Installing and commissioning instructions 
 
Velocity sensor VS-TRD  
  

LABCONTROL system 

 
MI/7.4/5/EN/2 

 

 

 
Attention! 
Before installing and commissioning 
read this manual carefully! 

 
 

Scope of application for VS-TRD 

The velocity sensor VS-TRD measures the face velocity 
of fume cupboards and gives an appropriate analog 
output signal with 2-10 V DC. 
In conjunction with TROX volume flow controllers based 
on LABCONTROL EASYLAB, TCU-II or TCU-LON-II the 
sensor is used for variable volume flow control. 
Alternatively the VS-TRD can be also used in conjunction 
with TROX LABCONTROL system TFM-2 for monitoring 
the face velocity. 
The sensor VS-TRD is placed for these functions at a 
suitable position on the fume cupboard. 
Please regard the assembling drafts on the following side. 
 
 
 
 

Safety instructions 

The installation and wiring must be carried out by 
qualified and instructed personnel. The country and local 
specific guidelines and regulations for electrical 
installations must be observed. 
 
During installation, wiring and commissioning, the 
established technical regulations, are to be observed, 
particulary those on safety and accident prevention. 
 
 
 
 
 

Technical data 

Power supply: 

24 V AC ±15 %, 50/60 Hz 

 

Temperature: 

10 - 40°C

 

 

Output: 

1 analog output 2-10 V DC 

 

equivalent to 0 - 1 m/s 

 

Protection class: 

IP 20 

 

Connector: 

Phoenix MC 1.5/3-ST-3.81 

br (br)   = Power supply  24 V AC 
ws (wt)   = Power supply  GND 

 

gn (gn)   = Analog output AO 
 

Dimensions: 

max. casing dimensions: 80 x 90 x 60 mm

 

max. installation depth: 88.1 mm 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Wiring 

The transducer is supplied with a prefabricated 3 m cable 
ready-made for plug into the control systems. The green 
3-pole Phoenix plug must be fitted in the corresponding 
plug socket on the EASYLAB, TCU-II respectively 
TCU-LON-II controller board. A cable extension with 5 m 
length is optionally available.  
(TROX -No. M536BA9) 
 

Installing instructions 

1.  Accessibility for further maintenance work must be 

regarded. 

2.  A hole of  

 21-22.5 mm diameter must be drilled in 

the top of the fume cupboard. 

3.  The hole diameter must be observed accurately, 

otherwise measuring errors may occur due to air flow 
besides the transducer. 
 

Positioning of the hole

For positioning the hole please follow these instructions: 