Inverter DC Volt: 12
Wire Gauge
Twin 00 (2/0)
Watts
6
4
2
0
00 (2/0)
(UT3012UL only)
500
15 ft
25 ft
39 ft
62 ft
79 ft
158 ft
700
11 ft
18 ft
28 ft
44 ft
56 ft
112 ft
1000
N/R
12 ft
20 ft
31 ft
39 ft
78 ft
2000
N/R
N/R
N/R
16 ft
20 ft
40 ft
3000
N/R
N/R
N/R
10 ft.
13 ft.
26 ft
†
N/R = Not Recommended. NOTE: Acceptable power is directly related to cable length (i.e. - the
shorter the cable, the better the performance)
Note on Labeling
Two symbols are used on the RV labels.
V~
: AC Voltage
V
: DC Voltage
Minimum Recommended Cable Sizing Chart
†
Use in conjunction with DC wiring connection instructions in the Battery Connection section.
Specifications
MODEL NUMBER:
UT750UL
UT1250UL
UT2012UL
UT3012UL
Series Number:
AGAP5088
AGAP5217
AGAP5290
AGAP4669
Agency Approvals:
cTUVus
cTUVus
cULus
cULus
AC Input Connection (for optional charging):
Input Cord
Input Cord
Input Cord
Hardwire AC Input
AC Output Connection:
Two GFCI Outlets
Two GFCI Outlets
Two GFCI Outlets
Hardwire AC Output
INVERTER
Continuous Power (@ 20 C):
750
1250
2000
3000
OverPower™ Peak Surge Power:*
1125
1875
3000
4500
Double Boost™ Peak Surge Power:*
1500
2500
4000
6000
Maximum Output AC Current (Continuous):
6.3 A
10.4 A
16.7 A
25 A
UL-Recognized DC Fuse Required:
One 80 A
One 200 A
Two 200 A
Two 275 A
DC Input Current @ Nominal V DC Full Load:
72 A
127 A
190 A
290 A
DC Input Volts (Nominal):
12 VDC
12 VDC
12 VDC
12 VDC
DC Input Voltage Range:
10-15 VDC
10-15 VDC
10-15 VDC
10-15 VDC
Output Volts (Nominal):
120 VAC, ± 5%
120 VAC, ± 5%
120 VAC, ± 5%
120 VAC, ± 5%
Output Frequency (Nominal):
60 Hz, ± 0.5 %
60 Hz, ± 0.5 %
60 Hz, ± 0.5%
60 Hz, ± 0.5%
Efficiency:
88% to 94%, depending on
88% to 94%, depending on
88% to 94%, depending on
99% to 94%, depending on
load and temperature
load and temperature
load and temperature
load and temperature
BATTERY CHARGER
Charging Capacity DC:
Selectable 45 A** / 11 A
Selectable 40 A** / 10 A
Selectable 60 A** / 15 A
Selectable 140 A** / 35 A
Input Current AC:
9.3 A
8.2 A
12 A
30 A
Acceptance Volts VDC:
Selectable 14.4V** /
Selectable 14.4V** /
Selectable 14.4 V** /
Selectable 14.4 V** /
14.2 V Wet** / Gel
14.2 V Wet** / Gel
14.2 V Wet** / Gel
14.2 V Wet** / Gel
Float Volts DC (Wet/Gel):
13.3 V (13.6 V)
13.3 V (13.6 V)
13.3 V (13.6 V)
13.3 V (13.6 V)
Input Volts (Nominal):
120 VAC
120 VAC
120 VAC
120 VAC
* OverPower duration (up to 1 hour). DoubleBoost duration (up to 10 seconds). Actual duration depends on battery age, battery charge level and ambient temperature. **Factory setting. The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice. This
product designed and engineered in the USA.
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number
can be found on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this
product, always refer to the series number. The series number should not be confused with the marking name or model number of the product.
1111 W. 35th Street Chicago, IL 60609 • (773) 869-1234 • www.tripplite.com
Copyright © 2005 Tripp Lite. All rights reserved.
200511035 93-2512
WARRANTY REGISTRATION
Visit www.tripplite.com/warranty today to register the warranty for
your new Tripp Lite product. You'll be automatically entered into a
drawing for a chance to win a FREE Tripp Lite product!*
* No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.
WARRANTY REGISTRATION:
register online today for a chance to win a FREE Tripp Lite product—www.tripplite.com/warranty