background image

 

17-12-143 - EN

 

 Revised by V. Li 08/22/2017 

 

HC350S, HCINT350S Series Power Module Application Guidelines 

Series AGSM5396, AGRT0829 

 

SAVE THESE INSTRUCTIONS

 

– This manual contains 

IMPORTANT SAFETY 

INSTRUCTIONS

 for that should be followed during installation and maintenance of the 

UPS and batteries.

 

 
The HC350S and HCINT350S series of hospital cart power modules are designed to 
provide AC voltage output power from either utility provided AC input voltage or from 
inverting 12VDC power from a sealed lead acid battery.  To ensure proper operation the 
following guidelines should be observed: 
 

1.  The power module can support AC loads up to a maximum of 400VA or 300W. 
2.  The power module charger is intended to be used with a 12V sealed lead acid 

absorbed glass mat (AGM) battery with a 33AH to 66AH

 

rating.  Batteries rated 

at less than 33AH are not recommended since the charger current of 12A would 
reduce the battery cycle life of smaller batteries.  

3.  Adequate provision for airflow needs to be provided at both the inlet and outlet 

vents of the power module.  There should be at least 0.5 inches of clear space 
on the fan end and on the vented end of the power module.  A baffle or air 
deflector is recommended at the fan end so that the air intake is raised at least 6 
inches above floor level to prevent dust accumulation inside the power module.  

4.  The power module may be mounted in any orientation.  Four 8-32 threaded 

inserts are provided on the surface with the AC input cord to facilitate mounting. 

5.  The AC voltage input and output connections are made with user supplied cables 

to the IEC input and output connectors on the power module.  Use only with 
approved plug/cord sets according to the equipment electrical ratings.

  

No 

external fusing is needed since safe operation is assured by internal non-
replaceable 10A fuses.  However, if a customer wishes to prevent the internal 
fuses from blowing in the event of an extreme overload, then an external fuse or 
circuit breaker rated at 6A to 10A (120VAC models) or 3A to 5A (230V models) 
should be provided on the AC voltage input. 

6.  The 12V battery input is made with a user supplied cable to the Anderson DC 

connector on the power module.  Proper polarity must be observed.  The 
recommended wire size is 8AWG in order to keep the voltage drop in the cable to 
less than 0.1V.  The length of cable between the battery and the power module 
should be less than 30 inches.  A user supplied 40A to 50A automotive style fuse 
is required in the positive lead of the battery (within 18 inches of the battery 
positive terminal). 

7.  Additional bonding is needed to connect the battery negative terminal to the case 

of the power module.  The wire (or metal frame of the cart) should be short (less 
than 18 inches) and preferably of the same gauge as the other battery wires 

Содержание HC350S Series

Страница 1: ...nt dust accumulation inside the power module 4 The power module may be mounted in any orientation Four 8 32 threaded inserts are provided on the surface with the AC input cord to facilitate mounting 5 The AC voltage input and output connections are made with user supplied cables to the IEC input and output connectors on the power module Use only with approved plug cord sets according to the equipm...

Страница 2: ...C function in order to prevent damage to the battery due to over discharge 10 The power module will not turn on unless connected to a battery that has a voltage greater than 9 6V If the battery voltage is less than 9 6V it is assumed to be defective and the charger is inhibited in order to prevent possible outgassing of the battery 11 The power module reports Battery Capacity through its USB port ...

Страница 3: ...déquat doit être fourni au niveau des évents d entrée et de sortie d air du module de puissance Il devrait y avoir un espace libre d au moins 1 27 cm 0 5 pouce de l extrémité du ventilateur et de l extrémité mise à l air libre du module de puissance Une chicane ou un déflecteur d air est recommandé à l extrémité du ventilateur de façon à ce que l entrée d air soit soulevée d au moins 15 24 cm 6 po...

Страница 4: ...nectés ou s ils sont intervertis le module de puissance ne fonctionnera pas L interface utilisateur à distance peut être une interface utilisateur à distance Tripp Lite ou une interface utilisateur à distance conçue par l utilisateur qui répond aux caractéristiques techniques de Tripp Lite 9 Le module de puissance inclut une fonction de seuil de sectionnement bas qui éliminera toute charge sur la ...

Страница 5: ... Le rapport sur le de capacité de la batterie et le voyant à DEL ne seront exacts qu une fois la charge initiale complétée Après l initialisation le module de puissance indiquera correctement le de capacité de la batterie car la batterie est déchargée et chargée à plusieurs reprises Toutefois chaque fois que la batterie est remplacée l initialisation devra être répétée ...