/CE and 2004/108CE EMC 

Manufactured in accordance to norms  UNE-EN 60598-2-22UNE-EN 61347-2-13 

 
 

Model 

Frame Color 

Autonomy 

Battery 

SPOT DL LED-1S 

Silver 

1 Hour 

6V - 0,8Ah 

SPOT DL LED-1W 

White 

1 Hour 

6V - 0,8Ah 

SPOT DL LED-3S 

Silver 

3 Hours 

6V - 2,5Ah 

SPOT DL LED-3W 

White 

3 Hours 

6V - 2,5Ah 

SPOT DL LED SIGN S 

Silver 

--- 

--- 

SPOT DL LED SIGN W 

White 

--- 

--- 

 
Wokring: 
Power presence
: The device charges permanently the battery and the Green led indicating the charging process in 
ON. In maintained mode, LED Lamp is permanently ON and in non-maintained mode the LED LAMP remains OFF 
and goes ON in emergency. 
 
Power failure: In case of power failure or low voltage, the luminary enters in emergency mode, the green led 
indicating the battery charge goes OFF,  
En maintained mode: The driver maintains LED lamp ON with battery power. 
En non maintained mode: The Driver switches ON the LED lamp with battery power. 
The autonomy of the luminary is 1or 3hours depending on the model. 
 
Verification TEST: Verification during power presence is done via TELEMANDO. 
By pressing ON (TM) the luminary enters into emergency mode, and comes back to normal mode as the ON button 
is released, see diagram next page. 
 
Installation: 
 
Make a hole of 70 mm diameter in the ceiling to introduce the driver and the battery and recess the luminary once 
connected. 
-  Please refer to the connection diagrams on next page for connection and follow the following steps. 
- Switch OFF the power to make the installation. 
- Make connections to the connector (N,L), this line should be permanent, as it is charging the battery permanently 
and if the line is cut the luminary will enter in emergency mode. 
- Make connection to connector (L1) (see Maintained mode connection diagram), It is also possible to connect a 
switch in this line to switch ON/OFF the in maintained mode (see connection diagram) 
- Connect the 3*1W LED lamp wire to the driver connector (LED LAMP + -) respecting the polarity indicated 
(red+/black-) 
- Connect the green LED wire to the driver connector (battery charging indicator), respecting the polarity, the 
special connector enables the possibility of connection error. 