PCVT-48VDC-53VDC Install Guide

 

33568 Rev. A 

www.transition.com/ 

Page 3 of 18 

Safety 

Before installing the PCVT, read this section and ensure that the requirements noted are met.  

Cautions and Warnings 

Definitions 

Cautions

 indicate that there is the possibility of poor equipment performance or potential damage to the 

equipment. 

Warnings

 indicate that there is the possibility of injury to a person.  

Cautions and Warnings appear here and may appear throughout this manual where appropriate. Failure to 
read and understand the information identified by this symbol could result in poor equipment 
performance, damage to the equipment, or injury to persons.  

Cautions 

 

  Do not

 ship or store devices near strong electrostatic, electromagnetic, magnetic, or radioactive fields.  

 

Caution

: When handling chassis Network Devices observe electrostatic discharge precautions. This requires proper 

grounding (i.e., wear a wrist strap). 

 

Caution

: Copper based media ports, e.g., Twisted Pair (TP) Ethernet, USB, RS232, RS422, RS485, DS1, DS3, 

Video Coax, etc., are intended to be connected to intra-building

 (inside plant)

 link segments that are not subject to 

lightening transients or power faults. They are 

not

 to be connected to inter-building 

(outside plant)

 link segments 

that are subject to lightening. 

 

Caution

Do not

 install the devices in areas where strong electromagnetic fields (EMF) exist. Failure to observe this 

caution could result in poor device performance.  

 

Caution

: Read the installation instructions before connecting the chassis to a power source. Failure to observe this 

caution could result in poor performance or damage to the equipment. 

 

Caution

: Only trained and qualified personnel should install or perform maintenance on the 

PCVT-48VDC-

53VDC

. Failure to observe this caution could result in poor performance or damage to the equipment. 

 

CAUTION

 – “Risk of Electric Shock – More than one disconnect switch may be required to de-energize 

the equipment.

 

 

Содержание PCVT-48VDC-53VDC

Страница 1: ...E Mark 5 FCC Regulations 5 Canadian Regulations 5 European Regulations 5 Electrical Safety Warnings 7 Unpacking 8 Ship Kit Contents 8 Mounting 9 Installation 10 Front Panel 10 Connect POWER INPUT 1 10 Connect POWER INPUT 2 10 Connect the POWER OUTPUT 10 Optional Terminal Block Euro Block Connection 11 Terminal Block Power Source 11 Grounding the PCVT 48VDC 53VDC 12 Grounding Procedure 13 Operation...

Страница 2: ...rew terminal power connections Operating temperature 40 o C to 70 o C UL60950 CE Mark IEC60068 2 31 IEC60068 2 27 IEC60068 2 6 FCC and TAA compliance Fixed configuration no DIP switches or jumpers Laying a PCVT unit upright on a floor or desktop blocks the bottom vents convection cooling issue DIN rail mount only Model Numbers Model Description PCVT 48VDC 53VDC Power Converter WMBD DIN Rail Mount ...

Страница 3: ...autions This requires proper grounding i e wear a wrist strap Caution Copper based media ports e g Twisted Pair TP Ethernet USB RS232 RS422 RS485 DS1 DS3 Video Coax etc are intended to be connected to intra building inside plant link segments that are not subject to lightening transients or power faults They are not to be connected to inter building outside plant link segments that are subject to ...

Страница 4: ...l to the equipment See Electrical Safety Warnings on page 7 for Electrical Safety Warnings translated into multiple languages Restricted Access Note WARNING Disconnect power before installing and wiring the PCVT 48VDC 53VDC for power Failure to observe this warning could result in an electrical shock Wiring considerations The following wiring considerations are recommended Use separate paths to ro...

Страница 5: ...e the user will be required to correct the interference at the user s own expense Canadian Regulations This digital apparatus does not exceed the Class A limits for radio noise for digital apparatus set out on the radio interference regulations of the Canadian Department of Communications Le présent appareil numérique n émet pas de bruits radioélectriques dépassant les limites applicables aux appa...

Страница 6: ...quipment communications equipment office appliances and multi media equipment for use in the home office business school computer room and similar locations IEC 60950 1 is developed maintained by IEC Technical Committee TC 108 Maintenance Team No 2 MT2 Safety and Energy Efficiency of Information Technology Equipment In China the ITE Standard formally designated GB 4943 1 2011 is based on the Secon...

Страница 7: ...chriften worden geïnstalleerd Sécurité électrique IMPORTANT Cet équipement doit être utilisé conformément aux instructions de sécurité Sähköturvallisuus TÄRKEÄÄ Tämä laite on asennettava turvaohjeiden mukaisesti Sicurezza elettrica IMPORTANTE questa apparecchiatura deve essere installata rispettando le norme di sicurezza Elektrisk sikkerhet VIKTIG Dette utstyret skal nstallers I samsvar med sikker...

Страница 8: ...ntents below 3 Place the PCVT and related materials in the desired install location Figure 2 PCVT 48VDC 53VDC Unpacking 4 Save the PCVT 10x9x4 Box and Insert for future use Ship Kit Contents The PCVT 48VDC 53VDC is shipped with several standard items Make sure you have received the following One PCVT 48VDC 53VDC Power Converter One DIN Rail Mount Bracket Kit One printed Product Documentation postc...

Страница 9: ...Install Guide 33568 Rev A www transition com Page 9 of 18 Mounting The PCVT must be mounted vertically using a DIN Rail mounting bracket Typically the Terminal Blocks will be facing upward as shown in the views below Figure 3 DIN Rail Mounting ...

Страница 10: ... connector see figure below See Power In Status LEDs on page 14 2 Connect the other end of the wires to the first power source ensuring correct polarity Connect POWER INPUT 2 1 Connect the wires to the V2 and V2 connections of the POWER INPUT 2 terminal block connector see figure below See Power In Status LEDs on page 14 2 Connect the other end of the wires to the second power source ensuring corr...

Страница 11: ...proper length 2 Insert the positive and negative power wires into V1 and V1 contacts respectively of the terminal block note polarity on the chassis Make sure the wires are secure See Figure 4 on the previous page 3 Insert the positive and negative power wires into V2 and V2 contacts respectively into the power source make sure the wires are secure See Figure 4 on the previous page 4 Insert the po...

Страница 12: ... conducting path from the PCVT 48VDC 53VDC must Flow via the grounding lugs to the common bonding network CBN for telecom installations or to an alternative approved grounding system if required for non telecom installations Be of sufficiently low impedance to conduct fault currents likely to be imposed on the PCVT 48VDC 53VDC and Enable proper operation of any over current protection devices The ...

Страница 13: ...ctor 2 Attach the grounding conductor to the PCVT 48VDC 53VDC by placing the two hole connector onto the grounding lugs and fasten with the enclosed lock washers lug nuts at the proper torque per the manufacturer s specification at the vendor web page 4 5 inch pounds typical or recommended 3 Attach the opposite end of the grounding conductor to the common bonding network CBN for telecom or to eart...

Страница 14: ...nstall Guide 33568 Rev A www transition com Page 14 of 18 Operation Power In Status LEDs Use the LEDs to monitor PCVT Power Input status POWER 1 LED Lit Connected to POWER INPUT 1 POWER 2 LED Lit Connected to POWER INPUT 2 Figure 8 Front Panel ...

Страница 15: ...ting Humidity 10 to 90 non condensing Altitude 500 to 10 000 H Output Output Voltage 53 VDC Current Rating 4 9A Power Rating 260 Watts Ripple Noise Max 200mV Maximum Voltage Tolerance 0 6 Line Regulation 0 6 Load Regulation 0 6 Setup Rise Time 100 mSec Hold Up Time 100 µSec Input Voltage Range 38 70 VDC Efficiency 80 MAX Current Typical 7 5A 48 VDC Inrush Current Cold 10A 48 VDC Protection against...

Страница 16: ...Transition Networks Inc PCVT 48VDC 53VDC Install Guide 33568 Rev A www transition com Page 16 of 18 Dimensions Figure 9 Dimensions ...

Страница 17: ...nternational 00 1 952 941 7600 See the Maintainance section on page 18 YES Proceed to step 2 below 2 Is the PCVT POWER 2 LED lit NO Is there a power connector plugged into the POWER 2 terminal block Is the VDC power source operating correctly Is there voltage in the range of 38 70 VDC present at the terminal block connector on the PCVT YES Check if the fuse is OK NO The fuse is not field replaceab...

Страница 18: ...nto Hwww transition comH and click the Learning Center link E Mail Ask a question anytime by sending an e mail to our technical support staff Htechsupport transition comH Address Transition Networks 10900 Red Circle Drive Minnetonka MN 55343 U S A telephone 952 941 7600 toll free 800 526 9267 fax 952 941 2322 Record of Revisions Rev Date Notes A 02 05 14 Initial release Trademark Notice All tradem...

Отзывы: