Overriding operating mode defaults set

by the central BMS

Operating mode default settings from the central

BMS can be overridden on the control panel for the

room.

Overriding the room operating mode 

temporarily

A centrally set room operating mode can be 

temporarily overridden at any time using the 

operating mode button on the control panel. The

operating mode selected on the room control  panel

remains active unless the central BMS sets another

operating mode. If the central BMS sets a different

default operating mode, that operating mode 

overrides the locally activated operating mode.
The operating mode for all room controllers is

always the operating mode that has been set last,

either by the central BMS or on the room control

panel.

Overriding the room operating mode 

permanently using manual control

A centrally set room operating mode

can be permanently overridden on the

room control panel. To do so, activate

manual control by pressing the 

corresponding button. This prevents

further overrides by the central BMS. You can then

set any other operating mode using the control

panel.
To resume the previous operating mode from the

central BMS, press the manual mode button again.
Manual operation can be set for a limited period.

The manual mode will then automatically be 

deactivated after the set delay, and the previous

operating mode will be resumed.

No override option for the room operating

mode

The central BMS can be configured to block 

the override function on the room control panel 

temporarily or permanently. In this case, manual

control cannot be used, and the control panel

shows only the centrally set operating mode. If a

user attempts to change the operating mode on 

the control panel, the active operating mode will

blink briefly.

Lighting

Use this button to switch the room lighting on or off.

This function is only available if the

room management function has been

configured accordingly.
This button can also be used for other

functions instead of or in addition to

switching the lighting on/off, e.g. for switching 

certain devices on/off.

Sun protection (e.g. blinds) 

Use these buttons to operate the sun protection,

e.g. blinds (by others).
These buttons are available only if this function has

been set for the control panel (configuration of the

room management function).

Open blinds

Close blinds

5 Operation · Room control

Содержание EASYLAB BE-LCD-01

Страница 1: ...ating and Installation Manual Leaflet no M375EV8 01 2015 The art of handling air The art of handling air Operating and Installation Manual EASYLAB Control panel BE LCD 01 for fume cupboard control and...

Страница 2: ...Fume cupboard lighting ________________ 10 Overriding operating mode defaults set by the central BMS____________________ 10 Operating states alarm messages fault displays ________________________ 11 5...

Страница 3: ...lation manual before starting any work and to comply with it The manual must be given to the facilities manager when handing over the system The facilities manager must include the manual with the sys...

Страница 4: ...reign matter if any If the device emits a smell or smoke have it checked by the manufacturer 4 BE LCD 01 Operating and Installation Manual Leaflet no M375EV8 01 2015 2 Safety and correct use Correct u...

Страница 5: ...green yellow red with text HIGH and LOW Connection socket for service and commissioning device Acoustic alarm acknowledgement Manual control Selection of operating mode Lighting or other equipment RM...

Страница 6: ...tion One button for the fume cupboard lighting One button for manual control Service socket The range of functions of the control panel can be adapted to project specific requirements using the EasyCo...

Страница 7: ...udes BE LCD 01 control panel with adapter Connecting cable approx 5 m patch cable blue Operating and installation manual Transport on site If possible take the control panel in the transport packaging...

Страница 8: ...of fume cupboard operating states and faults Display texts p 11 onwards The display of additional information can be configured Volume flow rate setpoint and actual values Face velocity actual value o...

Страница 9: ...me flow will then automatically be deactivated after the set delay Additional functions Depending on the configuration and operating mode default setting additional displays and function buttons may b...

Страница 10: ...ny other operating mode on the control panel This operating mode default setting can be terminated by pressing the manual control button again The fume cupboard controller then resumes the previous op...

Страница 11: ...e controller configuration the damper blade will remain open or will be shut shut off SC Automatic sash device Error message relating to the automatic sash device S1 Test function The general test fun...

Страница 12: ...f controllers 24 More than 24 controllers have been connected to the communcation cable Reduce the number of controllers C3 Communication cable termination The communication cable has not been termina...

Страница 13: ...supportive flow fan Control panel faults Code Message Explanation Actions remedial measures E1 Connection lost Communication between the control panel and the fume cupboard controller has been interru...

Страница 14: ...oard 1 Fume cupboard n Supply air Extract air Communication cable The BE LCD 01 control panel is used to display and control the most critical aerodynamic and safety related functions of an EASYLAB co...

Страница 15: ...and actual values The display can be adjusted using the configuration software BE LCD 01 Operating and Installation Manual Leaflet no M375EV8 01 2015 15 5 Operation Room control Volume flow rate cont...

Страница 16: ...This enables an automatic deactivation of the increased operation after the set delay Note Whether a defaulted operating mode applies to a controller in a room depends on the configuration of the cont...

Страница 17: ...an then set any other operating mode using the control panel To resume the previous operating mode from the central BMS press the manual mode button again Manual operation can be set for a limited per...

Страница 18: ...ic signal Alarm messages Code State Explanation Actions remedial measures A1 Volume flow rate too high The volume flow rate exceeds the setpoint value Check the actuator and the controller A2 Volume f...

Страница 19: ...either no differential pressure controller on the communication cable or the room management function is not active Include a differential pressure controller Activate differential pressure control i...

Страница 20: ...ler has been interrupted For technical reasons this text always appears in English Check the cable connection the control panel and the controller E2 CP CRC failure Communication between the control p...

Страница 21: ...e for mounting the control panel onto an adapter Danger Danger of electric shock Do not touch any live components Electrical equipment carries a dangerous electrical voltage during operation Only skil...

Страница 22: ...nto place See picture on p 23 5 Align the control panel including the cable with the adapter and press it onto the fixing points until it locks into place In the process carefully push the connecting...

Страница 23: ...to the right 5 Align the control panel including the cable with the base plate and press it back onto the base plate until it locks into place In the process carefully push the connecting cable back...

Страница 24: ...alarm in case the sash is opened beyond the maximum operational sash opening Enabling the function button for Increased Operation Enabling the function button for Reduced operation Enabling the funct...

Отзывы: