Electrical Data
40
UNT-PRC001-EN
Table ED-3. Free Discharge Motors on Units with Two-Row Coils
115 Volt
208-230 Volt
277 Volt
RPM
FC
FLA
HP (kW)
FLA
HP (kW)
FLA
HP (kW)
H
M
L
02
0.6
.03 (.02)
0.3
.03 (.02)
0.2
.03 (.02)
980
840
655
03
0.7
.04 (.02)
0.4
.04 (.02)
0.3
.04 (.02)
980
780
580
04
0.9
.05 (.04)
0.5
.05 (.04)
0.4
.05 (.04)
1050
780
580
06
1.2
.07 (.05)
0.6
.07 (.05)
0.5
.07 (.05)
1030
780
580
08
1.4
.12 (.09)
0.9
.12 (.09)
0.6
.12 (.09)
1080
800
600
10
0.9
1.2
.05 (.04)
.07 (.05)
0.5
0.6
.05 (.04) .07 (.05)
0.4
0.5
.05 (.04) .07 (.05)
1050
780
580
1030
780
580
12
0.9
1.4
.05 (.04)
.12 (.09)
0.5
0.9
.05 (.04) .12 (.09)
0.4
0.6
.05 (.04) .12 (.09)
1050
780
580
108
800
600
Table ED-4. High Static Motors on Units with Two-Row Coils
115 Volt
208-230 Volt
277 Volt
RPM
FC
FLA
HP (kW)
FLA
HP (kW)
FLA
HP (kW)
H
M
L
02
1.1
.07 (.05)
0.6
.07 (.05)
0.5
.07 (.05)
1480
1110
865
03
1.4
.08 (.06)
0.7
.08 (.06)
0.6
.08 (.06)
1400
1175
860
04
1.6
.10 (.07)
0.8
.10 (.07)
0.7
.10 (.07)
1475
1315
1070
06
2.6
.16 (.12)
1.2
.16 (.12)
1.0
.16 (.12)
1400
1070
855
08
3.4
.24 (.18)
1.4
.24 (.18)
1.1
.24 (.18)
1475
1285
975
10
1.6
2.6
.10 (.07)
.16 (.12)
0.8
1.2
.10 (.07) .16 (.12)
0.7
1.0
.10 (.07) .16 (.12)
1475
1315
1070
1400
1070
855
12
1.6
3.4
.10 (.07)
.24 (.18)
0.5
0.9
.10 (.07) .24 (.18)
0.7
1.1
.10 (.12) .24 (.18)
1475
1315
1240
1475
1285
975
Note:
Actual rpm will vary with application and configuration
Table ED-5. Free Discharge Motors on Units with Three and Four-Row Coils
115 Volt
208-230 Volt
277 Volt
RPM
FC
FLA
HP (kW)
FLA
HP (kW)
FLA
HP (kW)
H
M
L
02
0.6
.03 (.02)
0.3
.03 (.02)
0.2
.03 (.02)
980
840
655
03
0.8
.05 (.04)
0.5
.05 (.04)
0.4
.05 (.04)
1080
800
600
04
1.0
.06 (.04)
0.6
.06 (.04)
0.5
.06 (.04)
1080
800
600
06
1.4
.12 (.09)
0.9
.12 (.09)
0.6
.12 (.09)
1080
800
600
08
1.7
.13 (.10)
1.0
.13 (.10)
0.8
.13 (.10)
1080
800
600
10
1.0
1.4
.06 (.04)
.12 (.09)
0.6
0.9
.06 (.04) .12 (.09)
0.5
0.6
.06 (.04) .12 (.09)
1080
800
600
1080
800
600
12
1.0
1.7
.06 (.04)
.13 (.10)
0.6
1.0
.06 (.04) .13 (.10)
0.5
0.8
.06 (.04) .13 (.10)
1080
800
600
1080
800
600
Table ED-6. High Static Motors on Units with Three and Four-Row Coils
115 Volt
208-230 Volt
277 Volt
RPM
FC
FLA
HP (kW)
FLA
HP (kW)
FLA
HP (kW)
H
M
L
02
1.1
.07 (.05)
0.6
.07 (.05)
0.5
.07 (.05)
1480
1110
865
03
1.3
.08 (.06)
0.7
.08 (.06)
0.5
.08 (.06)
1500
1355
1110
04
2.1
.13 (.10)
0.9
.13 (.10)
0.7
.13 (.10)
1580
1375
1240
06
3.4
.24 (.18)
1.4
.24 (.18)
1.1
.24 (.18)
1475
1285
975
08
3.4
.24 (.18)
1.4
.24 (.18)
1.1
.24 (.18)
1475
1285
975
10
2.1
3.4
.13 (.10)
.24 (.18)
0.9
1.4
.13 (.10) .24 (.18)
0.7
1.1
.13 (.10) .24 (.18)
1580
1375
1240
1475
1285
975
12
2.1
3.4
.13 (.10)
.24 (.18)
0.9
1.4
.13 (.10) .24 (.18)
0.7
1.1
.13 (.10 ) .24 (.18)
1580
1375
1240
1475
1285
975
Note:
Actual rpm will vary with application and configuration.