Operating mode default setting
In standard mode all function button fields for all
available functions are indicated as blue symbols
(i.e. not active). Activate the special operating
modes using the following buttons:
Activate increased operation
Pressing this button activates the increased volume
flow rate set for the controller (e.g. for
emergency operating mode). The
symbol colour changes to white.
Activate reduced operation
Pressing this button activates the reduced volume
flow rate set for the controller (e.g. for night
setback). The symbol colour changes
to white.
Shut-off
Pressing this key activates shut-off.
The symbol colour changes to white.
Deactivating special operating
modes
Pressing the respective button deactivates the
special operating mode. To select a new operating
mode without first deactivating the previous function
just press the corresponding function button.
Increased operation can be set for a limited
period of time. The increased volume flow will then
automatically be deactivated after the set delay.
Additional functions
Depending on the configuration and operating
mode default setting additional displays and
function buttons may be available.
Available function buttons are visible (highlighted
in blue or white). Function buttons that are not
available are not visible.
Examples
White symbol
The function is active. Pressing the button again
deactivates the function.
Blue symbol
This function is available but not active.
Pressing the button activates the
function.
Non-visible (grey) symbol
The function is not available. This depends on the
configuration of the controller or on the
current operating state.
White symbol blinks
Increased operation
OPEN mode (special operating mode) is active.
White symbol -
blinks after button has been
pressed
If you press a function button field and the white
symbol blinks briefly, the selected function cannot
be deactivated at the moment. The cur-
rent operating mode default setting is of
higher priority and cannot be overrid-
den on the fume cupboard.
9
BE-LCD-01 Operating and Installation Manual / Leaflet no. M375EV8 (01/2015)
5 Operation · Fume cupboard control