Remote Panels and Sensors (Continued)
Degrees F°
Nominal Resistance
-20°
170.1 K - Ohms
-15°
143.5 K - Ohms
-10°
121.4 K - Ohms
-5°
103.0 K - Ohms
0°
87.56 K - Ohms
5°
74.65 K - Ohms
10°
63.80 K - Ohms
15°
54.66 K - Ohms
20°
46.94 K - Ohms
25°
40.40 K - Ohms
30°
34.85 K - Ohms
35°
30.18 K - Ohms
40°
26.22 K - Ohms
45°
22.85 K - Ohms
50°
19.96 K - Ohms
55°
17.47 K - Ohms
60°
15.33 K - Ohms
65°
13.49 K - Ohms
70°
11.89 K - Ohms
75°
10.50 K - Ohms
80°
9.297 K - Ohms
85°
8.247 K - Ohms
90°
7.330 K - Ohms
95°
6.528 K - Ohms
100°
5.824 K - Ohms
Remote Minimum Position Potentiometer
(BAYSTAT023A)
This device can be used with units with an economizer. It al-
lows the operator to remotely set the position of the econo-
mizer dampers from 0% to 50% of fresh air entering the
space.
Table 10
Temperature versus Resistance
(temperature vs resistance coefficient is negative)
Space Temperature Averaging
Space temperature averaging is accomplished by wiring a
number of remote sensors in a series/parallel circuit.
The fewest number of sensors required to accomplish space
temperature averaging is four. Example #1 illustrates two series
circuits with two sensors in each circuit wired in parallel.
Any number squared, is the number of remote sensors re-
quired. Example #2 illustrates three sensors squared in a
series/parallel circuit. NSB panel remote sensors must use
twisted/shielded cable.
To RTRM J6-1 and J6-2
or to ZSM terminals 1 and 2
or NSB panel terminals S1
and S2. Shield to terminal 11.
Содержание Voyager RT-SVX17C-EN
Страница 8: ...8 Figure 1 Unit Dimensions for TC_ TE_ and YC_330 360 and 420 MBH Units Low Heat ...
Страница 9: ...9 Figure 1 continued Unit Dimensions for YC_330 360 and 420 MBH Units High Heat ...
Страница 10: ...10 Figure 1 continued Unit Dimensions for TC_ TE_ and YC_480 and 600 MBH Units Low High Heat ...
Страница 24: ...24 Figure 10 Typical FieldWiring Requirements for CV Control Options ...
Страница 78: ......
Страница 79: ......
Страница 80: ......