TRQ I-SIGN Series Скачать руководство пользователя страница 1

       Lighting Technologies TRQ, S. L.

 

 

 

SELF CONTAINED EMERGENCY SIGN        

F

IP40

 

SERIE I-SIGN y VIZART 

Technical Characteristics: 

 

-

 

Supply 230V~ 50/60Hz. 

-

 

Maintained. 

-

 

Stand by and re-start via Telemando(TM). 

-

 

Green Led indicating, the Battery re-charging. 

-

 

Illumination via High luminosity white led. 

-

 

Stabilized current of Led (constant current control). 

-

 

Visibility 24 mts. (As per NORM UNE-EN 1838). 

-

 

Autonomy superior 1 hour. 

-

 

Battery Ni-Cd 6V – 0,8Ah. 

-

 

Protection Grade IP40. 

-

 

Connection via 

6 mm cable. 

-

 

Overload & end of battery discharge protection. 

-

 

Class I Luminary. 

-

 

Pmma Diffuser of 8 mm width. 

-

 

Aluminum  front frame in 2 colors: White & Black ( ISIGN) and White & Aluminum ( VIZART)   

-

 

Surface and wall recessed mounting. 

-

 

Pictograms & mounting accessories included. 

 
Norms Applied: 

 

-

 

CE marked as per 2006/95/CE y 2004/108/CE UNE-EN 60598-2-22 

-

 

UNE-EN 60598-1 

-

 

UNE-EN 1838 

 

Installation: 

 

-

 

Install  the  luminary  following  the  mounting  instructions  on  the  next  page  and  electrical  connection 
diagram. 

-

 

Switch  On  the  Power  and  verify  that  the  Pictograms  and  the  green  led  indicating  the  battering 
charging are illuminated. 

-

 

The Luminary will not respond to its complete autonomy until 24 hours, as the batteries are supplied 
Discharged. 

-

 

If  during  working,  the  frontal  diffuser  is  disconnected,  the  luminary  will  be  blocked,  to  reset,  first 
disconnect  the luminary  from the  power  supply  ,  then the battery,  wait  for  few  seconds and  connect 
first the battery then the power. 

 

Maintenance

-The Batteries should be changed once their duration gets inferior to the assigned.) 
 
-The Batteries and the electronic components should be re-cycled or eliminated in an adequate way. 
-Before doing any maintenance operation, please make sure that the Main supply is switched off and the             
luminary is in STAND BY Position. 
 
Telemando TM: TM is used for verification and also for standby / restart in emergency mode

 

Connection Diagram: 

 
 
 
 
 
 

 

 

 

 

 

A: 

Connection without Telemando.     

B: 

Connection with Telemando.

  

 

 

 

 

 

 

Отзывы: