background image

10

Wire specification (RS1 & RS2): 2 conductors, 18 gauge wire.  Make sure that the sensor wires have a cable separate from the thermostat 
cable.  Best results for distances of 100 feet or less.  Accuracy may be affected for distances up to a maximum of 200 feet.  Shielded cable is 
recommended for distances over 100 feet and less than 200 feet.

 CAUTION: Keep this wiring at least one foot away from large inductive loads such as electronic air cleaners, motors, 

line starters, lightning ballasts, and large distribution panels.  Failure to follow these wiring practices may introduce electrical 
interference (noise) which can cause erratic system operation.  Shielded cable is required if the above wiring guidelines cannot be 
met.  Be sure to ground only one end of the shield to the thermostat common terminal.  Tape back the other end of the shield.

Remote Sensors Part Numbers

Remote Indoor Sensor:  Use ZZSENSAL0400AA for indoor applications.
Remote Outdoor Sensor:  Use BAYSEN01ATEMPA for outdoor applications.

Î

Î

IMPORTANT:  Make sure that the sensor wires have a cable separate from the thermostat cable.

Î

Î

IMPORTANT:  Follow directions below for averaging.  These instructions replace the averaging information found in the Installer’s 
Guide for the ZZSENSAL0400AA.

Î

Î

Note:  Remote Sensor 2 can be selected as an indoor sensor or an outdoor sensor. 

Remote Temperature Sensor Connections and Operation:

A)  Indoor sensor connected to RS1.  Replaces internal sensor.  RS2 not connected. 

Remote Sensor 1 (RS1) replaces the internal 
temperature sensor of the thermostat. This allows the 
thermostat to be installed in a location different than 
the area where the temperature will be measured.  Use 
ZZSENSAL0400AA.   See Figure A.

B)  Indoor sensor connected to RS2.  Averages 

temperature with internal sensor.  RS1 not 
connected.

RS2 is used as an indoor temperature sensor that 
averages temperatures with the internal sensor.  Use 
ZZSENSAL0400AA.  See Figure B.
If RS2 is set to indoor location (“IN” - Default selection in 
the thermostat installation set up menu) and a sensor is 
attached to the RS2 sensor terminals of the thermostat, 
the RS2 temperature is averaged with the thermostats 
internal temperature sensor.

C)  Indoor sensors connected to RS1 and RS2.  

Averages RS1 and RS2 sensor temperatures.  
Internal sensor is not used.

Remote Sensor 1 (RS1) and Remote Sensor 2 (RS2) 
are both used as indoor sensors.  The RS1 temperature 
and RS2 temperature is averaged.  See Figure C.

D)  Outdoor sensor connected to RS2.  Reports 

outdoor temperature to comfort control.

RS2 is used as an outdoor temperature sensor.  Use 
BAYSEN01ATEMPA.  See Figure B.  
If RS2 is set to outdoor location (“OUT” in the thermostat installation set up menu) and a sensor is attached to the RS2 sensor terminals 
of the thermostat, the RS2 temperature is used to report outdoor temperature.  It is also displayed on the thermostat main screen.  See 
Step 19 to configure for outdoor temperature sensing.

E)  Indoor sensor connected to RS1 and Outdoor sensor connected to RS2.  RS1 replaces the internal sensor.  RS2 reads the 

outdoor temperature.

Remote Sensor 1 (RS1) replaces the internal temperature sensor of the thermostat. This allows the thermostat to be installed in a 
location different than the area where the temperature will be measured.  Use ZZSENSAL0400AA. 
RS2 is used as an outdoor temperature sensor.  Use BAYSEN01ATEMPA.  See Figure C.
If RS2 is set to outdoor location (“OUT” in the thermostat installation set up menu) and a sensor is attached to the RS2 sensor terminals 
of the thermostat, the RS2 temperature is used to report outdoor temperature.  It is also displayed on the thermostat main screen.  See 
Step 19 to configure for outdoor temperature sensing.

RS1 Sensor 

Remote Temp Sensor 

Figure A 

Sensor wiring is 
not polarized. 

Black 

Red 

RS1 

RS1 

RS2 

RS2 

RS2 Sensor 

RS2 

Remote Temp Sensor

Sensor wiring is 
not polarized. 

Black 

Red 

Figure B 

RS1 

RS1 

RS2 

RS2 

RS2 Sensor 

Figure C

RS1 Sensor 

Remote Temp Sensor 

Black 

Red 

RS1 

RS1 

RS2 

RS2 

RS2 

Remote Temp Sensor

Sensor wiring is 
not polarized. 

Black 

Red 

Optional Remote Temperature Sensors Installation - TZEMT500 Only

Содержание TZEMT400

Страница 1: ...s or oil furnace heat pump combined without adding a dual fuel accessory relay kit These thermostats do not have an emergency heat relay when applied with a dual fuel relay kit NOTE A 24 Volt common a...

Страница 2: ...or COM with a wire connected to it skip to step 6 b If your thermostat does not have a C X B or COM terminal or does not have a wire connected to it go to step 5 2 Remove the existing thermostat cove...

Страница 3: ...e the air handler or furnace panel This wire bundle is routed from the thermostat through the walls and into the air handler or furnace panel This bundle can be identified at the air handler or furnac...

Страница 4: ...24RC 24RH W1 W2 O B G Y1 Y2 Chart 2 Heat Pump Single Stage or Multistage Themostat Being Replaced Wire Labels Trane American Standard Weathertron or York COM C B R RC RH E X2 W W1 W2 Y AUX O G Y Y1 Y...

Страница 5: ...ncy RF communication between the thermostat and the Z waveTM bridge 24 C 24 RC 24 RH W1 G Y1 RS1 RS1 RS2 RS2 W2 0 B Y2 Wall plate Tabs 9 Mark two mounting holes using new wall plate a Pull wires throu...

Страница 6: ...24C 24RC 24RH W1 W2 0 G Y1 Y2 Field Wiring Diagrams TZEMT500 11 Install new wall plate a Pull wires through hole in center of wall plate b Locate the new wall plate over existing opening c Attach wal...

Страница 7: ...contains one 2 stage scroll compressor Note 5 The remote sensor feature is available only on the TZEMT500 Note 2 Note 2 YLO Outdoor Unit Compressor Stage 1 Y1 24VAC Return R 24VAC Common B Compressor...

Страница 8: ...oor sensor connected to RS1 Replaces internal sensor RS2 not connected Indoor sensor connected to RS2 Averages temperature with internal sensor RS1 not connected Indoor sensors connected to RS1 and RS...

Страница 9: ...ne terminal block with 8 terminals See the table below for a comparison of the terminal names Functionality is the same for the matching terminals Terminal Labels TZEMT500 TZEMT400 24C C 24V 24RC RC 2...

Страница 10: ...oor location IN Default selection in the thermostat installation set up menu and a sensor is attached to the RS2 sensor terminals of the thermostat the RS2 temperature is averaged with the thermostats...

Страница 11: ...2 2 2 O T R E P M U J T U C H R C R T I L P S TZEMT500 TZEMT400 15 Turn power to heating and cooling system back on The thermostat display should turn on and begin displaying information If the therm...

Страница 12: ...t option then press the Select button Done Select Menu Selection User Settings Usage Graph ESM Setpoints ZWave Install Select button Scroll up Scroll down c Scroll up or down to Set Clock it is the fi...

Страница 13: ...ntinue with steps g through j g Scroll down to 2nd Stage Heat h Press the button to change the setting to Y for Yes i If your system also has 2nd stage cooling scroll down to 2nd Stage Cool and Press...

Страница 14: ...and that each wire is securely attached to the appropriate terminal Also go back and verify that you have set up the Mechanical Settings to match your System Type FAN button MODE button MENU MODE FAN...

Страница 15: ...he steps Study the steps below before beginning b Press and release the plus button on the bridge c Press the MENU button on the thermostat d Scroll down to Z Wave Install and press the Select button...

Страница 16: ...plete when the orange light becomes solid Z Wave controllers from various manufacturers may support the Z Wave Thermostat General V2 Device class used by the Trane Z Wave Thermostat If you are using a...

Страница 17: ...button As you navigate through menus the labels for the buttons will change Setpoint Display and Setpoint Up Down Buttons The current heat and cool setpoints are displayed These setpoints may be set u...

Страница 18: ...mode Auto Fan on when cooling heating is necessary On Fan constantly on Schedule Mode Used to change the schedule mode Hold System maintains the current temperature setpoints Schedules are disregarde...

Страница 19: ...pressing and holding the two middle buttons until the Installer Settings appear Installer Settings Hidden Display Lock System Settings Mechanical Settings Type Fan Type C O Type 2nd Stage Heat Aux He...

Страница 20: ...press the Reset button to reset the Filter Runtime value to zero View Reset Filter Runtime 1 Press the MENU button 2 Scroll to User Settings and press the Select button 3 Scroll to Filter Service and...

Страница 21: ...disabled the runtime counter will continue to count the runtime but the maintenance service indicator will never be displayed 1 Press the MENU button 2 Scroll to User Settings and press the Select bu...

Страница 22: ...rature is 77 and the number of degrees of offset being applied is 1 Change the Sensor Calibration 1 Press the MENU button 2 Scroll to User Settings and press the Select button 3 Scroll to Sensor Calib...

Страница 23: ...r of seconds The backlight time out can be set between 0 and 120 seconds Thirty 30 is the default setting When set to Zero 0 the backlight will remain always on Adjust the Contrast 1 Press the MENU bu...

Страница 24: ...may be Standard or Heat Pump Fan Type Gas Fan type may be Gas or Elect electric Item Description TZEMT400AB32 Model Number Ver 01 00 10 Firmware version number may vary ZVER 02 00 9 Z Wave version num...

Страница 25: ...ccessed but no menu options may be selected The Installer Settings hidden button operation is always operational allowing Display Lock to be turned off Max Heat SP 55F to 90F 12C 32C 90F 32C Sets the...

Страница 26: ...covery the 4th status line will be labeled Recov Recovery works in heat or cool mode While in recovery the Aux Heat stage will never engage Maximum Smart Recovery time is one hour H C Delta 3 15 degre...

Страница 27: ...eat Pump system 2nd Stage Cool Y or N N Enables the 2nd Stage Cool operation Fan Cycler Settings Changing these settings will affect the operation of the heating cooling system To view and edit these...

Страница 28: ...ed 3 Scroll to Systems Settings and press the Select button 4 Scroll to Sched Enable and press the plus button to enable scheduling or the minus button to disable scheduling When scheduling is enabled...

Страница 29: ...the left or right arrow buttons Then press the plus or minus buttons as necessary Continue pressing the left or right arrow buttons to move to the next line Copy a Day Schedule 1 Press the MENU butto...

Страница 30: ...system is running On Heat On Heating Minimum Run Time MRT See Installer Settings on page 25 for more information LED 2 Green System Stage display Off None 1st stage heating or cooling On 2nd Stg Stage...

Страница 31: ...t control if it is damaged while in your possession including but not limited to 1 damage caused by unreasonable use of the low voltage room comfort control 2 damage from failure to properly maintain...

Страница 32: ...tinuous product and product data improvement and it reserves the right to change design and specifications without notice Literature Order Number File number Supersedes Date 2010 Schlage Lock Company...

Отзывы: