75
COMPONENT
FAILURE RESPONSE
NORMAL RANGE
DIAGNOSTIC
(CFS) Clogged Filter
This input is for "indication"
Normal operation =
SERVICE LED ON
Switch
only and does not effect
0 VAC measured
2-30 VDC present at
the normal operation
between terminals
RTRM J6-6 and J6-10
of the unit.
J5-1 and Ground.
(FFS)
Unit will not operate in
0.5" W.C.
Service Failure Output
Supply Fan Proving
any mode.
Normally Open
at RTRM J6-6 to J6-10
Switch
"SERVICE" LED blinks
at ZSM
(SPT)
IGV will not open
0.25 - 4 VDC
Heat and Cool Failure
Static Pressure
between J8 and J9
Output at RTRM J6-7 to J6-6
Transducer VAV
on VAV
& RTRM J6-8 to J6-6
"HEAT" and "COOL" LED's
blink at ZSM
*NONE* = No LED indication
WARNING
Hazardous Voltage! w/Capacitors!
Disconnect all electric power, including remote discon-
nects before servicing. Follow proper lockout/tagout pro-
cedures to ensure the power cannot be inadvertently en-
ergized. For variable frequency drives or other energy
storing components provided by Trane or others, refer to
the appropriate manufacturer’s literature for allowable
waiting periods for discharge of capacitors. Verify with an
appropriate voltmeter that all capacitors have dis-
charged. Failure to disconnect power and discharge ca-
pacitors before servicing could result in death or serious
injury.
Note: For additional information regarding the safe dis-
charge of capacitors, see
PROD-SVB06A-EN
HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK 1TB1
OR UNIT DISCONNECT SWITCH 1S14.
2. To modify parameters:
(a) Press the Extended Menu button
(b) Press the Left or Right Arrow button to scroll
through menus
(c) Press the up or down arrow to scroll through
parameter settings within a specified menu
(d) Press the Change Data button to allow a parameter
VFD Programming Parameters
Units shipped with an optional variable frequency drive
(VFD) are preset and run tested at the factory. If a problem
with a VFD occurs, ensure that the programmed parameters
listed in Table 25 have been set before replacing the drive.
Note: Check to make sure that parameter 104 is set
to 60 Hz. To check parameter 104 press the
Extended Menu button, press the Left Arrow button
until menu Load & Motor is shown, press the up
arrow until parameter 104 is displayed. Parameter
104 can then be modified by pressing the Change
Data button and then the Up Arrow button. When
the desired selection has been made press the OK
button.
Should replacing the a VFD become necessary, the re-
placement is not configured with all of Trane's operating pa-
rameters. The VFD must be programmed before attempting
to operate the unit.
To verify and/or program a VFD, use the following steps:
1. Remove the mode input (RTRM J6-2 and J6-4) or turn
the NSB panel to OFF so that the fan will not attempt to
start during programming.
Table 29
Supply and Exhaust Fan VFD Programming Parameters
Menu
Parameter Description
Setting
Description
102
Motor Power
Set Based on Motor Nameplate
Set only for applications using 3hp Hi-
Efficiency motors. Set to 2.2 kW.
103
Motor Voltage Set Based on Motor Nameplate
Set only for 200/230v 60hz & 380/415
50hz applications
105
Motor Current Set Based on Motor Nameplate
Sets the motor FLA
106
Motor RPM
Set Based on Motor Nameplate
Sets the motor RPM
Reference
&
Limits
215
Current Limit
1 x Rated Current
Limits the maximum current to motor
Load
&
Motor
Component Failure Mode (Continued)/VFD Programming Parameters
Содержание Voyager RT-SVX17C-EN
Страница 8: ...8 Figure 1 Unit Dimensions for TC_ TE_ and YC_330 360 and 420 MBH Units Low Heat ...
Страница 9: ...9 Figure 1 continued Unit Dimensions for YC_330 360 and 420 MBH Units High Heat ...
Страница 10: ...10 Figure 1 continued Unit Dimensions for TC_ TE_ and YC_480 and 600 MBH Units Low High Heat ...
Страница 24: ...24 Figure 10 Typical FieldWiring Requirements for CV Control Options ...
Страница 78: ......
Страница 79: ......
Страница 80: ......