Electrical Data
UNT-PRC001-EN
71
Table B-ED-2. Three and Four-Row Coils — Free Discharge Motors
115 Volt
208 Volt RPM
FC
FLA
HP (kW)
FLA
HP (kW)
H
M
L
04
1.0
.06
0.6
.06
108
800
600
(.04)
(.04)
06
1.4
.12
0.9
.12
108
800
600
(.09)
(.09)
08
1.7
.13
1.0
.13
108
800
600
(.10)
(.10)
Table B-ED-3. Three and Four-Row Coils — High Static Motors
115 Volt
208 Volt RPM
FC
FLA
HP (kW)
FLA
HP (kW)
H
M
L
04
2.1
.13
0.9
.13
1580
1375
1240
(.10)
(.10)
06
3.4
.24
1.4
.24
1475
1285
975
(.18)
(.18)
08
3.4
.24
1.4
.24
1475
1285
975
(.18)
(.18)
Note: Actual RPM will vary with application and configuration.
Minimum Circuit Ampacity (MCA) and Maximum Fuse Size (MFS) Calculations for fan-
coils: (Motors only)
MCA = (1.25) x [Largest Motor Amperes (FLA)]
MFS or Heating, Air-Conditioning, and Refrigeration (HACR) Type Circuit Breaker = 15
amps for all fan-coils without electric heat
Table B-ED.4. Decimal to Fractional HP (kW)
Conversion
Unit Size
Decimal
Fraction
04
.04
1/25
.06
1/16
.10
1/10
.13
1/8
06
.09
1/11
.12
1/8
.18
1/6
.24
1/4
08
.10
1/10
.13
1/8
.18
1/6
.24
1/4
Basic Series