The UPS’s control panel lights will turn on in the sequences below to signal that the UPS is having 
operational difficulties.

Lights (On/Flashing) and Condition 

Solution

On: REPLACE BATT

 

Let the UPS system charge for at least 12 hours 

Condition: Replace Battery

 

and perform a self test using the "ON/Test  

 

Switch" as described on page 6. If the light  

 

continues to stay on, contact Tripp Lite for service.

On: BATT LOW, ON BATT 

Prepare for imminent UPS shutdown.

 

Condition: Battery Low
On: BYPASS, LINE, LOAD, OVERLOAD 

Reduce the load the UPS supports. 

Condition: On Bypass due to Overload
Flashing: OVERLOAD 

Remove the cause of the short circuit 

 

Condition: Short Circuit

 

from the UPS output.

On: FAULT 

Check the utility line for wiring problems such as 

Condition: Wiring Fault

 

reversed line and neutral or a missing ground.

On: FAULT, 100% 

Restart the UPS. If the problem persists,  

Condition: Battery Voltage too High

 

contact Tripp Lite for repairs.

On: FAULT, BYPASS, LINE, 50% 

Restart the UPS. If the problem persists,

 

Condition: On Bypass due to 

 

contact Tripp Lite for repairs. 

High Output Voltage
On: FAULT, BYPASS, LINE 

Restart the UPS. If the problem persists,

 

Flashing: 50% 

contact Tripp Lite for repairs.

 

Condition: On Bypass due to

 

 

Low Output Voltage
On: FAULT, BYPASS, LINE, 25% 

Restart the UPS. If the problem persists,

 

Condition: On Bypass due to High 

 

contact Tripp Lite for repairs.  

Bus Voltage
On: FAULT, BYPASS, LINE 

Restart the UPS. If the problem persists,

 

Flashing: 25% 

contact Tripp Lite for repairs.

 

Condition: On Bypass due to Low 

 

 

Bus Voltage
On: BYPASS, LINE   

Check the UPS to be sure that there is 

 

Flashing: FAULT 

adequate space for air to circulate near

 

Condition: On Bypass due to High  

 

the vents and that the fan is working 

Internal Temperature

 

properly. Restart the UPS.

Flashing: LINE 

This indicates that utility power is too high or low

 

Condition: Input Abnormal

 

for the UPS to operate in BYPASS mode, so if an  

 

inverter failure occurs, the UPS will deliver no output.

On: FAULT, 50%

 

Restart the UPS. If the problem persists, 

Flashing: LINE 

contact Tripp Lite for repairs.

 

Condition: No Output due to High 

 

Output

 

Voltage and Abnormal Input

On: FAULT  

Restart the UPS. If the problem persists,

 

Flashing: LINE, 50%

 

contact Tripp Lite for repairs. 

Condition: No Output due to Low

 

Output Voltage and Abnormal Input
On: FAULT, 25% 

Restart the UPS. If the problem persists,

 

Flashing: LINE

 

contact Tripp Lite for repairs.  

Condition: No Output due to High

  

Bus Voltage and Abnormal Input
On: FAULT 

Restart the UPS. If the problem persists,

 

Flashing: LINE, 25%

 

contact Tripp Lite for repairs.  

Condition: No Output due to Low

 

Bus Voltage and Abnormal Input
Flashing: LINE, FAULT 

Check the UPS to be sure that there is adequate

 

Condition: No Output due to High

 

space for air to circulate near the vents and that 

Internal Temperature and Abnormal 

 

the fan is working properly. Restart the UPS. 

Input 

If the problem persists, contact Tripp Lite for repairs.

Troubleshooting

10

200907169  93-2615.indd   10

8/11/2009   10:15:05 AM

Содержание SmartOnline 2-9USTAND

Страница 1: ...Systems Intelligent True On Line Operation Pure Sine Wave Output Zero Transfer Time 1000VA 2200VA Capacities Extended Run Options Warranty Registration 12 Copyright 2009 Tripp Lite All rights reserve...

Страница 2: ...d is sized properly by using properly gauged wire and properly connected by having a 3 prong grounded plug on one end and a 3 prong receptacle on the other end of this cord The UPS itself must be dire...

Страница 3: ...tach mounting ears D to the front mounting holes of your equipment E using the screws provided F The ears should face forward Using an assistant if necessary lift your equipment and slide it onto the...

Страница 4: ...conds until you hear a beep Release it Your UPS will begin providing AC power to its outlets The ON LINE LED will illuminate Note The UPS system will function properly upon initial startup however max...

Страница 5: ...rnal batteries you are connecting match the voltage listed on your UPS s battery connector All UPS models come with a robust internal battery system all models feature connectors that accept optional...

Страница 6: ...rging and the fan will continue to cool internal components even after you turn the UPS receptacles off To turn the UPS OFF completely including the charger disconnect the UPS s power cord after press...

Страница 7: ...four dual function LEDs is displaying the load level of your UPS BATT ACTIVE METER LED This green light will illuminate when your UPS is operating from battery power to indicate that the set of four...

Страница 8: ...ustomer Support at 773 869 1234 for the appropriate Tripp Lite battery pack to connect Refer to instructions available with the Battery Pack for complete connection information and safety warnings Fan...

Страница 9: ...PowerAlert Software and the appropriate cable did not come with your UPS you can obtain the software FREE via the Web at www tripplite com Any user supplied DB9 pass through or USB cable may then be u...

Страница 10: ...YPASS LINE Restart the UPS If the problem persists Flashing 25 contact Tripp Lite for repairs Condition On Bypass due to Low Bus Voltage On BYPASS LINE Check the UPS to be sure that there is Flashing...

Страница 11: ...wer cord from the wall outlet Next disconnect all equipment to avoid battery drain If you plan on storing your UPS for an extended period of time fully recharge the UPS batteries once every three mont...

Страница 12: ...the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can r...

Отзывы: