26
SINGLE SETPOINT MANUAL CHANGE OVER
FAN AUTO - FAN ON
HEAT - OFF - COOL
Remote Panel W/O NSB (BAYSENS010B)
This electronic sensor features four system switch settings
(Heat, Cool, Auto, and Off) and two fan settings (On and
Auto) with four system status LED's. It is a manual or auto
changeover control with dual setpoint capability. It can be
used with a remote zone temperature sensor
BAYSENS017B.
Remote Panel with NSB (BAYSENS019*)
This 7 day programmable sensor features four periods for
Occupied\Unoccupied programming per day. A liquid crystal
display (LCD) displays zone temperature, temperature
setpoints, week day, time, and operational mode symbols. If
the power is interrupted, the program is retained in perma-
nent memory. If power is off longer than 2 hours, only the
clock and day may have to be reset.
The front panel allows selection of four system modes
(Heat, Cool, Auto, and Off), two fan modes (On and Auto),
six programming buttons, and dual temperature selection
and start time.
The "Occupied" cooling setpoint ranges between 45
o
and
98
o
Fahrenheit. The "Unoccupied" cooling setpoint ranges
between 45 and 98 degrees Fahrenheit. The heating set-
point ranges between 43 and 96 degrees Fahrenheit.
The options menu is used to enable or disable applicable
functions, i.e, Morning warm-up, economizer minimum posi-
tion override during unoccupied status, Fahrenheit or centi-
grade, supply air tempering, remote zone temperature sen-
sor, 12/24 hour time display, smart fan, and computed re-
covery.
During an occupied period, an auxiliary relay rated for 1.25
amps @ 30 volts AC with one set of single pole double
throw contacts is activated. See Table 10 for the Temp vs
Resistance coefficient, if the optional remote sensor is used.
Remote Panels and Sensors
RTRM
Constant Volume Control Options continued
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote discon-
nects before servicing. Follow proper lockout/tagout pro-
cedures to ensure the power can not be inadvertently en-
ergized. Failure to disconnect power before servicing
could result in death or serious injury.
Zone Panel (BAYSENS006B)
This electronic sensor features three system switch settings
(Heat, Cool, and Off) and two fan settings (On and Auto). It is
a manual changeover control with single setpoint capability.
Zone Panel (BAYSENS008B)
This electronic sensor features four system switch settings
(Heat, Cool, Auto, and Off) and two fan settings (On and
Auto). It is a manual or auto changeover control with dual
setpoint capability. It can be used with a remote zone tem-
perature sensor BAYSENS017B.
Содержание Voyager RT-SVX17C-EN
Страница 8: ...8 Figure 1 Unit Dimensions for TC_ TE_ and YC_330 360 and 420 MBH Units Low Heat ...
Страница 9: ...9 Figure 1 continued Unit Dimensions for YC_330 360 and 420 MBH Units High Heat ...
Страница 10: ...10 Figure 1 continued Unit Dimensions for TC_ TE_ and YC_480 and 600 MBH Units Low High Heat ...
Страница 24: ...24 Figure 10 Typical FieldWiring Requirements for CV Control Options ...
Страница 78: ......
Страница 79: ......
Страница 80: ......