Tridium Vykon NPB-2X-485 Скачать руководство пользователя страница 1

3951 Westerre Parkway, Suite 350
Richmond, Virginia 23233 USA

NPB-2X-485 Option

INSTALLATION SHEET

 

NPB-2X-485 Option Installation Sheet

Part Number 10621 Rev 2

Updated: May 28, 2009

 

1

Information and specifications published here are current as of the date of publication of this document. Tridium, Inc. reserves the right to change or modify 
specifications without prior notice. The latest product specifications can be found by contacting our corporate headquarters, Richmond, Virginia. Products or 
features contained herein may be covered by one or more U.S. or foreign patents. © 2009 Tridium, Inc.

This

 

document

 

covers

 

the

 

mounting

 

and

 

wiring

 

of

 

the

 

NPB

2X

485

 

option

 

card

 

in

 

a

 

Vykon

®

 

JACE

 

controller

 

(JACE

200/600,

 

SEC

J

x

01,

 

or

 

J

202

XPR

 

series).

Refer

 

to

 

the

 

appropriate

 

JACE

®

 

mounting

 

and

 

wiring

 

document

 

for

 

further

 

JACE

 

installation

 

details.

Included in this Package

Included

 

in

 

this

 

package

 

you

 

should

 

find

 

the

 

following

 

items:

NPB

2X

485

 

option

 

card,

 

connector

 

end

 

plate.

two

 

3

position

 

terminal

 

plugs,

 

for

 

wiring

 

to

 

an

 

RS

485

 

network

This

 

NPB

2X

485

 

Option

 

Installation

 

Sheet

,

 

Part

 

Number

 

10621

 

Rev

 

2.

Material and Tools Required

The

 

following

 

tools

 

and

 

supplies

 

may

 

be

 

required

 

for

 

installation:

#2

 

phillips

 

screwdriver:

 

used

 

to

 

install

 

the

 

NPB

2X

485.

Small

 

flat

blade

 

screwdriver:

 

used

 

for

 

making

 

wiring

 

connections

 

to

 

the

 

RS

485

 

networks.

#1

 

phillips

 

screwdriver:

 

to

 

remove

 

and

 

refasten

 

J

202

XPR

 

covers

 

(if

 

applicable).

Figure 1

NPB-2X-485 option.

Mounting

Warning

Power

 

to

 

the

 

JACE

 

must

 

be

 

OFF

 

when

 

installing

 

or

 

removing

 

option

 

cards,

 

or

 

damage

 

will

 

occur!

 

Also,

 

you

 

must

 

be

 

very

 

careful

 

to

 

plug

 

any

 

option

 

card

 

into

 

its

 

connector

 

properly

 

(pins

 

aligned).

Mount

 

the

 

NPB

2X

485

 

option

 

card

 

in

 

either

 

of

 

the

 

option

 

card

 

slots

 

of

 

the

 

JACE,

 

as

 

needed.

 

Note

 

the

 

J

202

XPR

 

series

 

has

 

only

 

one

 

option

 

card

 

slot.

Note

If

 

installing

 

in

 

a

 

Security

 

JACE

 

(SEC

J

x

01),

 

install

 

in

 

Option

 

Card

 

Slot

 

2

.

See

 

the

 

notes

 

in

 

Table 1

 

on

 

software

 

COM

 

port

 

assignments

 

for

 

installed

 

NPB

2X

485

 

option

 

cards.

Procedure 1

Mounting NPB-2X-485 option card on a JACE.

1.

Remove power

 

from

 

the

 

JACE—see

 

the

 

previous

 

Warning

.

 

Wait

 

for

 

all

 

LEDs

 

on

 

the

 

unit

 

to

 

be

 

Off.

2.

Remove

 

the

 

JACE

 

cover

 

or

 

covers

 

(J

202

XPR).

For

 

all

 

but

 

the

 

J

202

XPR,

 

press

 

in

 

the

 

four

 

tabs

 

on

 

both

 

ends

 

of

 

the

 

unit,

 

and

 

lift

 

the

 

cover

 

off.

Note

If

 

accessory

 

modules

 

are

 

plugged

 

into

 

the

 

JACE,

 

you

 

may

 

need

 

to

 

slide

 

them

 

away

 

from

 

the

 

unit

 

to

 

get

 

to

 

the

 

cover

 

tabs.

Table 1 NPB-2X-485 option description.

Description

Notes / COM Port Assignments

Dual port, 
optically isolated 
RS-485 adapter, 
with two 
3-position, 
removable 
screw-terminal 
connector plugs.

See 

Figure 2

 on 

page 2 for 
location of Option 
Slots 1 and 2 on a 
JACE-200/600.

The J-202-XPR series controller accepts 
only one (1) option card, where ports for 
the NPB-2X-485 are COM7 and COM8.

For other JACE models (JACE-200/600, 
SEC-J-

x

01) up to 2 RS-485 option cards 

may be installed, where:

If 

single

 RS-485 option in Option Slot 1, 

ports are COM3, COM4.

If 

two

 RS-485 options, ports are 

COM3, COM4 for Option Slot 1, 
and COM5, COM6 for Option Slot 2.

If 

single

 RS-485 option in Option Slot 2, 

ports are COM3, COM4, 

unless

 one of 

the following are in Option Slot 1:
• NPB-232: ports are COM4, COM5.
• NPB-GPRS: ports are COM5, COM6.

S

R

5

8

4

s

X

R

X

T

X

R

X

T

s

COM3 / COM5

COM7

COM4 / COM6

COM8

See Notes in 

Table 1

.