8
Commissioning
Checking / adjusting the configuration settings
Controller parameters are factory set as ordered.
Carry out commissioning based on any project-spe-
cific data and the project-specific wiring docu-
ments..
Connection with configuration cable
Fig. 9: PC connection via various interfaces
1
Connection to terminal-1/-2 (Service X2 / X3)
2
Connection to the service socket of the BE-
LCD control panel
1.
Using a PC or notebook and the TROX
EasyConnect configuration software, you
can verify the configuration settings and
adjust them if necessary.
To do this, connect the computer and the
controller with the configuration cable (USB-
RS485) to one of the interfaces shown
above.
The required cables and adapters as well as
the software license are available as acces-
sories (part no. B588NF4).
Alternatively: BlueCon Bluetooth adapter
Fig. 10: Bluetooth connection via various interfaces
1
Connection to terminal-1/-2 (Service X2 / X3)
2
Connection to the service socket of the BE-
LCD control panel
2.
You can also establish a wireless connection
(Bluetooth) between the controller and your
PC. To do this, plug the BlueCON module
into one of the interfaces shown above. This
requires a Bluetooth interface on the PC or
notebook (either integral hardware or
external, e.g. with a USB stick).
Andriod APP EasyCon
Alternatively, diagnosis and maintenance
can also be performed via an Android
smartphone or tablet. The Android device
can be used to access the controller via
the BlueCon module.
The required EasyCon APP can be down-
loaded from Google PlayStore.
Commissioning
Control components for VAV terminal units TROX UNIVERSAL
25