 NOTICE!

Risk of damage to property due to electro-
static charge

Electrostatic charge can damage the electronics.

Avoid skin contact with any components or
printed circuits.

Touch an equipotentially bonded metal sur-
face before you touch any printed circuit
boards.

Wear conductive footwear and antistatic
clothing.

 NOTICE!

In an emergency

Immediately disconnect the power supply to the
controller. Emergencies include, for example, a
damaged mains cable, a damaged casing, the
ingress of a liquid or foreign matter, a smell or
smoke.

Have the device checked by the manufacturer
before you put it into operation again.

Correct use

Only use the device for its intended correct use and
in compliance with the safety precautions and infor-
mation in this manual in order to avoid danger to
persons and property.

The correct use of this device encompasses:

The electronic control of volume flow rate,
room pressure or duct pressure for supply or
extract air in conjunction with a TROX air ter-
minal unit.

Indoor use for ventilation and air conditioning
systems.

The controller is typically used in a group of
several controllers for complete room control,
but it may also be used as a single controller.

For error-free operation, the installation orien-
tation of the controller must be observed; pos-
sible installation orientations are indicated on
the installation orientation label on the device.

Incorrect use

Do not use the controller in an installation orienta-
tion or for areas of application that are not
described in this manual.

Do not use the controller outdoors, in wet areas, or
in areas with potentially explosive atmospheres.

Residual risks

Power failure

If the power fails, the damper blade of the VAV ter-
minal unit remains in the position at that time; the
controller will resume operation once power returns.

In control units with spring return actuator (TUNF),
the control damper blade moves to a definable posi-
tion (OPEN or CLOSED) in the event of a power
failure.

For safety related applications you may use expan-
sion module EM-TRF-USV, which ensures uninter-
ruptible power supply. If the emergency power unit
has been correctly connected and charged, it will
supply power for the set operating times (

Ä

Tech-

nical Data for EM-TRF-USV).

Monitoring function

Alarm signal in the event of insufficient volume
flow rate, 

Ä

   on page 12

Alarm signal in the event of insufficient duct or
room pressure, 

Ä

   on page 12

Alarm signal in the event of volume flow rate in
shut-off position, 

Ä

   on page 12

For safety related applications you should check
whether then safety measures are required, such
as alarms. You may use the alarm relay for
switching operations.

Safety and correct use

 

Control components for VAV terminal units TROX UNIVERSAL

7

Содержание TROX UNIVERSAL

Страница 1: ...Control components for VAV terminal units TROX UNIVERSAL Installation and operating manual GB en...

Страница 2: ...GmbH 2017 TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Telephone 49 0 2845 202 0 Fax 49 0 2845 202 265 E mail trox trox de Internet www trox de 06 2019 Control components for VAV termi...

Страница 3: ...signal lamps on the con troller casing 14 Interfaces and signal lamps in the con troller casing 16 6 Installation 18 Tube connection on the external pressure transducer 22 7 Wiring 23 Safety instructi...

Страница 4: ...ing over the system The system owner must include the manual with the system documen tation The manual must be kept in a place that is accessible at all times Illustrations in this manual are mainly f...

Страница 5: ...e an infringe ment of copyright and the violator will be held liable for any damage This applies in particular to Publishing content Copying content Translating content Microcopying content Saving con...

Страница 6: ...and correct use General safety notes DANGER Risk of injury from the damper blade of the VAV terminal unit The damper blades of VAV terminal units close or open extremely quickly 90 within 3 seconds an...

Страница 7: ...ler must be observed pos sible installation orientations are indicated on the installation orientation label on the device Incorrect use Do not use the controller in an installation orienta tion or fo...

Страница 8: ...professional or technical training knowledge and actual experience to enable them to work on electrical systems understand any poten tial hazards related to the work under consideration and recognise...

Страница 9: ...m The 24 V supply voltage may be connected for a maximum of 5 controllers Micro fuse 2 5 A slow blow 250 V as glass fuse 5 x 20 mm Volume flow rate measurement Differential pressure transducer with ro...

Страница 10: ...ns Fig 1 Dimensions universal Keep clear to provide access 1 In combination with TVRK TVR TVA TVZ TVJ TVT TA TZ Silenzio VMR VME VMRK Technical data Control components for VAV terminal units TROX UNIV...

Страница 11: ...dered see delivery note Operating and installation manual The electronic controller is typically delivered fully mounted on a TROX air terminal unit If any expansion modules have been ordered the cont...

Страница 12: ...s on opposite sides of the con troller casing blink continuously The alarm relay of the controller drops out wire break proof If necessary external alarm signal External signaling of setpoint deviatio...

Страница 13: ...level system only with expansion module EM LON EM IP or EM BAC MOD Monitoring shut off Display on the control panel BE LCD Yellow light flow rate above setpoint Signaling to the higher level system on...

Страница 14: ...operation 2 Yellow Cable termina tion LED on Cable termination is active LED off Cable termination is inactive 3 Green Not used 4 Yellow Data reception in progress LED on Data is being received from...

Страница 15: ...2 8 Actuator X4 Actuator The actuator of the damper blade is factory fitted 9 Sensor X5 Analogue input AI5 For room or duct pressure control for connection of the pressure sensor otherwise for connec...

Страница 16: ...pressure transducer analogue voltage 0 10 VDC 10 mA max 3 Expansion slot 1 ESP KOM Connection for expansion modules to connect the controller to higher level systems EM LON BUS communication LonWorks...

Страница 17: ...switch contacts 5 V DC xx mA 12 Terminal block TI1 Input for temperature sensor PT1000 not supported 13 Terminal block AI1 AI4 Analogue inputs 1 4 Can be configured for 0 10 V DC 10 mA max 14 Clip co...

Страница 18: ...position of the diaphragm pressure transducer in the controller casing If you install the controller above or below a duct you have to adapt the position of the diaphragm pressure transducer 18 Altern...

Страница 19: ...al ducts Fig 7 Tubing 4 Check all connections and make sure that the tubes and wires of the transducer are properly connected and have not been kinked Connect any disconnected wires on the PCB Valve 1...

Страница 20: ...stall the controller according to the sticker showing the correct installation orientations 18 Fig 8 Detaching the controller 1 Use a screwdriver to flip up the lug 1 and lift the controller In some c...

Страница 21: ...Installation Control components for VAV terminal units TROX UNIVERSAL 21...

Страница 22: ...1 2 Room pressure control extract air Measuring point Tube connection PT699 Positive Room pressure Negative Room pressure 1 2 Duct pressure control supply air Measuring point Tube connection PT699 1...

Страница 23: ...ed electrician has to select the correct cable types and sizes This job must only be carried out by specialist electrical companies For the electrical connection comply with any applicable regulations...

Страница 24: ...ed to improve electromagnetic com patibility EMC We recommend you to connect the device to equi potential bonding in order to improve electromag netic compatibility Strain relief Use the cable clips i...

Страница 25: ...ters as well as the software license are available as acces sories part no B588NF4 Alternatively BlueCon Bluetooth adapter Fig 10 Bluetooth connection via various interfaces 1 Connection to terminal 1...

Страница 26: ...d white 1 from the angled pieces 2 on the sensor tube or from the T pieces 3 on the controller Zero point correction can alternatively also be carried out with the EasyCon APP When the zero point corr...

Страница 27: ...rrected To do this press the diagnostics push button Adaption in the EasyCon nect software For adaptation the actuator moves to the end positions and then automatically switches to control mode Functi...

Страница 28: ...m pressure transducer is required in regular intervals not required for controllers with expansion module EM AUTOZERO Carry out manual zero point cor rection at least once per year as part of a functi...

Страница 29: ...t carries a dangerous elec trical voltage Only skilled qualified electricians are allowed to work on the electrical system Switch off the power supply before working on any electrical equipment 1 Inte...

Страница 30: ...Appendix Control components for VAV terminal units TROX UNIVERSAL 30...

Страница 31: ...ND Raumbetriebsart Erh ht Vmax Potentialfreier Kontakt geschlossen erh ht Schalter bauseits DI3 GND Raumbetriebsart Absperrung Zu Potentialfreier Kontakt geschlossen zu Schalter bauseits DI4 GND Raumb...

Страница 32: ...ung Raumbetriebsart Reduziert Vmin Potentialfreier Kontakt geschlossen reduziert Schalter bauseits DI2 GND Raumbetriebsart Erh ht Vmax Potentialfreier Kontakt geschlossen erh ht Schalter bauseits DI3...

Страница 33: ...z Auf C NC NO DO4 Sonnenschutz Zu Ausgangs Beschaltung Raumbetriebsart Reduziert Vmin Potentialfreier Kontakt geschlossen reduziert Schalter bauseits DI2 GND Raumbetriebsart Erh ht Vmax Potentialfreie...

Страница 34: ...enstellung Regler Raum Management Funktion RMF TROX UNIVERSAL Regler TCU3 Abluft Raumzuluftregler TU RE Anschl sse Geh useau enseite KL KOMMUNIKATION COMM 1 X6 COMM 2 X7 Anschl sse Geh useau enseite A...

Страница 35: ...0s NF Federr cklauf 150s S schnelllaufend 4s AO1 GND Lokaler Ist Volumenstrom C NC NO DO1 Lokaler Alarm 24V AC GND Power 24 VAC AO3 GND Klappenstellung Regler KL KL Term KL Term Raumbetriebsart Reduzi...

Страница 36: ...2 5 mm 12 30 AWG 2 x 0 75 230 VAC 8 A 1000 V DO6 NO NC C 0 2 2 5 mm 12 30 AWG 2 x 0 75 230 VAC 8 A 1000 V DI2 DI2 GND 0 14 1 5 mm 16 26 AWG 2 x 0 75 max 40 m 131 ft 5 V 10 mA 1 6 KV DI3 DI3 GND 0 14 1...

Отзывы: