background image

Ceiling installation

If possible, install the device before fixing the ceiling
tiles; if this is not possible, remove the adjacent
ceiling tiles.

Use only approved and adequately sized suspen-
sion systems (fixing material is not included in the
supply package). Dimensions and weight

Ä

 Chapter 4  ‘Technical data’ on page 4

.

If you have to install larger devices, it is best to
either ask someone to give you a hand or use a lift.

Fig. 8: Plenum box suspension

Variant

A [mm]

L

3

HS/HA

VS

PL50-1

178

216

Ä

 Table on page 5

PL50-2

223

254

PL50-3

278

310

PL50-4

318

375

1.

Fix the suspension parts such as ropes,
cables or metal hangers (Fig. 8/1) to the
ceiling.

2.

Turn up the suspension lugs.

3.

Use all of the available suspension points on
the plenum box.

Linear run

Fig. 9: Linking slot diffusers

4.

The supplied alignment plates (Fig. 9/1) help
you align slot diffusers for a continuous
linear arrangement.

Fix an alignment plate (2 each per diffuser)
on one side, then connect the next diffuser
to it.

Assembly

 

Air diffusers Slot Diffusers Type PURELINE50

7

Содержание PL50-1

Страница 1: ...or Lip seal Damper unit for volume flow rate balancing Optional equipment Installation instructions GB en Air diffusers Slot Diffusers Type PURELINE50 TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vl...

Страница 2: ...uthorised modifications The actual scope of delivery may differ from the information in this manual for special constructions additional order options or as a result of recent technical changes Person...

Страница 3: ...and install the air con trol elements so as not to accidentally change their position Transport on site CAUTION Danger of injury from sharp edges sharp cor ners and thin sheet metal parts Sharp edges...

Страница 4: ...nt for construction VS Fig 3 Plenum box variants 1 PL50 HS symmetric position of plenum box side entry spigot 2 PL50 HA asymmetric position of plenum box side entry spigot 3 PL50 VS symmetric position...

Страница 5: ...40 210 Variant R mm O mm PF HA SF HA PL50 1 152 Y 98 84 PL50 2 172 Y PL50 3 197 Y 82 PL50 4 229 Y Neck extension Y 0 22 47 72 97 121 Variant D mm C mm PL50 1 123 48 158 50 PL50 2 158 198 PL50 3 198 24...

Страница 6: ...earing structural elements Load suspension systems only with the weight of the product Adjacent components and con necting ducts must be supported separately The air terminal devices must remain acces...

Страница 7: ...lift Fig 8 Plenum box suspension Variant A mm L3 HS HA VS PL50 1 178 216 Table on page 5 PL50 2 223 254 PL50 3 278 310 PL50 4 318 375 1 Fix the suspension parts such as ropes cables or metal hangers...

Страница 8: ...d by others The end plates or end angles must be fitted with screws Fig 10 1 and Fig 11 1 Connecting corner sections Fig 12 Fitting a corner section with extended border Corner sections are supplied w...

Страница 9: ...th of installation opening when an end angle is used L1 29 Installation in continuous ceilings Fig 15 Installation with extended border into a con tinuous ceiling required length of installation openi...

Страница 10: ...ng Assemble the fixing material as shown The fixing material is supplied separately Then insert the fixture into the diffuser face and position it as required Move the diffuser face towards the plenum...

Страница 11: ...ing clip fixing Fig 18 Position of the spring ceiling thickness up to 9 mm Fig 19 Position of the spring ceiling thickness greater than 9 mm installation dimensions Diffuser faces on page 5 Assembly A...

Страница 12: ...nnection Variants with a double lip seal allow for a sufficiently tight connection additional sealing is not required Initial commissioning maintenance and cleaning Initial commissioning Before you st...

Страница 13: ...adjusted even after the diffuser face has been installed Fig 22 Setting the damper blade e g with a screwdriver Move the air control element near the spigot in such a way that it is possible to insert...

Страница 14: ...ing of the air control elements Alternating horizontal air discharge Alternating air control elements set to left hand or right hand air discharge Alternating angled air discharge Alternating air cont...

Страница 15: ...ndard apply Clean surfaces with a damp cloth Use only common household cleaners do not use any aggressive cleaning agents Do not use cleaning agents that contain chlorine Do not use equipment for remo...

Страница 16: ...Air diffusers Slot Diffusers Type PURELINE50 16...

Отзывы: