Installation
RT-SVX38B-EN
17
Foundation
Horizontal Units
If the unit is installed at ground level, elevate it above the
snow line. Provide concrete footings at each support
location with a “full perimeter” support structure or a slab
foundation for support. Refer to
Table 1, p. 17
for the unit’s
operating and point loading weights when constructing a
footing foundation.
If anchoring is required, anchor the unit to the slab using
hold down bolts or isolators. Isolators should be installed
to minimize the transmission of vibrations into the
building.
Table 1.
Maximum unit & corner weights (lbs/kgs) and center of gravity dimensions (in/mm) - gas/electric models
Unit
Maximum Model
Weights
(a)
Corner Weights
(b)
Center of Gravity (in./
mm)
Tons
Model No.
Shipping
Net
A
B
C
D
Length
Width
5
YSC060E
689/312 584/264
181/82
144/65
122/55
137/62
40/1025
24/600
6
YSC072E
975/443
843/383
296/134
209/95
158/72
180/82
39/980
21/542
7½
YSC090E
1016/461 884/401
346/157
198/90
159/72
181/82
36/909
20/519
8½
YSC102E
1125/510 987/447
325/147
278/126
174/79
210/95
41/1031
21/526
10
YSC120E
1149/522
1011/459
344/156
265/120
193/88
209/95
40/1020
21/538
(a) Weights are approximate.
(b) Corner weights are given for information only.
Figure 12.
Rigging and center of gravity
Table 2.
Factory installed options (fiops)/accessory net weights (lbs)
(a),(b)
YSC060ED
YSC072E-120ED
Net Weight
Net Weight
Accessory
5 Ton
6-10 Ton
Barometric Relief
7/3
10/5
Coil Guards
12/5
20/9
Economizer
26/12
36/16
Hinged Doors
10/5
12/5
Manual Outside Air Damper
16/7
26/12
Motorized Outside Air Damper
20/9
30/14
Oversized Motor
–
8/4
Roof Curb
61/28
78/35
(a) Weights for options not listed are <5 lbs.
(b) Net weight should be added to unit weight when ordering factory-installed accessories.