Self contained LED Emergency
SERIE MIZAR S AT, SP AT & SI AT
F
I
P
4
0
Technical Characteristics:
-
Supply 230V~ 50/60Hz.
-
LED /Maintained/Class II luminary/ IP Grade IP40/ Standby & Restart via Telemando TM or Test button
-
Automatic & Manual Self Test (manual test by pressing test button or by Telemando TM)
-
Tri colour Led (green/red/orange) indicating, the Battery re-charging and the test results.
-
Visibility 25m model SP AT, 33m model S AT and 40m model SI AT (As per NORM UNE-EN 1838).
-
Autonomy > 1 hour.
-
Battery Ni-Cd 6V
– 0,8Ah / Luminous Flux: 2 lm.
-
Connection via
6 mm cable.
-
Overload & end of battery discharge protection.
-
ACRYLIC Diffuser of 8 mm width.
-
Frontal, lateral mounting & suspended via cable / Pictograms & mounting accessories included.
-
Manufactured in accordance to the norms UNE-EN 60598-2-22, UNE-EN 60598-1, UNE-EN 1838 and marked CE as per directives
.
SELFTEST Function
The Emergency Luminary has a programmed micro controller to execute automatically or manually a series of verification TESTS, to verify the
working of the Luminary.
Basically these TESTS do the verification of the two of the most important elements of the Luminary:
1. Emergency Lamp: Runs an Automatic TEST WEEKLY during 15 seconds.
2. Battery (Autonomy): Runs an Automatic TEST according to programming.
*use a internal clock for the timings and it is not as perfect as a profession calendar clock
Installation:
-
Place the 2 polycarbonate pictograms (one per side) and fix them to the metacrilate diffuser by the means of 4 plastic screws included.
-
Install the luminary as required (wall, or ceiling) as indicated in the fig.
-
Make the connections of the supply, hiding the cable in the gap in the upper as indicated in the fig.
-
Switch On the Power and verify that the Pictograms and the green led indicating the battering charging are illuminated.
-
The Luminary will not respond to its complete autonomy until 24 hours, as the batteries are supplied discharged
Test Results Indications:
Luminary OK:
GREEN LED ON.
Lamp Failure:
RED LED “Blinking”
Battery Failure (Autonomy):
RED LED ON.
Electronic Failure
: ORANGE LED ON
Indications for DIFFERENT SITUATIONS:
1.
Power presence and Working OK:
Green LED ON.
2.
Power presence and Battery Charging during 1
st
24 hours or after prolonged Power Failure or after battery test:
Green LED
“Blinking”
3.
Power Failure or Voltage below 170 Volts:
GREEN /RED/ ORANGE Led OFF.
4.
Fault in Electronic LED driver
: ORANGE LED
“Blinking”.
5.
Power presence and Battery failure:
RED LED ON.
6.
During the LED lamp TEST:
GREEN LED “Blinking” (1 short blink).
7.
During the Battery TEST:
GREEN LED “Blinking” (2 short blink).
8.
On Pressing the Manual TEST Button:
GREEN and RED LED are illuminated alternatively.
SELF TEST programming:
Once the Luminary is connected to the Power for the 1
st
time, the dates for AUTOMATIC TESTS are set. It runs a Verification TEST of LED
LAMP weekly and a verification TEST of the BATTERY according to programming.
In a situation, when there is a POWER failure coinciding with the execution of the Programmed BATTERY TEST, the TEST is postponed and is
executed when NEXT LAMP TEST is programmed. If during a TEST there is a power failure, the TEST will continue till the end. The battery
TEST can be cancelled by pressing the TEST button for more than 6 seconds.
The TEST results are indicated by Green / Red/ Orange LED and are memorized until the Power and the battery are disconnected or till performing
RESET
RESET:
On doing the RESET all the Timings and Alarms are
RESTARTED
. To perform the RESET, disconnect the Power and the battery connector,
wait approx. from 8 to 12 seconds, connect the battery and then the power.
MANUAL TESTS
:
The LED LAMP and battery TESTS can also be done manually by using the TEST Button incorporated on the Luminary or if the luminary by
TELEMANDO TM (pressing ON).
TEST BUTTON (incorporated on the Luminary):
LED LAMP TEST
: To execute the LAMP TEST manually, press the manual TEST button during 3 to 6 seconds.
BATTERY TEST
: To execute the BATTERY TEST manually, Press the manual TEST button for more than 6 seconds
On executing the manual test all the times are RESET. During the 1st 24 hours or after prolonged power failure it only allows to do the tube
TEST and not the battery test. Once the battery test is executed it can be cancelled as indicated above.
Telemando TM:
By pressing ON all the luminaries connected to TELEMANDO all the luminaries connected to it will launch the TEST, follow the
same rules as the test button to launch the respective tests.
Maintenance:
-The Batteries should be changed once their duration gets inferior to the assigned.)
-The Batteries and the electronic components should be re-cycled or eliminated in an adequate way.
-Before doing any maintenance operation, please make sure that the Main supply is switched off and the luminary is in STAND BY Position.
-To change the battery, remove the cover, disconnect & remove the battery accordingly, as indicated in the fig.
Connection diagram: