Operation

Switch Modes

After configuring, mounting and connecting your Inverter/Charger, you
are able to operate it by switching between the following operating
modes as appropriate to your situation:

AUTO/REMOTE:

Switch to this mode when you

need constant, uninterrupted AC power for connected
appliances and equipment. The Inverter/Charger will
continue to supply AC power to connected equipment
and to charge your connected batteries while utility-
or generator-supplied AC power is present. Since the
inverter is ON (but in Standby) in this mode, it will automatically
switch to your battery system to supply AC power to connected
equipment in the absence of a utility/generator source or in over/under
voltage situations. “AUTO/REMOTE” also enables an optional
remote control module (Tripp Lite model APSRM4, sold separately)
to function when connected to the unit. 

CHARGE ONLY

: Switch to this mode when you

are not using connected appliances and equipment in
order to conserve battery power by disabling the
inverter. The Inverter/Charger will continue to supply
AC power to connected equipment and charge con-
nected batteries while utility- or generator-supplied
AC power is present. However, since the inverter is OFF in this
mode, it WILL NOT supply AC power to connected equipment in the
absence of a utility/generator source or in over/under voltage situations.

OFF: 

Switch to this mode to shut down the

Inverter/Charger completely, preventing the inverter
from drawing power from the batteries, and preventing
utility AC from passing through to connected equipment
or charging the batteries. Use this switch to automatically
reset the unit if it shuts down due to overload or
overheating. First remove the excessive load or
allow the unit to sufficiently cool (applicable to your situation).
Switch to “OFF”, then back to “AUTO/REMOTE” or “CHARGE
ONLY” as desired. If unit fails to reset, remove more load or allow
unit to cool further and retry. Use an optional remote control mod-
ule (Tripp Lite model APSRM4, sold separately) to reset unit due to
overload only.

Indicator Lights

Your Inverter/Charger (as well as an optional Tripp Lite Remote
Control Module, sold separately) is equipped with a simple, intuitive,
user-friendly set of indicator lights. These easily-remembered “traffic
light” signals will allow you, shortly after first use, to tell at a glance
the charge condition of your batteries, as well as ascertain operating
details and fault conditions.

LINE Green Indicator:

If the operating mode

switch is set to “AUTO/REMOTE,” this light will
ILLUMINATE CONTINUOUSLY when your con-
nected equipment is receiving continuous AC power
supplied from a utility/generator source.
If the operating mode switch is set to “CHARGE ONLY,” this light
will FLASH to alert you that the unit’s inverter is OFF and will NOT
supply AC power in the absence of a utility/generator source or in
over/under voltage situations.

INV (Inverting) Yellow Indicator: 

This light will

ILLUMINATE CONTINUOUSLY whenever connected
equipment is receiving battery-supplied, inverted AC
power (in the absence of a utility/generator source or
in over/under voltage situations). This light will be off
when AC power is supplying the load. This light will
FLASH to alert you if the load is less than the Battery Charge
Conserver (Load Sense) setting.

LOAD Red Indicator: 

This red light will ILLUMI-

NATE CONTINUOUSLY whenever the inverter is
functioning and the power demanded by connected
appliances and equipment exceeds 100% of load
capacity. The light will FLASH to alert you when the
inverter shuts down due to a severe overload or over-
heating. If this happens, turn the operating mode switch “OFF”;
remove the overload and let the unit cool. You may then turn the
operating mode switch to either “AUTO/REMOTE” or “CHARGE
ONLY” after it has adequately cooled. This light will be off when
AC power is supplying the load. 

BATTERY Indicator Lights: 

These three lights will illuminate in

several sequences to show the approximate charge level of your con-
nected battery bank and alert you to two fault conditions:

Approximate Battery Charge Level*

Indicator Illuminated

Battery Capacity 

(Charging/Discharging)

Green

91%–Full

Green & Yellow

81%–90%

Yellow

61%–80%

Yellow & Red

41%–60%

Red

21%–40%

All three lights off

1%–20%

Flashing red

0% (Inverter 
shutdown)

* Charge levels listed are approximate. Actual conditions vary 
depending on battery condition and load.

Fault Condition

Indicator Illuminated

Fault Condition

All three lights 

Excessive discharge 

flash slowly*

(Inverter shutdown)

All three lights 

Overcharge (Charger 

flash quickly**

shutdown)

*Approximately ½ second on, ½ second off. See Troubleshooting section. ** Approximately ¼ sec-
ond on, ¼ second off. May also indicate a battery charger fault exists. See Troubleshooting sec-
tion.

Resetting Your  Inverter/Charger 
to Restore AC Power

Your Inverter/Charger may cease supplying AC power or DC charging
power in order to protect itself from overload or to protect your elec-
trical system. To restore normal functioning:

Overload Reset:

Switch operating mode switch to “OFF” and

remove some of the connected electrical load (ie: turn off some of
the AC devices drawing power which may have caused the overload
of the unit). Wait one minute, then switch operating mode switch
back to either “AUTO/REMOTE” or “CHARGE ONLY.” 

Output Circuit Breaker Reset: 

Alternatively, check output circuit

breaker(s) on the unit’s front panel. If tripped, remove some of the elec-
trical load, then wait one minute to allow components to cool before
resetting the circuit breaker. See Troubleshooting for other possible
reasons AC output may be absent.

1

2

3

4

5

6

7

1

2

1

2

3

4

5

6

7

1

2

200711152 93-2752 230V APS OM.qxd  11/29/2007  2:15 PM  Page 4

Содержание APINT Series

Страница 1: ...ection Automatic Overload Protection Ideal Output for All Loads including computers Frequency Controlled Output Fast Load Switching Balanced Load Sharing Better for Your Batteries Faster Battery Recha...

Страница 2: ...water might accumulate Mounting should be in the driest location available Leave a minimum of 5 cm clearance at front and back of the Inverter Charger for proper ventilation The heavier the load of co...

Страница 3: ...utility or generator supplied AC power when used with a user supplied cable with country specific plug Hardwire AC Input Output Terminal Strip not on corded models securely connects the Inverter Charg...

Страница 4: ...CHARGE ONLY this light will FLASH to alert you that the unit s inverter is OFF and will NOT supply AC power in the absence of a utility generator source or in over under voltage situations INV Invert...

Страница 5: ...tage Point and or decreasing the Low AC Voltage Point you will reduce the number of times your unit switches to battery due to voltage swings Group B DIP Switches Select Load Sharing OPTIONAL Your Inv...

Страница 6: ...ly from full output at 33 of the Inverter Charger s load rating to about 33 of full output at full load Least Limiting B1 Up B2 Down Charger limiting begins at when the Inverter Charger s load reaches...

Страница 7: ...ur batteries with utility or genera tor supplied AC power Compensate for inefficiency by multiplying this number by 1 2 This will give you a rough estimate of how many amp hours of battery power from...

Страница 8: ...izontal surface leaving the heads slightly raised Slide the Inverter Charger back over the fasteners to engage the mounting slots molded on the bottom of the Inverter Charger cabinet Install and tight...

Страница 9: ...iring Though your Inverter Charger is a high efficiency con verter of electricity its rated output capacity is limited by the length and gauge of the cabling run ning from the battery to the unit Use...

Страница 10: ...te over the hardwire terminal box Remove the knockout covers closest to the desired electrical source and to your equipment Attach 1 28 cm diameter conduits user supplied to the knockouts and thread w...

Страница 11: ...e fuse Battery cabling is loose Check and tighten or replace cabling Unit has shut down due to battery overcharge preventing Disconnect any auxiliary chargers Reset by moving Operating Mode battery da...

Страница 12: ...es integrada Isobar Protecci n autom tica contra sobrecarga Salida ideal para cualquier carga incluyendo computadoras Salida controlada por frecuencia R pida conmutaci n de carga Reparto de carga bala...

Страница 13: ...a de 5 cm en la parte frontal y posterior del inversor cargador para una adecuada ventilaci n A mayor carga del equipo conectado la unidad generar m s calor No instale el inversor cargador directament...

Страница 14: ...CA de la red o suministrada por un generador cuando se emplea con un cable suministrado por el usuario con alg n enchufe de uso local especial Regleta cableada de terminales de entrada salida de corri...

Страница 15: ...e NO suministrar energ a de corriente alterna en ausencia de alimentaci n de la red o de un generador o en casos de sobrevoltaje o bajo voltaje Indicador INV Inversi n amarillo Esta luz se ILUMINAR CO...

Страница 16: ...dad de veces que su unidad cambia a bater a debido a variaciones de voltaje Conmutadores DIP Grupo B Seleccionar reparto de carga OPCIONAL Su inversor cargador presenta un cargador de bater a de alta...

Страница 17: ...alida completa a plena carga M nima limitaci n B1 arriba y B2 abajo La limitaci n del cargador comien za cuando la carga del inversor cargador alcanza el 66 de su capacidad total de carga La salida de...

Страница 18: ...por 1 2 Esto le dar un estimado grueso de cuantos amperios hora de energ a de bater a de una o varias bater as debe conectar a su inversor cargador NOTA La capacidad de amperios hora de una bater a u...

Страница 19: ...el inversor cargador hacia atr s sobre los tornillos para enganchar las ranuras de montaje moldeadas en la parte inferior del gabinete del inversor cargador Instale y apriete dos tornillos de 6 mm sum...

Страница 20: ...iciencia su capacidad de salida est limitada por la longitud y el calibre del cableado desde la bater a hasta la unidad Use la longitud m s corta y el calibre de mayor di metro del cableado m ximo cal...

Страница 21: ...as cubiertas de los agujeros ciegos m s cercanas a la fuente el ctrica deseada y a su equipo Conecte tubos de 1 2 de di metro suministrados por el usuario a los agujeros ciegos y pase los conductores...

Страница 22: ...Revise y reemplace el fusible El cableado de la bater a est flojo Revise y ajuste o reemplace el cableado La unidad se ha apagado debido a sobrecarga de la bater a Desconecte cualquier cargador auxili...

Страница 23: ...ection automatique contre les surcharges Sortie id ale pour toutes les charges y compris les ordinateurs Sortie fr quence contr l e Commutation rapide de la charge Partage quilibr e de la charge Meill...

Страница 24: ...placement le plus sec possible Maintenez un d gagement minimal de 5 cm l avant et l arri re de l onduleur chargeur pour garantir une bonne circulation d air Plus la charge de l quipement branch est lo...

Страница 25: ...cteur ou produit par une g n ratrice l aide d un c ble quip d une fiche sp cifique au pays fourni par l utilisateur Barrette raccordement fixe de bornes d entr e de sortie CA pas sur les mod les cordo...

Страница 26: ...us avertir que l onduleur de l unit est OFF ferm et Ne fournira Pas de courant CA en l absence d une source du secteur ou d une g n ratrice ou dans des situations de basse ou haute tension Voyant jaun...

Страница 27: ...int haut de tension d entr e CA ou en abaissant le point bas de tension d entr e CA vous r duirez le nombre de fois o votre unit passera sur batterie cause de variations de tension Groupe B de commuta...

Страница 28: ...de l onduleur chargeur environ 33 de la sortie pleine pleine charge Limitation minimale No B1 en haut ET No B2 en bas La limitation du chargeur commence lorsque la charge de l ond uleur chargeur atte...

Страница 29: ...ne estimation grossi re de la puissance de batterie en A h d une ou de plusieurs batteries que vous devrez brancher votre CO REMARQUE La puissance nominale en A h des batteries est habituellement donn...

Страница 30: ...ement relev es Glisser l onduleur chargeur entre les attaches pour engager les fentes de fixation moul es la base du bo tier de l onduleur chargeur Installer et serrer deux attaches de 6 mm po fournie...

Страница 31: ...leur chargeur est un c o n v e r t i s s e u r hautement efficace d lectricit sa puissance nominale de sortie est limit e par la longueur et le calibre des connecteurs CC du c blage reliant la batteri...

Страница 32: ...t le couvercle de la bo te de bornes raccordement fixe Enlever les entr es d fon ables les plus proches de la source lectrique d sir e et de votre quipement Fixer des tubes protecteurs de 1 28 cm de d...

Страница 33: ...e a saut V rifier et remplacer le fusible Le c blage de la batterie est l che V rifier et resserrer ou remplacer le c blage L unit s est teinte cause d une surcharge emp chant des D brancher tous les...

Страница 34: ...Espa ol 12 Fran ais 23 PowerVerter APSX APSINT 12 24 36 230 50 230 50 12 24 36 1111 W 35th Street Chicago IL 60609 USA 773 869 1212 www tripplite com 750 1250 2007 PowerVerter Tripp Lite Tripp Lite A...

Страница 35: ...Tripp Lite 120 Tripp Lite Tripp Lite Tripp Lite RMA Returned Material Authorization Tripp Lite Tripp Lite 10 TRIPP LITE TRIPP LITE Tripp Lite Tripp Lite Tripp Lite 5 UPS Uninterruptible Power Supply...

Страница 36: ...RGE ONLY IEC 320 IEC 320 Tripp Lite APSRM4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 OUTPUT NEUTRAL OUTPUT HOT GROUND INPUT NEUTRAL INPUT HOT FOR USE WITH COPPER WIRE ONLY 1 2 4 3 5 9 10 11 13 8 14 2012 2424 3...

Страница 37: ...ONLY OFF OFF AUTO REMOTE CHARGE ONLY Tripp Lite APSRM4 Tripp Lite LINE AUTO REMOTE CHARGE ONLY INV LOAD 100 OFF AUTO REMOTE CHARGE ONLY BATTERY 91 81 90 61 80 41 60 21 40 1 20 0 OFF AUTO REMOTE CHARGE...

Страница 38: ...A3 A4 INPUT C B 10A OUTPUT C B 12A B4 B3 B2 B1 A4 A3 A2 A1 DIP B DIP A DIP A 201 A4 A3 182 A4 A3 163 A4 A3 144 A4 A3 182 DIP B DIP A1 A2 A3 A4 B2 B1 B B B B APSINT2424 APSINT3636 278 259 APSX750 APSX1...

Страница 39: ...ualize Reset DIP 3 B1 B2 230 B1 B2 33 33 33 B1 B2 66 66 66 B1 B2 B1 B2 B3 B4 B1 B2 B3 B4 B1 B2 B3 B4 B1 B2 B3 B4 B1 B2 B3 B4 750 1250 8 Tripp Lite APSRM4 B1 B2 B3 B4 OFF LESSER LOAD ON MAX GREATER LOA...

Страница 40: ...40A 6 Marine 8D DIP Tripp Lite 1 1 3 1 3 230 300 75 80 2 1 12 24 3 2 1 2 20 55 50 9 30 4 3 Tripp Lite 1000 Tripp Lite Tripp Lite 300 220 20 540 300 140 100 540 540 12 45 45 5 1 2 270 270 30 9...

Страница 41: ...41A Tripp Lite Tripp Lite Tripp Lite 750 1250 6 6 2012 2424 3636 6 6 A B C A B C A C B M A C B M APS M M M M M M 11 4 cm 17 1 cm 20 cm 14 16 cm 38 12 cm M M M M...

Страница 42: ...2A 12 24 36 12 24 36 12 12 12 24 24 12 24 2 12 6 24 4 6 12 Tripp Lite X 12 24 36 UL 45 2 0 5 4 3 2 1 XB XB 4 1 2 3 24B 6B 6B 6B 6B 1 2 2 2 2 4 3 5 2 0 200 3 5 8 AWG American Wire Gage Tripp Lite 45 18...

Страница 43: ...43A 100 IEC 320 IEC 320 1 28 OUTPUT NEUTRAL OUTPUT HOT GROUND INPUT NEUTRAL INPUT HOT FOR USE WITH COPPER WIRE ONLY 5 4 1 3 2 1 2 3 4 5 DoubleBoostTM Tripp Lite 10 OverPowerTM Tripp Lite 1 150...

Страница 44: ...EMOTE CHARGE ONLY CHARGE ONLY AUTO REMOTE OFF 1 AUTO REMOTE CHARGE ONLY Tripp Lite OFF 1 AUTO REMOTE CHARGE ONLY OFF 1 AUTO REMOTE CHARGE ONLY Tripp Lite OFF 1 AUTO REMOTE CHARGE ONLY Tripp Lite LOW 5...

Отзывы: