background image

Product overview

Fig. 1: Schematic illustration, e. g. TFM

Spigot with lip seal

Casing

Internal measuring tube

Suspension

Pressure measurement point

Bracket for tensioning frame

Test groove

Filter

Clamping frame for the filter element

Clamping screw

Diffuser face

Screw fixing diffuser face

Sealing plug for connecting holes

Installation and maintenance 
manual

GB/en

TFM

Particulate filter modules for ceilings

TROX GmbH

Heinrich-Trox-Platz
47504 Neukirchen-Vluyn, 
Ger-many
Germany
Phone: +49 (0) 2845 2020

 

Fax: +49 (0) 2845 202265

 

E-

mail: [email protected]

 

Internet: 

http://www.trox-

technik.com

A00000072700, 02/2019, 

©

 2015 TROX GmbH

TFM Particulate filter modules for ceilings

1

Содержание TFM

Страница 1: ...nt Clamping screw Diffuser face Screw fixing diffuser face Sealing plug for connecting holes Installation and maintenance manual GB en TFM Particulate filter modules for ceilings TROX GmbH Heinrich Tr...

Страница 2: ...erence to the applicable standards and guidelines the state of the art and our expertise and experience of many years The manufacturer does not accept any liability for damages resulting from Non comp...

Страница 3: ...ular checks and smaller adjustments Personal protective equipment Personal protective equipment must be worn for any work in order to reduce health or safety haz ards to the minimum The appropriate pr...

Страница 4: ...unit from the effects of weather Protect the unit from humidity dust and con tamination Storage temperature 10 C to 50 C Relative humidity 95 max no condensation Assembly General information Fix the...

Страница 5: ...secure fixing after installation 1 Remove the clamping frame from the casing To do so loosen the clamping screws Fig 1 5 then remove the clamping frame Fig 1 4 Remove and dispose of the spacers keep...

Страница 6: ...stem as long as the modules were connected with one another correctly However the increased load on the suspension system must be taken into account 1 Remove the sealing plug on the connecting sides o...

Страница 7: ...d air conditioning system for 24 hours before you insert the filter element Volume flow rate balancing To adjust the ventilation and air conditioning system you first have to carry out volume flow rat...

Страница 8: ...ave inserted the filter element check that there are no leaks Leakage test on an installed filter on page 9 6 Installing the diffuser face Installing the diffuser face Fig 6 TFM assembly diffuser face...

Страница 9: ...sealing integrity testing leakage testing filter changes or cleaning require you to remove the diffuser face Fig 7 Removing the diffuser face Unscrew the knurled screws Fig 7 2 and remove diffuser fa...

Страница 10: ...er frame There are two ways to measure the differential pressure Permanent measurement Continuous differential pressure measurement and monitoring of the final differential pressure This is done with...

Страница 11: ...page 7 Disposal ENVIRONMENT Risk of harm to the environment due to the incor rect handling of hazardous materials and sub stances Filters and cleaning materials that have been contaminated with bacte...

Страница 12: ...ation It is then sufficient to clean and disinfect wipe the filter casing and the diffuser face this has to be done for the first time just before the ventilation and air conditioning system is switch...