Service

If you are returning your Inverter/Charger to Tripp Lite, please pack it carefully, using the ORIGINAL PACKING MATERIAL that came
with the unit. Enclose a letter describing the symptoms of the problem. If the Inverter/Charger is within the warranty period, enclose a copy
of your sales receipt. To obtain service you must obtain a Returned Material Authorization (RMA) number from Tripp Lite or an author-
ized Tripp Lite service center. 

Your Inverter/Charger requires no maintenance and contains no user-serviceable or replaceable parts, but should be kept dry at all times.
Periodically check, clean and tighten all cable connections as necessary, both at the unit and at the battery.

Try these remedies for common Inverter/Charger problems before calling for assistance. Call Tripp Lite Customer Service before returning
your unit for service.

Maintenance

Troubleshooting

SYMPTOM

PROBLEMS

CORRECTIONS

No AC Output

Unit is not properly connected to utility power.

Connect unit to utility power.

(All Indicator Lights Are OFF)

Operating Mode Switch is set to “OFF” and 

Set Operating Mode Switch to “AUTO/REMOTE” or “CHARGE ONLY.”

AC input is present.

This is normal when the Operating Mode Switch 

No correction is required. AC output will return when AC input 

is set to “CHARGE ONLY” and AC input is absent.

returns. Set Operating Mode Switch to “AUTO/REMOTE” if you
require AC output.

Circuit breaker is tripped.

Reset circuit breaker.

Unit has shut down due to battery overcharge (preventing

Disconnect any auxiliary chargers. Reset by moving Operating

battery damage). The problem may be with connected

Mode Switch to “OFF.” Wait 1 minute and switch to “AUTO/REMOTE”

auxiliary chargers, if any, or with the unit’s charger.

or “CHARGE ONLY.” If unit remains in shutdown mode after several
attempts to reset, contact Tripp Lite Customer Service for assistance.

Unit has shut down due to excessive battery discharge.

Use an auxiliary charger* to raise battery voltage. Check external 
battery connections and fuse. Unit automatically resets when
condition is cleared.

Unit has shut down due to overload.

Reduce load. Reset by moving Operating Mode Switch to “OFF.”
Wait 1 minute. Switch to “AUTO/REMOTE” or  “CHARGE ONLY.”

Battery Not Recharging

Connected batteries are dead.

Check and replace old batteries.

(AC Input Present)

Battery fuse* is blown.

Check and replace fuse.*

Battery cabling* is loose.

Check and tighten or replace cabling.*

Unit has shut down due to battery overcharge (preventing

Disconnect any auxiliary chargers. Reset by moving Operating Mode

battery damage). The problem may be with connected

Switch to “OFF.” Wait 1 minute and switch to “AUTO/REMOTE” or

auxiliary chargers, if any, or with the unit’s charger.

“CHARGE ONLY.” If unit remains in shutdown mode after several
attempts to reset, contact Tripp Lite Customer Service for assistance.

Input circuit breaker is tripped.

Reset circuit breaker.

All Three Battery Indicator Lights

Battery is excessively discharged.

Use an auxiliary charger* to raise battery voltage. Check external 

Are Slowly Flashing

battery connections and fuse. Unit automatically resets when

(½ Second Flashes)

condition is cleared.

All Three Battery Indicator Lights

Battery is overcharged. Unit will shut down to prevent

Disconnect any auxiliary chargers. Reset by moving Operating Mode

Are Rapidly Flashing

battery damage. The problem may be with connected

Switch to “OFF.” Wait 1 minute and switch to “AUTO/REMOTE”

(¼ Second Flashes)

auxiliary chargers, if any, or with the unit’s charger.

or “CHARGE ONLY.” If unit remains in shutdown mode after several
attempts to reset, contact Tripp Lite Customer Service for assistance.

Red “LOW” Battery

Battery voltage is low. Unit will automatically shut down

Make sure that AC power is present in order to recharge batteries.

Indicator Light is Flashing

after 5 seconds to protect battery from damage.

Reset by moving Operating Mode Switch to “OFF then to
“AUTO/REMOTE” or “CHARGE ONLY.”

False reading due to undersized or insufficiently connected 

Use sufficient size DC cable sufficiently connected to the

DC cabling.

Inverter/Charger.

Red “LOAD” Operation

Inverter is overloaded. Unit will automatically shut down 

Reduce load. Reset by moving Operating Mode Switch to “OFF.”

Indicator Light Flashing

after 5 seconds.

Wait 1minute. Switch to “AUTO/REMOTE” or “CHARGE ONLY.”

* User-supplied.

Battery Indicator Lights

Operating Mode Switch

Operation Indicator Lights

Regulatory Compliance Identification Numbers

For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with
all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The series number should not be confused with the marking name or model
number of the product.

200711152 93-2752 230V APS OM.qxd  11/29/2007  2:15 PM  Page 11

Содержание APINT Series

Страница 1: ...ection Automatic Overload Protection Ideal Output for All Loads including computers Frequency Controlled Output Fast Load Switching Balanced Load Sharing Better for Your Batteries Faster Battery Recha...

Страница 2: ...water might accumulate Mounting should be in the driest location available Leave a minimum of 5 cm clearance at front and back of the Inverter Charger for proper ventilation The heavier the load of co...

Страница 3: ...utility or generator supplied AC power when used with a user supplied cable with country specific plug Hardwire AC Input Output Terminal Strip not on corded models securely connects the Inverter Charg...

Страница 4: ...CHARGE ONLY this light will FLASH to alert you that the unit s inverter is OFF and will NOT supply AC power in the absence of a utility generator source or in over under voltage situations INV Invert...

Страница 5: ...tage Point and or decreasing the Low AC Voltage Point you will reduce the number of times your unit switches to battery due to voltage swings Group B DIP Switches Select Load Sharing OPTIONAL Your Inv...

Страница 6: ...ly from full output at 33 of the Inverter Charger s load rating to about 33 of full output at full load Least Limiting B1 Up B2 Down Charger limiting begins at when the Inverter Charger s load reaches...

Страница 7: ...ur batteries with utility or genera tor supplied AC power Compensate for inefficiency by multiplying this number by 1 2 This will give you a rough estimate of how many amp hours of battery power from...

Страница 8: ...izontal surface leaving the heads slightly raised Slide the Inverter Charger back over the fasteners to engage the mounting slots molded on the bottom of the Inverter Charger cabinet Install and tight...

Страница 9: ...iring Though your Inverter Charger is a high efficiency con verter of electricity its rated output capacity is limited by the length and gauge of the cabling run ning from the battery to the unit Use...

Страница 10: ...te over the hardwire terminal box Remove the knockout covers closest to the desired electrical source and to your equipment Attach 1 28 cm diameter conduits user supplied to the knockouts and thread w...

Страница 11: ...e fuse Battery cabling is loose Check and tighten or replace cabling Unit has shut down due to battery overcharge preventing Disconnect any auxiliary chargers Reset by moving Operating Mode battery da...

Страница 12: ...es integrada Isobar Protecci n autom tica contra sobrecarga Salida ideal para cualquier carga incluyendo computadoras Salida controlada por frecuencia R pida conmutaci n de carga Reparto de carga bala...

Страница 13: ...a de 5 cm en la parte frontal y posterior del inversor cargador para una adecuada ventilaci n A mayor carga del equipo conectado la unidad generar m s calor No instale el inversor cargador directament...

Страница 14: ...CA de la red o suministrada por un generador cuando se emplea con un cable suministrado por el usuario con alg n enchufe de uso local especial Regleta cableada de terminales de entrada salida de corri...

Страница 15: ...e NO suministrar energ a de corriente alterna en ausencia de alimentaci n de la red o de un generador o en casos de sobrevoltaje o bajo voltaje Indicador INV Inversi n amarillo Esta luz se ILUMINAR CO...

Страница 16: ...dad de veces que su unidad cambia a bater a debido a variaciones de voltaje Conmutadores DIP Grupo B Seleccionar reparto de carga OPCIONAL Su inversor cargador presenta un cargador de bater a de alta...

Страница 17: ...alida completa a plena carga M nima limitaci n B1 arriba y B2 abajo La limitaci n del cargador comien za cuando la carga del inversor cargador alcanza el 66 de su capacidad total de carga La salida de...

Страница 18: ...por 1 2 Esto le dar un estimado grueso de cuantos amperios hora de energ a de bater a de una o varias bater as debe conectar a su inversor cargador NOTA La capacidad de amperios hora de una bater a u...

Страница 19: ...el inversor cargador hacia atr s sobre los tornillos para enganchar las ranuras de montaje moldeadas en la parte inferior del gabinete del inversor cargador Instale y apriete dos tornillos de 6 mm sum...

Страница 20: ...iciencia su capacidad de salida est limitada por la longitud y el calibre del cableado desde la bater a hasta la unidad Use la longitud m s corta y el calibre de mayor di metro del cableado m ximo cal...

Страница 21: ...as cubiertas de los agujeros ciegos m s cercanas a la fuente el ctrica deseada y a su equipo Conecte tubos de 1 2 de di metro suministrados por el usuario a los agujeros ciegos y pase los conductores...

Страница 22: ...Revise y reemplace el fusible El cableado de la bater a est flojo Revise y ajuste o reemplace el cableado La unidad se ha apagado debido a sobrecarga de la bater a Desconecte cualquier cargador auxili...

Страница 23: ...ection automatique contre les surcharges Sortie id ale pour toutes les charges y compris les ordinateurs Sortie fr quence contr l e Commutation rapide de la charge Partage quilibr e de la charge Meill...

Страница 24: ...placement le plus sec possible Maintenez un d gagement minimal de 5 cm l avant et l arri re de l onduleur chargeur pour garantir une bonne circulation d air Plus la charge de l quipement branch est lo...

Страница 25: ...cteur ou produit par une g n ratrice l aide d un c ble quip d une fiche sp cifique au pays fourni par l utilisateur Barrette raccordement fixe de bornes d entr e de sortie CA pas sur les mod les cordo...

Страница 26: ...us avertir que l onduleur de l unit est OFF ferm et Ne fournira Pas de courant CA en l absence d une source du secteur ou d une g n ratrice ou dans des situations de basse ou haute tension Voyant jaun...

Страница 27: ...int haut de tension d entr e CA ou en abaissant le point bas de tension d entr e CA vous r duirez le nombre de fois o votre unit passera sur batterie cause de variations de tension Groupe B de commuta...

Страница 28: ...de l onduleur chargeur environ 33 de la sortie pleine pleine charge Limitation minimale No B1 en haut ET No B2 en bas La limitation du chargeur commence lorsque la charge de l ond uleur chargeur atte...

Страница 29: ...ne estimation grossi re de la puissance de batterie en A h d une ou de plusieurs batteries que vous devrez brancher votre CO REMARQUE La puissance nominale en A h des batteries est habituellement donn...

Страница 30: ...ement relev es Glisser l onduleur chargeur entre les attaches pour engager les fentes de fixation moul es la base du bo tier de l onduleur chargeur Installer et serrer deux attaches de 6 mm po fournie...

Страница 31: ...leur chargeur est un c o n v e r t i s s e u r hautement efficace d lectricit sa puissance nominale de sortie est limit e par la longueur et le calibre des connecteurs CC du c blage reliant la batteri...

Страница 32: ...t le couvercle de la bo te de bornes raccordement fixe Enlever les entr es d fon ables les plus proches de la source lectrique d sir e et de votre quipement Fixer des tubes protecteurs de 1 28 cm de d...

Страница 33: ...e a saut V rifier et remplacer le fusible Le c blage de la batterie est l che V rifier et resserrer ou remplacer le c blage L unit s est teinte cause d une surcharge emp chant des D brancher tous les...

Страница 34: ...Espa ol 12 Fran ais 23 PowerVerter APSX APSINT 12 24 36 230 50 230 50 12 24 36 1111 W 35th Street Chicago IL 60609 USA 773 869 1212 www tripplite com 750 1250 2007 PowerVerter Tripp Lite Tripp Lite A...

Страница 35: ...Tripp Lite 120 Tripp Lite Tripp Lite Tripp Lite RMA Returned Material Authorization Tripp Lite Tripp Lite 10 TRIPP LITE TRIPP LITE Tripp Lite Tripp Lite Tripp Lite 5 UPS Uninterruptible Power Supply...

Страница 36: ...RGE ONLY IEC 320 IEC 320 Tripp Lite APSRM4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 OUTPUT NEUTRAL OUTPUT HOT GROUND INPUT NEUTRAL INPUT HOT FOR USE WITH COPPER WIRE ONLY 1 2 4 3 5 9 10 11 13 8 14 2012 2424 3...

Страница 37: ...ONLY OFF OFF AUTO REMOTE CHARGE ONLY Tripp Lite APSRM4 Tripp Lite LINE AUTO REMOTE CHARGE ONLY INV LOAD 100 OFF AUTO REMOTE CHARGE ONLY BATTERY 91 81 90 61 80 41 60 21 40 1 20 0 OFF AUTO REMOTE CHARGE...

Страница 38: ...A3 A4 INPUT C B 10A OUTPUT C B 12A B4 B3 B2 B1 A4 A3 A2 A1 DIP B DIP A DIP A 201 A4 A3 182 A4 A3 163 A4 A3 144 A4 A3 182 DIP B DIP A1 A2 A3 A4 B2 B1 B B B B APSINT2424 APSINT3636 278 259 APSX750 APSX1...

Страница 39: ...ualize Reset DIP 3 B1 B2 230 B1 B2 33 33 33 B1 B2 66 66 66 B1 B2 B1 B2 B3 B4 B1 B2 B3 B4 B1 B2 B3 B4 B1 B2 B3 B4 B1 B2 B3 B4 750 1250 8 Tripp Lite APSRM4 B1 B2 B3 B4 OFF LESSER LOAD ON MAX GREATER LOA...

Страница 40: ...40A 6 Marine 8D DIP Tripp Lite 1 1 3 1 3 230 300 75 80 2 1 12 24 3 2 1 2 20 55 50 9 30 4 3 Tripp Lite 1000 Tripp Lite Tripp Lite 300 220 20 540 300 140 100 540 540 12 45 45 5 1 2 270 270 30 9...

Страница 41: ...41A Tripp Lite Tripp Lite Tripp Lite 750 1250 6 6 2012 2424 3636 6 6 A B C A B C A C B M A C B M APS M M M M M M 11 4 cm 17 1 cm 20 cm 14 16 cm 38 12 cm M M M M...

Страница 42: ...2A 12 24 36 12 24 36 12 12 12 24 24 12 24 2 12 6 24 4 6 12 Tripp Lite X 12 24 36 UL 45 2 0 5 4 3 2 1 XB XB 4 1 2 3 24B 6B 6B 6B 6B 1 2 2 2 2 4 3 5 2 0 200 3 5 8 AWG American Wire Gage Tripp Lite 45 18...

Страница 43: ...43A 100 IEC 320 IEC 320 1 28 OUTPUT NEUTRAL OUTPUT HOT GROUND INPUT NEUTRAL INPUT HOT FOR USE WITH COPPER WIRE ONLY 5 4 1 3 2 1 2 3 4 5 DoubleBoostTM Tripp Lite 10 OverPowerTM Tripp Lite 1 150...

Страница 44: ...EMOTE CHARGE ONLY CHARGE ONLY AUTO REMOTE OFF 1 AUTO REMOTE CHARGE ONLY Tripp Lite OFF 1 AUTO REMOTE CHARGE ONLY OFF 1 AUTO REMOTE CHARGE ONLY Tripp Lite OFF 1 AUTO REMOTE CHARGE ONLY Tripp Lite LOW 5...

Отзывы: