Specifications
MODEL NUMBER:
EMS1012UL
EMS1250UL
EMS2012UL
Series Number:
AGAP100012MV3
AGAP5094
AGAP200012MV3
AC Input Connection:
Input Cord
Input Cord
Hardwire
INVERTER
Common Specifications for All Models
• DC Input Volts (Nominal): 12 VDC • DC Input Voltage Range: 10 - 15 VDC • Output Volts (Nominal): 120 VAC, ± 5% • Output Frequency (Nominal): 60 Hz, ± 0.5%
• Efficiency: 88% to 94% depending on load and temperature
Tripp Lite Inverter/Chargers include a Battery Charge Conserver (Load Sense) Control which saves battery power by allowing users
to set the minimum load level at which the unit’s inverter turns on. Users can significantly reduce the No Load DC Input Current
(approximately 1 A to 3 A for all models) to a very low amp level with the use of this control.
Continuous Power (@ 20 C):
1000
1250
2000
OverPower™ Peak Surge Power:*
1500
1875
3000
Double Boost™ Peak Surge Power:*
2000
2500
4000
Maximum Output AC Current (Continuous):
8.3 A
10.4 A
16.7 A
UL-Recognized DC Fuse Required:
200 A
200 A
400 A
DC Input Current @ Nominal V DC
Full Load
95 A
127 A
190 A
BATTERY CHARGER
Common Specifications for All Models
• Acceptance Volts VDC: Selectable 14.4 V** / 14.2 V Wet** / Gel • Float Volts DC (w/gel): 13.3 V (13.6 V) • Input Volts (Nominal): 120 VAC
Charging Capacity DC:
55 A**/14 A
55 A** / 14 A
100 A**/25 A
Input Current AC:
11.5 A
11 A
20A
LINE VAC OPERATION
Common Specifications for All Models
• Minimum Input Volts (Transfer to Battery): Selectable 75,** 85, 95 or 105 VAC • Maximum Input Volts (Transfer to Battery): Selectable 135** or 145 VAC
†
• Input
Frequency (Nominal): 60 Hz, ±10%
Maximum Input AC Current (Continuous, Charger at Maximum):
12 A
12 A
38 A
Maximum Bypass AC Current (load circuit breaker limited):
12 A
12 A
20 A
* OverPower duration (up to 1 hour). DoubleBoost duration (up to 10 seconds). Actual duration depends on battery age, battery charge level and ambient temperature. **Factory setting.
†
Not applicable to Model EMS1250UL; switches select Charger Enable/Charger Inhibit.
The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.
Note on Labeling
Two symbols are used on the EMS labels.
V~
: AC Voltage
V
: DC Voltage
Inverter/Charger DC Volt: 12
Wire Gauge
Watts
6
4
2
0
00 (2/0)
500
15 ft
25 ft
39 ft
62 ft
79 ft
700
11 ft
18 ft
28 ft
44 ft
56 ft
1000
N/R
12 ft
20 ft
31 ft
39 ft
2000
N/R
N/R
N/R
16 ft
20 ft
2400
N/R
N/R
N/R
13 ft
16 ft
3000
N/R
N/R
N/R
10 ft
13 ft
Minimum Recommended Cable Sizing Chart
*
Use in conjunction with DC wiring connection instructions in the Battery Connection section.
* N/R = Not Recommended. NOTE: Acceptable power is directly related to cable length (i.e. the shorter the cable, the better the performance)