www.tridonic.com
13
Subject to change without notice. Information provided without guarantee.
Data sheet 11/20-EM110-1
Emergency lighting units
EM converterLED
8. Battery data
8.1 Battery selection
8.2 Battery charge / discharge data
EM converterLED PRO, 1 / 2 / 3 h
Type
EM converterLED PRO
302 MH/LiFePO4 50V
EM converterLED PRO
303 MH/LiFePO4 50V
EM converterLED PRO
304 MH/LiFePO4 50V
Article no.
89800640
89800641
89800642
Duration
1 h
2/3 h
1 h
2/3 h
1 h
2/3 h
Technology and
capacity
Design
Number
of cells
Type
Article no.
Assignable batteries
NiMH 4.0 Ah
LA cells
stick
1 x 2
Accu-NiMH 2A CON
28002316
•
stick
1 x 3
Accu-NiMH 3A CON
89800441
•
stick
1 x 4
Accu-NiMH 4A CON
89800442
•
stick + stick
2 + 2
Accu-NiMH 4C CON
89800438
•
remote box
1 x 3
Pack-NiMH 4Ah 3 CON 28001896
•
remote box
1 x 4
Pack-NiMH 4Ah 4 CON 28001897
•
LiFePO
4
1.5 Ah
18650 cells
stick
1 x 1
Accu-LiFePO4
1A CON
28002317
•
stick
1 x 2
Accu-LiFePO4
2A CON
28002318
•
•
•
stick
1 x 4
Accu-LiFePO4
4A CON 28002322
•
stick
1 x 5
Accu-LiFePO4
5A CON
28002325
•
stick + stick
2 + 2
Accu-LiFePO4
4C CON
28002324
•
stick + stick
3 + 2
Accu-LiFePO4
5C CON
28002327
•
side by side
2 x 1
Accu-LiFePO4
2B CON
28002319
•
•
•
side by side
4 x 1
Accu-LiFePO4
4B CON
28002323
•
side by side
5 x 1
Accu-LiFePO4
5B CON
28002326
•
EM converterLED PRO, 1 / 2 / 3 h, NiMH
Type
EM converterLED PRO
302 MH/LiFePO4 50V
EM converterLED PRO
303 MH/LiFePO4 50V
EM converterLED PRO
304 MH/LiFePO4 50V
Article no.
89800640
89800641
89800629
Duration
1 h
2/3 h
1 h
2/3 h
1 h
2/3 h
Battery charge
time
Initial charge
20 h
Fast recharge
10 h
15 h
10 h
15 h
10 h
15 h
Trickle charge
continuously
Charging current
Initial charge
110 – 150 mA
280 – 320 mA
110 – 150 mA
280 – 320 mA
110 – 150 mA
280 – 320 mA
Fast recharge
190 – 230 mA
310 – 350 mA
190 – 230 mA
310 – 350 mA
190 – 230 mA
310 – 350 mA
Trickle charge
110 – 150 mA / 4 min.
0 mA / 16 min.
180 – 220 mA / 4 min.
0 mA / 16 min.
110 – 150 mA / 4 min.
0 mA / 16 min.
180 – 220 mA / 4 min.
0 mA / 16 min.
110 – 150 mA / 4 min.
0 mA / 16 min.
180 – 220 mA / 4 min.
0 mA / 16 min.
Discharge current
730 – 790 mA
730 – 790 mA
770 – 830 mA
770 – 830 mA
790 – 850 mA
790 – 850 mA
Charge voltage range
1
0.9 – 1.65 V per cell
Discharge voltage range
1.65 – 1.05 V per cell
1
The battery will be charged below 0.9 V. The EM converterLED will indicate a battery fault.
The emergency lighting LED Driver will recharge the battery normally after running the test of 61347-2-7 CL 22.3 (abnormal operating conditions).