5.7.4 Dry mortarless installation with fire batt
Fig. 94: Dry mortarless installation into a timber wall or CLT wall, with a fire batt
1
FKRS-EU
2.4
Fire batt with ablative coating
3.11
Solid wood wall / CLT wall
4.1
Solid ceiling slab / solid floor
6.10
Ablative coating around the perimeter,
d = at least 2.5 mm
6.19
Mineral wool > 1000 °C, > 80 kg/m³,
thickness = 20 mm, panel material around the
perimeter, leave out the actuator and release
mechanism; inspection openings must remain
accessible
6.20
Sleeve (can be ordered separately)
6.24
Elastomeric foam (flame-resistant, non-dripping)
The following applies in Germany: For notes on
the use of elastomeric foams, see
.
7.10
Trim panels (fire-resistant)
7.13
Cladding, single-layer, fire-resistant
7.14
Reinforcing board of the same material as the
wall
#
optional
*
6.19, 6.20 or 6.24 as an alternative
**
Installation near the floor analogous to
–
Up to EI 90 S
Installation
Solid wood walls > Dry mortarless installation with fire batt
Fire damper Type FKRS-EU
111
Содержание FKRS-EU