Adjustment sticker
Fig. 26: Adjustment sticker XM0 and XS0
①
Commission number. Order number
②
Type designation of terminal unit
③
Nominal size
④
Control component
⑤
Operating mode
M
ð
Modbus
F
ð
constant value
V
ð
variable
0 or 2
ð
characteristic type
⑥
Characteristics 0 – 10 V or 2 – 10 V
⑦
Volume flow rate ranges q
vmin
– q
vmax
or constant
value
⑧
Nominal volume flow rate q
vnom
⑨
Hardware type designation
⑩
Control components:
OF
ð
equipped at the factory
SP
ð
replacement part
⑪
Serial number
⑫
Test ID number
8.2 Service tools functional overview
Functions
Display
Adjust-
ment
device
PC soft-
ware
Actual value display
✔
✔
✔
Changes from q
vmin
and q
vmax
✔
✔
✔
Mode setting (0…10
V / 2…10 V /
Modbus)
✔
✔
✔
Record running
times (operating
time, running time,
ratio)
✖
✖
✔
Perform test run
function
✔
✔
✔
Setpoint value signal
in Y [V]
✔
✔
✔
Actual value return
U [V]
✔
✔
✔
Assign bus address
✔
✔
✔
Set Modbus param-
eter sets
✔
✔
✔
8.2.1 Display XM0 / XS0
Current values can be read, operating parameters can
be set and the status can be read from the control com-
ponent.
After applying the supply voltage, various functions are
available.
Additional information:
Chapter 7 ‘Operation and status of the control
8.2.2 Adjustment device GUIV3-M
Fig. 27: GUIV3-M is connected to the control compo-
nent by means of the cable provided in the supply
package.
Commissioning and operation
Service tools functional overview > Adjustment device GUIV3-M
Control component Compact XM0 • XS0 for VAV terminal unit TVE
27