I N S T R U C T I O N S

67677 10/16 - (KPA)

MD-DPC-24

• English
• Deutsch
• Français

English

LIST OF FIGURES

The following figures are located at the back of 

the instructions:

Fig. 1:  Menu scheme

Fig. 2:  Dimensioned drawing

Fig. 3:   Position of transmitter in relation to 

bends and branches

Fig. 4:  Wiring diagram

Fig. 5:  

Relay operation diagram

Fig. 6:  Orientation of MD

INTRODUCTION

MD-DPC-24 is electronic air pressure / flow 

transmitter with integrated relay. The relay can 

be used as feedback to a BMS system or to 

control an audio/visual alarm. MD has an 0-10V 

and 0-20mA analog output for read-out of air 

pressure / flow.

MD use a semiconductor pressure element with 

no air throughput, thus protecting the unit from 

dust in the ventilation system. The pressure 

element is temperature compensated to provide 

accurate pressure measurement throughout 

the specified temperature range. See ‘Technical 

Data’.

INSTALLATION

MD should be attached to a firm, level surface 

using two screws. The pressure controller also 

functions with only one tube fitted to the tube 

connectors (+ or -). However, two tubes should 

always be fitted to maintain the enclosure rat-

ing.

Pressure is supplied to the measurement unit by 

tubes, the higher pressure being connected to 

the ‘+ tube connector’ and the lower pressure 

to the ‘÷ tube connector’ (see fig. 4). 

The pressure tubes must be as short as pos-

sible and must be secured in position to prevent 

vibration. 

To obtain the best possible results, pressure 

must be measured where there is least risk of 

turbulence, i.e. in the centre of the ventilation 

duct and at a distance of at least twice the 

width of the duct from bends and six times the 

width from branches (see fig. 3).

The housing is opened without the use of tools 

by pressing the snap lock beside the tube con-

nectors. 

Cable connection

The output from the MD is either voltage or cur-

rent controlled. The MD must be provided with 

a 24 VAC/DC power supply, see figure 4.

Setup menu

Use the buttons 

5

 , 

6

 and  

OK 

to navigate 

the menu. The buttons can be found on the 

backside off the lid. The menu is divided into 

three parts - Setup [ Set ], Relay [ ReL ] and 

Calibration [ CAL ]. Follow the menu scheme in 

figure 1 from the bottom up. Note the shown 

menues depends en the selection of Pressure 

or flow mode.

Setup - Pressure or flow mode 

 ]

Use Setup menu 1 to choose between Pressure 

or Flow mode. 

Setup - Pressure range 

 ]

Use Setup menu 2 to enter the pressure range. 

Pressure range defines the pressure at which 

the analogue output reaches the maximum 

value.

Setup - Pressure setpoint 

 ]

Use Setup menu 3 to enter the pressure set-

point. Minimum is 0 Pa and maximum is 2500 

Pa.

Setup - k-factor  

 ]

Use Setup menu 4 to enter the k-factor. The 

scale is 0.001 to 9999. The dot position shall 

be set before entering the value. The selected 

dot position will also apply to the display, when 

showing the current flow. After entering the 

k-factor, place the correct unit stamp on the 

MD front.

Setup - Flow range 

 ]

Use Setup menu 5 to enter the flow range. Flow 

range defines the flow at which the analogue 

output reaches the maximum value.

Setup - Flow setpoint 

 ]

Use Setup menu 6 to enter the air flow setpoint. 

The scale is 0.000 to 9999. The dot position 

shall be set before entering the value. The se-

lected dot position will also apply to the display, 

when showing the current flow. 

Setup - Damping 

 ]

Use Setup menu 7 to enter the damping. 

Minimum damping is 1 seconds and maximum 

damping is 30 seconds. A low damping can 

result in unsteady readings, while a higher 

damping gives a more steady reading but also 

a slower response time for the regulation. MD 

uses a ±2% dynamic average correction.

Setup - Analog output type 

 ]

Use Setup menu 8 to enter the analog output  

mode. It is possible to switch between 0 - 10 

VDC, 0 - 20 mA, 2 - 10 VDC and 4 - 20 mA as 

transmitter output.

Relay menu

Relay - Activation delay 

 ]

Use Relay menu 1 to enter the relay activation 

delay. Minimum delay is 0 seconds and maxi-

mum delay is 3600 seconds.

Relay - Hysteresis 

 ]

Use Relay menu 2 to enter the pressure 

hysteresis. Minimum hysteresis is 1% and 

maximum hysteresis is 50% of the pressure / 

flow setpoint. 

Relay - Invert relay 

 ]

Use Relay menu 3 to invert the default output 

state for the relay. This feature allow applica-

tions where an alarm can be sent both on out of 

range and on power supply failure. Invert relay 

has to be set to ON to obtain this function.

Relay - Invert LED 

 ]

Use Relay menu 4 to invert the default LED 

colour from Green to Red. This feature is useful 

when the MD is used as a pressure guard when 

controlling a heater element. Here, the LED 

should be Red until the setpoint is reached.

Calibration menu

When calibrating, make sure the MD are in a 

pressure free environment. To obtain a pressure 

free enviroment remove the two air tubes on the 

MD. For caution reasons, each calibration will 

only calibrate ±5 Pa.

Calibration 

 ]

Use Calibration menu 1 to calibrate. Confirm by 

pressing [ 

 ]. 

Factory reset 

 ]

Use Calibration menu 2 to set the MD back to 

factory reset. Confirm by pressing [ 

 ].

LED INDICATOR

An LED on the front side of the MD indicates 

the operating status. Operating range is defined 

as the setpoint ±hysteresis.

Non-inverted LED:

 A red light indicates that 

the operating range has not been reached. 

Conversely, a green light indicates that the 

operating range has been reached. 

Inverted LED:

 A green light indicates that the 

current pressure/flow is below the operating 

range. Conversely, a red light indicates that the 

pressure/flow is above the operating range.

A flashing red light indicates that an error is ac-

tive. See Troubleshooting for more information.

TECHNICAL DATA

Supply voltage ........  24 VAC/VDC ±15%. 50/60 Hz

Power consumption ...................................0.5 W

with relay active  .....................................1.0 W

Output ...............................0-10 VDC, 2-10 VDC,

0-20 mA, 4-20 mA

Electrical connection .......... 7 × spring terminals,  

max. 1.5 mm

2

Measuring range, pressure  ................ 0-2500 Pa

Accuracy relay setpoint ........0.5% x MV ±2.5 Pa

Accuracy output signal ........................................

 

1,5 % x MV + 0,3% x SR + 2,5 Pa

(MV=measured value / SR=set measuring range)

Maximum pressure ................................... 20 kPa

Ambient air humidity .......................10-95 %RH, 

non-condensing  

Housing dimensions [h

×

w

×

d] .. 91 × 75 × 38 mm

Cable gland ................................................PG11

Cable dimension ................................. ø3-10 mm

Pressure tubes ............................... 2 × ø6,2 mm.

Maximum load

 

0 - 10 VDC ........................................> 2.5 kΩ

 

0 - 20 mA ........................................ <= 450 Ω

Relay ................................... SPDT 30VDC/AC, 1A

Relay power consumption .........................0.1 VA

Содержание MD-DPC-24

Страница 1: ...he flow at which the analogue output reaches the maximum value Setup Flow setpoint Use Setup menu 6 to enter the air flow setpoint The scale is 0 000 to 9999 The dot position shall be set before enter...

Страница 2: ...stromgeregelt MD ist mit 24 V zu versorgen siehe Abb 4 Einstellungsmen Zur Navigation im Men die Tasten 5 6 und OK benutzen Die Tasten befinden sich rechts unten auf der Frontabdeckung Das Men teilt...

Страница 3: ...gemeinsam mit Haushaltsm ll entsorgt werden sondern m ssen entsprechend den geltenden lokalen Richtlinien bei einer Abfallsammelstelle abgeliefert werden HERSTELLER TROX GmbH Heinrich Trox Platz D 475...

Страница 4: ...te d alimentation L inversion du relais doit tre r gl e ON pour obtenir cette fonction Relais Inversion DEL Utilisez le menu 4 du relais pour inverser la couleur par d faut de la DEL du vert au rouge...

Страница 5: ...es produits marqu s de ce symbole ne doivent pas tre rebut s avec les d chets domestiques mais doivent tre livr s un centre de collecte de rebuts en conformit avec la r gle mentation locale en vigueur...

Страница 6: ...n Value Setpoint Red Invert relay normal output state Inverted output state Hysteresis 01 50 of maximum setpoint Relay activation delay 0000 3600 Sec Out Return to parent menu Analog output type 0 10V...

Страница 7: ...t k is entered into the MD Example of calculation The k factor data for the equipment is declared to be 5 6 based on liter per seconds l s You want the MD to handle flow in cubicmeters per hours m h O...

Страница 8: ...s A S ON 1 2 3 BR1009B01a 2014 OJ Electronics A S ON 1 2 3 BR1009B01a 2014 OJ Electronics A S ON 1 2 3 BR1009B01a 2014 OJ Electronics A S ON 1 2 3 BR1032A006a BR1032A013a Fig 4 Wiring diagram BR1032A0...

Отзывы: