Ventilation Override Mode - If a VOM goes active in
which the Supply Fan is commanded ON (Purge,
Pressurize, etc.) the Supply Fan will be energized
and the Fan Speed output will ramp to 100%.
•
Zone Temperature Sensor Failure - If the Active
Zone Temperature input goes out of range, the unit
will discontinue all Heating, Cooling, and Hot Gas
Reheat operation.
•
Supply Air Temperature Sensor Failure - If the
Supply Air Temperature input goes out of range,
the unit will revert back to Full Airflow, Traditional
CV control. The unit will call out a Supply Air
Temperature Sensor Failure Alarm, the RTRM
System LED will flash the 2-blink error code, and
the Zone Sensor Heat (Modulating Heat Only) and
Cool LEDs will flash.
•
Frostat Failure - If the unit has a Froststat Failure
occur, all active Heating, Cooling, and Hot Gas
Reheat will be de-energized immediately and the
Supply Fan will ramp up to 100%.
•
Heat Failure (High Temp. Limit Trip) - If a unit
configured with Gas Heat has a High Temp. Limit
trip the Supply Fan will be requested to remain ON
and the Fan Speed output will ramp to full speed.
Low Pressure Control (LPC)
Sequence of Operation (ReliaTel
Control)
When the LPC is opened for one (1) continuous second,
the compressor for that circuit is turned off
immediately. The compressor will not be allowed to
restart for a minimum of three (3) minutes.
If four consecutive open conditions occur during the
first three minutes of operation, the compressor will be
locked out, a diagnostic communicated to ICSTM if
applicable, and a manual reset will be required to
restart the compressor.
High Pressure Control and
Temperature Discharge Limit
(ReliaTel Control)
The Temperature Discharge Limit (TDL) is located in
the Compressor Output circuit and is connected in
series with the High Pressure Control (HPC). The RTRM
will register an auto reset lockout if either the high
pressure control switch or the temperature discharge
limit opens during compressor operation. If the
compressor output circuit is opened four consecutive
times during compressor operation, the RTRM will
generate a manual reset lockout.