Installation opening without installation sub-
frame

L = Grille length to be ordered - L= 15 mm

H = Grille height to be ordered - H= 15 mm

Assembly of extension spigot for supply air
(optional)

Create an assembly opening in accordance
with the nominal size of the supply air grille.

Disassemble the spigot on the device (loosen
screws) and insert it from outside through the
plasterboard bulkhead into the device, then re-
attach it to the device.

Fig. 8: DID-E2 plasterboard bulkhead – air intake
through open shadow gaps

a

Minimum distance 50 mm, for distances
between 50 and 150 mm, a reduction in per-
formance of approx. 10% is expected, recom-
mended distance 

150 mm.

1

Plasterboard bulkhead (provided by others)

2

Ventilation grille for supply air (optional)

3

Suspension (provided by others)

4

Air intake through open shadow gaps

Connecting the water pipes

 CAUTION!

Hot surface!

Danger of burn or scald injuries when working on
the hot water system.

Before working on the unit, shut down the
system, depressurise it and let it cool down.

The heat exchanger is fitted with water flow and
water return connections:

Fig. 9: Example DID-E2 with 4-pipe-system, water
connections on the right

2-pipe system: 2 water connections

4-pipe system: 4 water connections

Flow and return can be freely selected

Make sure that the water temperature does not fall
below the dew point.

Water connection

Spanner

Type of connection

Copper tubes 12 

×

 1

mm

Soldered (rigid)
Flexible hoses (acces-
sory)

G 1/2" external thread
and flat seal

SW22

Screw connection
(rigid)
Flexible hoses (acces-
sory)

G 1/2" union nut and
flat seal

SW24

Screw connection
(rigid)
Flexible hoses (acces-
sory)

Connecting the water pipes

 

Active chilled beams Type DID-E2

10

Содержание DID-E2 Series

Страница 1: ...t for supply air optional 10 Ventilation grille for supply air optional 11 Installation subframe for secondary air grille optional 12 Safety cable for securing the grille 13 Secondary air grille optio...

Страница 2: ...ears The manufacturer does not accept any liability for damages resulting from Non compliance with this manual Incorrect use Operation or handling by untrained individuals Unauthorised modifications T...

Страница 3: ...ct use Incorrect use of the unit can lead to dangerous situations Never use the unit in areas with potentially explosive atmos pheres in humid rooms in rooms with aggressive or dust laden air Importan...

Страница 4: ...ses 6 bar Max operating temperature 75 C 55 C when using flexible connecting hoses Minimum operating temperature 6 C NOTICE Water damage by condensate An undershooting of the dew point temperature cau...

Страница 5: ...length LN 1000 x 320 1000 x 512 1125 x 320 1125 x 512 1250 x 320 1250 x 512 DID E2 15 5 20 5 17 0 23 0 19 0 25 0 Supply air spigot Z 1 7 1 7 1 9 1 9 2 1 2 1 Installation subframe ERS 1 4 1 5 1 6 1 7 1...

Страница 6: ...0 x 320 1000 x 512 1125 x 320 1125 x 512 1250 x 320 1250 x 512 DID E2 VC 21 5 26 5 24 0 29 5 26 0 32 0 Supply air spigot Z 1 7 1 7 1 9 1 9 2 1 2 1 Installation subframe ERS 1 4 1 5 1 6 1 7 1 8 1 9 Con...

Страница 7: ...g 4 Carrying the unit in pairs Use only lifting and transport gear designed for the required load Always secure the load against tip ping and falling Upon delivery carefully remove the packaging and c...

Страница 8: ...rk in pairs preferably use a lift DANGER Danger of death from the fall of a suspended unit Only use fixing materials designed for the required load Use all hanging brackets supplied Stand clear of sus...

Страница 9: ...d provided by others 3 Suspension provided by others 4 Installation subframe for secondary air grille optional Assembly of the installation subframe optional Create an assembly opening in accordance w...

Страница 10: ...uspension provided by others 4 Air intake through open shadow gaps Connecting the water pipes CAUTION Hot surface Danger of burn or scald injuries when working on the hot water system Before working o...

Страница 11: ...with a spanner NOTICE Subzero temperatures will damage the heat exchanger Only fill the heat exchanger if there is no danger of freezing 3 Fill the heat exchanger and vent it To fill the system use c...

Страница 12: ...terminal box Fig 1 2 24 V supply voltage only via safety trans former Terminal connections No Designation Wire colour Function 1 Black 24 V AC DC supply voltage 2 Red 3 Y White Control signal force s...

Страница 13: ...used Cleaning the heat exchanger Personnel Specialist personnel Protective equipment Industrial safety helmet Safety shoes Protective gloves CAUTION Hot surface Danger of burn or scald injuries when w...

Страница 14: ...ury from the grille falling Safety cables are provided on the optional installation subframe for securing the grille When adjusting the grille attach the safety cables to the grille If an installation...

Страница 15: ...Active chilled beams Type DID E2 15...

Страница 16: ...Active chilled beams Type DID E2 16...

Отзывы: